Plan Review Details - Permit 19030753
Plan Review Stops For Permit 19030753
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-10 Cont ID  
Sent By cthroop Date 2019-06-10 Time 07:28 Rev Time 0.00
Received By cthroop Date 2019-06-10 Time 07:27 Sent To  
Notes
2019-06-10 07:28:26SIGNATURE REVIEW OK. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-06 Cont ID  
Sent By jduprey Date 2019-05-06 Time 11:49 Rev Time 0.00
Received By jduprey Date 2019-05-06 Time 11:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-22 Cont ID  
Sent By jduprey Date 2019-04-22 Time 08:47 Rev Time 0.00
Received By jduprey Date 2019-04-22 Time 07:57 Sent To  
Notes
2019-04-22 08:56:52BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ON DRAWING SHEET G1.0 UNDER BUILDING INFO, SPECIFY
 THE USE OF THE 2014 FBC 5TH EDITION. THE CURRENT
 BUILDING CODE IS THE 2017 FBC 6TH EDITION. PLEASE
 VERIFY AND RE-SUBMIT. FBC 107
  
 2. DRAWING SHEET A1.0 UNDER GENERAL FLOOR NOTES, NOTE
 NUMBER 7 INDICATES "CONCRETE USED TO PATCH ANY
 PENETRATION MUST MATH EXISTING ADJACENT SLAB THICKNESS,
 REIFORCEMENT AND TREATED WITH CRETSEAL APPLICATION TO
 PREVENT MOISTURE MIGRATION" HOWEVER NO STRUCTURAL
 DETAIL WAS PROVIDED. PLEASE PROVIDE A STRUCTURAL DETAIL
 WERE SHOWS CONNECTION BETWEEN EXISTING SLAB ON GRADE
 AND THE SPECIFICS FOR THE REPAIR. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-29 Cont ID  
Sent By jleahy Date 2019-03-29 Time 16:49 Rev Time 0.00
Received By jleahy Date 2019-03-29 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-24 Cont ID  
Sent By pleduc Date 2019-05-24 Time   Rev Time 0.00
Received By pleduc Date 2019-05-24 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-05-15 Cont ID  
Sent By sathomas Date 2019-05-15 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-05-15 Time 00:00 Sent To I
Notes
2019-05-15 10:30:27THE FOLLOWING COMMENTS WERE SUBMITTED BY SANDRA THOMAS,
 FIRE INVESTIGATOR, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 1. COVER PAGE SUGGESTS BUILDING IS UNSPRINKLERED, WHILE
 PAGE FP-100 ILLUSTRATES SPRINKLERS TO BE INSTALLED.
  
 2. 1 HR. DEMISING WALL ON PAGE G-003 IS BASED ON HAVING
 A SPRINKLERED BUILDING, WHICH AGAIN CONTRADICTS WHAT IS
 DEPICTED ON PAGE FP-100.
  
 3. PAGE E-200 NOTES # 32 & 35 SUGGEST A FIRE ALARM
 SYSTEM TO BE INSTALLED. CLARIFICATION IS NEEDED.
  
 WHERE APPLICABLE:
  
 ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A CERTIFIED
 FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA 72. A
 SEPARATE SHOP DRAWING IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY WORK ON THE SYSTEM.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE
 COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND
 SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE
 REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE
 FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-25 Cont ID  
Sent By scaldero Date 2019-03-25 Time 09:12 Rev Time 0.00
Received By scaldero Date 2019-03-25 Time 09:01 Sent To  
Notes
2019-03-25 09:15:06PERMIT # 19030753
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 3) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 4) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 5) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO
 THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 6) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-10 Cont ID  
Sent By cthroop Date 2019-06-10 Time 07:29 Rev Time 0.00
Received By cthroop Date 2019-05-23 Time 10:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 07:28 Rev Time 0.00
Received By shill Date 2019-05-02 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-22 Cont ID  
Sent By jduprey Date 2019-04-22 Time 08:58 Rev Time 0.00
Received By jduprey Date 2019-03-18 Time 10:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-04-22 Cont ID  
Sent By jduprey Date 2019-04-22 Time 08:58 Rev Time 0.00
Received By jduprey Date 2019-04-22 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-06-06 Cont ID  
Sent By ccole Date 2019-06-06 Time 16:36 Rev Time 0.00
Received By ccole Date 2019-06-06 Time 16:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By ccole Date 2019-05-13 Time 14:43 Rev Time 0.00
Received By ccole Date 2019-05-13 Time 14:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By ccole Date 2019-04-10 Time 15:17 Rev Time 0.00
Received By ccole Date 2019-04-10 Time 14:44 Sent To  
Notes
2019-04-10 15:27:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19030753
 4/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.0: REFER TO SECTION 510.1 FBC M AND
 DESCRIBE THE ACTIVITIES AND PROCESSES THAT TAKE PLACE
 IN THE LAB AND WHAT MATERIALS OR CHEMICALS ARE USED AND
 STORED THERE. IF THIS ROOM IS CLASSIFED AS A LAB THEN
 AN EXHAUST VENTILATION SYSTEM IS REQUIRED, AND
 RECIRCULATION OF AIR FROM THE ROOM IS PROHIBITED- TABLE
 403.3.1.1 FBC M. PLEASE PROVIDE EXPALNATORY NOTES ON
 THE PLAN TO CLARIY. IF THIS ROOM IS NOT A LAB, PLEASE
 CHANGE THE NAME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-05 Cont ID  
Sent By gjohnson Date 2019-06-05 Time 14:10 Rev Time 0.00
Received By gjohnson Date 2019-06-05 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 16:00 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 14:33 Sent To  
Notes
2019-05-07 16:00:29PLUMBING 2ND REVIEW**DENIED** PLEASE NOTE FL ST 553.80
 (B)2B WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
 1) ANSWERED
  
