Plan Review Details - Permit 19030804
Plan Review Stops For Permit 19030804
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-05-22 Cont ID  
Sent By thunt Date 2019-05-22 Time 16:03 Rev Time 0.00
Received By thunt Date 2019-05-22 Time 16:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-20 Cont ID  
Sent By thunt Date 2019-05-20 Time 10:24 Rev Time 0.00
Received By thunt Date 2019-05-20 Time 10:24 Sent To  
Notes
2019-05-20 10:28:45GAS 1ST REVIEW**DENIED**
  
  
 1) GENERATOR APPOVED UNDER MASTER # 19030804 IS A 22KW.
 GAS ISOMETRIC IS CALLING OUT FOR A 27 KW 405,000BTU.
 PROVIDE GENERATOR INSTALLATION MANUAL. MASTER WILL NEED
 REVISION. FBC 107.2.1
  
 2) REMOVE OLD ISOMETRIC FROM PACKET. FBC 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-22 Cont ID  
Sent By thunt Date 2019-05-22 Time 16:04 Rev Time 0.00
Received By thunt Date 2019-05-21 Time 13:53 Sent To  
Notes
2019-05-22 13:53:57RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-20 Cont ID  
Sent By lmarchan Date 2019-05-20 Time 11:57 Rev Time 0.00
Received By lmarchan Date 2019-05-16 Time 11:22 Sent To  
Notes
2019-05-17 11:23:03RESUB ROUTED TO THUNT