Plan Review Details - Permit 19030553
Plan Review Stops For Permit 19030553
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By pvalenti Date 2019-04-02 Time 16:11 Rev Time 0.00
Received By pvalenti Date 2019-04-02 Time 16:10 Sent To  
Notes
2019-04-02 17:30:23***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC ER = FBC ENERGY RESIDENTIAL
 FBC BRS = FBC BUILDING REFERENCED STANDARDS (AWS =
 AMERICAN WELDING SOCIETY)
  
 BUILDING REVIEW DENIED:
  
 1. FBC B 107.2.1 THE FOUNDATION/FOOTING DETAILS ARE NOT
 COMPLETE:
 A. FOOTING DIMENSIONS ARE NOT COMPLETE
 B. FOOTING REINFORCEMENT IS NOT COMPLETE
 C. EMBEDDED STEEL PLATES WITH 12" LONG DOWEL DETAILS
 ARE NOT COMPLETE (MISSING TYPE OF STEEL, DIAMETER, &
 WELDING SPECS)
 PROVISO: IN ADDITION TO THE REQUIREMENTS ABOVE,BEARING
 CAPACITY/SOIL COMPACTION TEST RESULTS/TERMITE
 TREATMENT/FORM BOARD SURVEY CAN BE ON-SITE AT TIME OF
 INSPECTION.
  
 2. FBC B 107.2.1 THE HANDRAIL TO MAIN STRUCTURE
 CONNECTIONS ARE NOT CLEAR.
  
 3. FBC R 310.2.1 THE 1ST FLOOR BEDROOM WINDOW SIZE
 (CLEAR OPENING IS TOO SMALL).
  
 4. FBC B 107.2.1 & FBC R 903.2 THE LOW ROOF AT SIDE
 ENTRY IS MISSING DETAILS FOR THE STRUCTURAL CONNECTIONS
 TO THE BUILDING AND ROOF FLASHING.
  
 5. FBC B 310 ACCORDING TO THE PLAN DETAILS THE
 OCCUPANCY CLASSIFICATION SHOULD BE "R-3".
  
 6. FBC ER 401.2 ENERGY CALCULATIONS FOR THE STRUCTURE
 ARE REQUIRED.
 PROVISO: IN ADDITION TO REQUIREMENTS ABOVE, BUILDING
 THERMAL ENVELOPE TESTING WILL BE REQUIRED PRIOR TO
 FINAL INSPECTION.
  
 7. FBC B 107.2.1 & FBC R 316.3 THE PRODUCT APPROVALS
 FOR ICENYNE INSULATION (INCLUDING FLAME SPREAD TEST
 RESULTS) ARE REQUIRED.
  
 8. FBC R 903.2, FBC R 903.4, & FBC R 904.2 THE PLANS
 NEED TO SHOW WOOD DECKING AS A ROOF SUBSTRATE TO MATCH
 THE SUBMITTED N.O.A. 17-0824.09 FOR POLY-GLASS MODIFIED
 BITUMEN ROOF SYSTEM OVER WOOD DECKS AND INDICATE WHICH
 SYSTEM FROM WITHIN THE N.O.A. WILL BE USED.
  
 9. FBC B 107.2.1 & FBC BRS = AWS D1.1 THE PLANS
 INDICATE SEVERAL AREAS WHERE WELDING IS REQUIRED, BUT
 HAVE MINIMAL DETAILS AT: FOOTING BASE PLATES, COLUMN
 CONNECTIONS, WINDOW FRAMING, & JOINING OF CONTAINERS.
 PROVIDE MORE DETAILED INFORMATION ON PLANS.
 PROVISO: IN ADDITION TO THE REQUIREMENTS ABOVE, AWS
 D1.1 CLAUSE 3.1 (WELD PROCEDURE SPECIFICATION/SHOWS
 ESSENTIAL VARIABLES) & CLAUSE 4.2.2 (WELD PERFORMANCE
 QUALIFICATION RECORD/SHOWS WELDERS CERTS) ARE REQUIRED
 AT TIME OF INSPECTION.
  
