Plan Review Details - Permit 19030585
Plan Review Stops For Permit 19030585
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By shill Date 2019-06-04 Time 08:56 Rev Time 0.00
Received By shill Date 2019-06-04 Time 08:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 17:52 Rev Time 0.00
Received By shill Date 2019-04-30 Time 17:23 Sent To  
Notes
2019-04-30 17:51:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, REMOVE THE YELLOW HIGHLIGHTING WHICH IS ON
 EVERY PAGE AS IT MAKES THE PLAN DIFFICULT TO READ.
  
 2. FBC 107, SHEET A1 SHOWS AN "EXISTING ELEVATOR LOBBY"
 BUT THE RATING DOES NOT APPEAR TO BE CONTINUOUS, PLEASE
 CLARIFY.
  
 3. THE ARCHITECT'S PAGES LACK A SEAL, SEE FS481.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-08 Cont ID  
Sent By fgiaquin Date 2019-06-08 Time 10:11 Rev Time 0.00
Received By fgiaquin Date 2019-06-08 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By jleahy Date 2019-04-16 Time 08:33 Rev Time 0.00
Received By jleahy Date 2019-04-16 Time 08:33 Sent To  
Notes
2019-04-16 08:35:11FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1,
 FS 471, 481

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By pleduc Date 2019-05-17 Time   Rev Time 0.00
Received By pleduc Date 2019-05-17 Time 16:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By pleduc Date 2019-04-02 Time   Rev Time 0.00
Received By pleduc Date 2019-04-01 Time 13:00 Sent To  
Notes
2019-04-01 14:20:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET T 1 - THERE ARE INDICATIONS OF FIRE SPRINKLER
 AND FIRE ALARM NOTES WITH WORK UNDER SEPARATE SHOP
 DRAWINGS; HOWEVER, NOTHING ABOUT MAINTAINING EITHER
 SYSTEMS WHILE UNDER DEMO & CONSTRUCTION.
  
 THE FS AND FA SYSTEMS SHALL REMAIN FUNCTIONAL AND BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION.
  
 PLEASE ENSURE AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 2) SHEETS A 1 & A 3 - DOOR 01 SWINGS OUT INTO THE EXIT
 CORRIDOR WHICH DOES NOT APPEAR TO ENCROACH INTO THE
 REQUIRED EGRESS WIDTH: HOWEVER, THE DOOR SWINGS AT 90'.
  
 PER NFPA 101 THE DOOR IS REQUIRED TO SWING 180'
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED,
 UNLESS BOTH
 OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE
 REQUIRED WIDTH
 OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING,
 UNLESS THE DOOR
 LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE
 AND IS NOT
 REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE
 DIRECTION OF
 EGRESS TRAVEL.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) SHEET A 3 - THERE IS AN INDICATION THAT DOOR 02
 HARDWARE AS HAVING A KEY. THIS DOOR IS INDICATED AS AN
 EXIT DOOR.
  
 PER NFPA 101 CH 38 & 7
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 4) SHEET A 3 - THERE IS AN INDICATION THAT DOOR 01
 HARDWARE AS HAVING A KEY AND DEADBOLT. THIS DOOR IS
 INDICATED AS AN EXIT DOOR.
  
 PER NFPA 101 CH 38 & 7
  
 38.2.2.2 DOORS.
 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 5) SHEET LS 1 & A 4 - DOOR 04 IS INDICATED AS AN EXIT
 THAT IS LEADING TO AN AREA AS FUTURE EXPANSION.
  
 HOW WILL THIS EXIT BE CONTROLLED AND MAINTAINED AND
 FUNCTION AS AN EXIT?
  
 PLEASE PROVIDE DETAILS
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-06-10 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-14 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 17:53 Rev Time 0.00
Received By shill Date 2019-03-26 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-06-12 Cont ID  
Sent By ccole Date 2019-06-12 Time 07:27 Rev Time 0.00
Received By ccole Date 2019-06-12 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-06-10 Cont ID  
Sent By ccole Date 2019-06-10 Time 12:38 Rev Time 0.00
Received By ccole Date 2019-06-10 Time 12:38 Sent To  
Notes
2019-06-10 12:48:142ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19030565
 6/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED M.1 FLOOR PLAN LAYOUT DOES NOT MATCH THE
 LAYOUTS SHOWN IN THE ARCHITECTURAL PLANS. WHERE THE
 ARCHITECTURAL PLANS SHOW LARGE OPEN OFFICE AND STORAGE
 AREAS, THE MECHANIOCAL PLANS SHOW THESE AREAS DIVIDED
 UP INTO VARIOUS UNIDENTIFIED ROOMS AND SPACES. PLEASE
 CORRECT- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-16 Cont ID  
Sent By ccole Date 2019-04-16 Time 08:49 Rev Time 0.00
Received By ccole Date 2019-04-16 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By shill Date 2019-06-04 Time 08:57 Rev Time 0.00
Received By shill Date 2019-06-04 Time 08:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 17:52 Rev Time 0.00
Received By shill Date 2019-04-30 Time 17:52 Sent To  
Notes
2019-04-30 17:52:43ARCHITECTURAL, ELECTRICAL, MECHANICAL PAGES LACK A
 SIGNATURE AND SEAL, FS471.
  
  
2019-04-16 08:37:00ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED BY
 THE DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC
 107.2.1, FS 471, 481 JLEAHY 4/16/19
2019-04-16 08:30:52MECH PLANS NOT DIGITALLY SIGNED AND SEALED.