Plan Review Details - Permit 19030803
Plan Review Stops For Permit 19030803
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-16 Cont ID  
Sent By jleahy Date 2019-04-16 Time 10:18 Rev Time 0.00
Received By jleahy Date 2019-04-16 Time 10:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By jleahy Date 2019-04-25 Time 08:39 Rev Time 0.00
Received By jleahy Date 2019-04-25 Time 08:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-05 Cont ID  
Sent By jleahy Date 2019-04-05 Time 11:51 Rev Time 0.00
Received By jleahy Date 2019-04-05 Time 11:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-05-08 Cont ID  
Sent By rmcdouga Date 2019-05-08 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2019-05-08 Time 13:27 Sent To  
Notes
2019-05-08 13:27:34SEPARATE PERMIT FOR GAS.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-04-25 Cont ID  
Sent By thunt Date 2019-04-25 Time 10:32 Rev Time 0.00
Received By thunt Date 2019-04-25 Time 10:32 Sent To  
Notes
2019-04-25 10:34:30GAS 2ND REVIEW**DENIED** 2ND REQUEST ON ALL COMMENTS**
 I WOULD RECOMMEND YOU COMING IN FOR A REVIEW OF YOUR
 PLANS BEFORE RE-SUBMITTAL.
  
 **PLEASE NOTE FL ST 553.80 (B)2B WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) NOT ADDRESSED. PROVIDE MATERIAL AND PIPE SIZE
 LEAVING THE GAS METER THAT YOU ARE CONNECTING
 INTO.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 2) NOT ADDRESSED. YOU MUST SHOW ALL APPLIANCES. YOU ARE
 MISSING THE WATER HEATER, THE 2ND BBQ LISTED ON
 PERMIT#02071266, AND YOU LISTED THE POOL HEATER ON YOU
 PLAN BUT NOT THE BTU'S FOR IT. THE PLANS INDICATE AN
 EXISTING GAS METER. THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 3) NOT ADDRESSED. CITY RECORDS SHOW THIS EXISTING
 SYSTEM AS 12" W.C AND NOT 2PSI AS YOU CALL OUT. PLEASE
 CLARIFY IS IT YOUR INTEND TO UPGRADE THE GAS METER AND
 INSTALL PRESSURE REGS FOR ALL OTHER APPLIANCES? FBC-R G
 2413.2, 2413.4.3
  
 4) PROVIDE A COMPLETE AND ACCURATE GAS ISOMETRIC
 DRAWING. FBC 107.3.5
  
 5) YOU SUBMITTED DOCUMENTS CONFLICT WITH EACH OTHER.
 ONE SHEET CALL OUT 330,000 BTU'S @ 10' P.E PIPING , THE
 NEXT PAGE CALLS OUT 330,000 BTU'S @ 15' P.E AND THE
 LATEST SUBMITTAL CALLS OUT 350,000 BTU'S @ 20' P.E
 PIPING. PLEASE CLARIFY AND REMOVE ALL PAGES THAT ARE
 NOT PART OF THE DESIGN. FBC 107.2.1
  
 6) NEW COMMENT: IF 2LB SYSTEM. AT SOME POINT THE SYSTEM
 WILL TRANSITION TO SCH 40 METAL PIPING @ .5LB. PROVIDE
 ANY AND ALL SIZING TABLES NEEDED TO PROPERLY SIZE THIS
 SYSTEM. SUBMIT TWO COPIES OF ALL APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN
 THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
  
 7) NEW COMMENT: IF 2LB SYSTEM. SHOW THE LOCATION OF ALL
 MP (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL
 BE INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 2017 FBC-FUEL GAS SEC.409.4, FBC-RESIDENTIAL SEC. G
 2420.4.
  
 8) NEW COMMENT: IF 2LB SYSTEM. SHOW THE DISTANCE FROM
 THE 2 PSI REGULATOR TO THE APPLIANCE. COMPLY WITH 2017
 FBC-FUEL GAS SEC. 402.4.1 OR 2017 FBC-RES. SEC.
 G2413.4.1, G2413.4.2 FOR THE PROPER PIPE SIZE AND BTU
 LOAD.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-03-27 Cont ID  
Sent By thunt Date 2019-03-27 Time 17:37 Rev Time 0.00
Received By thunt Date 2019-03-27 Time 17:37 Sent To  
Notes
2019-03-27 17:37:31GAS 1ST REVIEW**DENIED**
  
 1) SHOW WHERE YOU ARE CONNECTING INTO THE EXISTING
 SYSTEM. PROVIDE PIPE MATERIAL AND SIZE. SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC-FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC-RES SEC. G2413.4.1,
 G2413.4.2.
  
 2) CITY RECORDS (PERMIT # 02071266 LIST OTHER GAS
 FIXTURES IN HOME. LIST THE BTU LOAD OF EACH APPLIANCE
 AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 THE PLANS
 INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 3) CITY RECORDS SHOW THIS SYSTEM AS 12" W.C AND NOT 2
 LB AS YOU CALL OUT. PLEASE CLARIFY. IS IT YOUR INTENT
 TO INSTALL PRESSURE REG'S AT ALL FIXTURES? INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN PER
 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 THRU 402.6 OR 2017
 FBC RES. SEC. G2413.2, G2413.4.3.
  
 4) PROVIDE A COMPLETE AND ACCURATE GAS ISOMETRIC
 DRAWING. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 THUNT@CGA SOLUTIONS.COM
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-25 Cont ID  
Sent By thunt Date 2019-04-25 Time 10:34 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 13:04 Sent To  
Notes
2019-04-17 13:04:14RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-16 Cont ID  
Sent By jleahy Date 2019-04-16 Time 10:19 Rev Time 0.00
Received By jleahy Date 2019-04-16 Time 10:19 Sent To  
Notes
2019-03-19 13:21:29ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-27 Cont ID  
Sent By mcruz Date 2019-03-27 Time 09:11 Rev Time 0.00
Received By mcruz Date 2019-03-27 Time 09:02 Sent To  
Notes
***NONE***