 2) NOT ADDRESSED: YOU PROVIDED A PARALLEL APPROACH BUT
 DID NOT CENTER THE FIXTURE ON THE CLEAR FLOOR SPACE.
 SHT A3.0 WAS NOT REVISED AND IS STILL SHOWING CABINET
 HEIGHT AS 3'0". COMMENT: BOTH THE EXAM ROOM AND PRETEST
 SINK SHALL COMPLY WITH FBC-A 212.3 AS AT LEAST 1 OF
 EACH TYPE SHALL BE PROVIDED IN EACH ACCESSIBLE ROOM.
 PROVIDE CLEAR FLOOR SPACE, TURNING SPACE, AND COUNTER
 TOP HEIGHT OF 34" ON PLAN. FBC-A 606
  
 3) ANSWERED
  
 4) ANSWERED
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-08 Cont ID  
Sent By thunt Date 2019-04-08 Time 14:14 Rev Time 0.00
Received By thunt Date 2019-04-08 Time 13:14 Sent To  
Notes
2019-04-08 14:14:41PLUMBING 1ST REVIEW**DENIED**
  
 1) COVER PAGE LIST CODES IN PLACE AS FBC 210 AND 2014.
 AS OF 12/31/2107 WE ARE CURRENTLY USING THE 2017 FBC.
 THIS PROJECT WOULD FALL UNDER THE THE 2017 6TH ED
 EXISTING BUILDING CODES CHAPTERS 7,8,9.
  
 2) BOTH THE EXAM ROOM AND PRETEST SINK SHALL COMPLY
 WITH FBC-A 212.3 AS AT LEAST 1 OF EACH TYPE SHALL BE
 PROVIDED IN EACH ACCESSIBLE ROOM. PROVIDE CLEAR FLOOR
 SPACE, TURNING SPACE, AND COUNTER TOP HEIGHT OF 34" ON
 PLAN. FBC-A 606
  
 3) SHT. P3.0. YOU MUST PROVIDE A AN APPROVED ASSE 1070
 DEVICE FOR TEMPERING HANDSINKS. FBC-P 607.1.2.
 TEMPERING WATER MY MEANS OF THE WATER HEATERS CONTROLS
 IS NOT PERMITTED. FBC-P 607.1.1
  
 4) PROVIDE NOTE ON PLAN THE NEW SINKS SHALL DISCHARGE
 DOWNSTREAM OF THE BATHROOM GROUP WET VENT. FBC 912.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-06-10 Cont ID  
Sent By cthroop Date 2019-06-10 Time 07:28 Rev Time 0.00
Received By cthroop Date 2019-06-10 Time 07:26 Sent To  
Notes
2019-06-10 07:29:32VERIFIED DIGITAL SIG. & SEAL ON PAGES M1.0 & P2.0. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-05-08 Cont ID  
Sent By thunt Date 2019-05-08 Time 15:54 Rev Time 0.00
Received By thunt Date 2019-05-06 Time 11:53 Sent To  
Notes
2019-05-13 14:47:10SHEET M1.0 DOES NOT HAVE ELECTRONIC SIGNATURE AND SEAL,
 OR TITLE BLOCK- SECTION 61G15-23.002 & 23.005 FAC.
2019-05-08 15:53:57BOTH PLUMBING AND MECHANICAL PAGES LACK TITLE BLOCK AND
 DIGITAL SIGNATURE AS REQUIRED FAC 61G15-23.003
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
2019-05-06 11:54:06BUILDING - OK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-04-22 Cont ID  
Sent By jduprey Date 2019-04-22 Time 08:58 Rev Time 0.00
Received By jduprey Date 2019-04-22 Time 08:57 Sent To  
Notes
2019-03-19 10:29:29DIGITALLY SIGNED P2.0 IS UNDER "SIGNATURES"

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By eschneid Date 2019-05-08 Time 11:24 Rev Time 0.25
Received By eschneid Date 2019-05-08 Time 11:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 16:05 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 16:05 Sent To  
Notes
2019-05-07 16:07:34WRONG COMMENTS ENTERED

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-08 Cont ID  
Sent By eschneid Date 2019-04-08 Time 14:30 Rev Time 0.50
Received By eschneid Date 2019-04-08 Time 14:08 Sent To  
Notes
***NONE***