 10. FBC B 107.2 PROVIDE ENGINEER OF RECORD SIGNED AND
 SEALED LETTER APPROVING THE EXISTING CONDITION FOR THE
 1ST, 2ND, AND ROOF LEVEL STRUCTURAL DECKS.
  
 11. FBC B 107.2.1.3 PROVIDE ENGINEER OF RECORD ANALYSIS
 & CALCULATIONS APPROVING ALL LOADS, AND CONFIGURATIONS
 OF CONTAINERS.
  
 12. PLEASE PROVIDE A BREAK DOWN OF VALUATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By jpearson Date 2019-03-26 Time 09:04 Rev Time 0.00
Received By jpearson Date 2019-03-25 Time 12:50 Sent To  
Notes
2019-03-26 09:04:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 2/0 ALUMINUM CONDUCTORS FOR THE
 FEED TO THE INTERIOR PANEL WITH A 1/0 ALUMINUM GROUNDED
 CONDUCTOR AND A # 6 COPPER EQUIPMENT GROUNDING
 CONDUCOTR. ALUMINUM CONDUCTORS OF THIS SIZE ARE NOT
 RATED FOR A 200 AMP SERVICE. ADDITIONALLY, IF YOU WANT
 TO INSTALL A REDUCED GROUNDED CONDUCTOR SIZE, A LOAD
 CALCULATION FOR THE GROUNDED CONDUCTOR IS REQUIRED.
 PROVIDE CORRECTIONS. FBC RE E3603.1
 2. THERE IS A CONFLICT ON THE PLAN IF REFERENCE TO AFCI
 PROTECTION REQUIRED. THERE IS ONE NOTE TO THE RIGHT OF
 FLOOR PLANS THAT ACCURATELY STATES THE REQUIREMENT.
 HOWEVER, THERE IS ANOTHER NOTE BELOW THE RISER DIAGRAM
 THAT INCORRECTLY STATES THE REQUIREMENT. REMOVE OR EDIT
 THE NOTE BELOW THE RISER DIAGRAM. WPB FBC 107.2.1
 3. RISER DIAGRAM SHOWS THE 2011 NEC AS BASIS FOR THE
 REQUIREMENT OF NEC 250.94. THIS IS NOT THE CURRENT
 CODE, PROVIDE CORRECTION. WPB FBC 107.2.1; FBC PREFACE
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By fmittner Date 2019-03-22 Time 15:44 Rev Time 0.00
Received By fmittner Date 2019-03-22 Time 15:44 Sent To  
Notes
2019-03-22 15:51:35ELEVATIONS DO NOT MATCH WHAT HPB APPROVED APRIL 2018

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-03 Cont ID  
Sent By cmontell Date 2019-04-03 Time 14:11 Rev Time 0.00
Received By cmontell Date 2019-04-03 Time 14:10 Sent To  
Notes
2019-03-13 13:53:33R21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By pvalenti Date 2019-04-02 Time 17:30 Rev Time 0.00
Received By pvalenti Date 2019-04-02 Time 17:30 Sent To  
Notes
2019-04-02 17:34:17***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 REVIEW DENIED:
  
 AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED.
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS FROM THE CITY AND TAKE IT TO THE COUNTY. THE
 PLANS ARE TO BE STAMPED BY THE COUNTY AND THE RECEIPT
 SHOWING THAT FEES DUE, IF APPLICABLE, ARE PROVIDED.
 THEN RETURN TO THE CITY.
 FOR MORE INFORMATION PLEASE CALL PALM BEACH COUNTY
 IMPACT FEES AT 561- 233-5025.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-03 Cont ID  
Sent By cmontell Date 2019-04-03 Time 14:10 Rev Time 0.00
Received By cmontell Date 2019-04-03 Time 14:09 Sent To I
Notes
2019-04-03 14:10:30MECHANICAL PLAN REVIEW FAIL
  
 1 NEED MECGANICAL PLANS PER FBC WPB SEC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-03-26 Cont ID  
Sent By thunt Date 2019-03-26 Time 11:17 Rev Time 0.00
Received By thunt Date 2019-03-26 Time 10:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By pvalenti Date 2019-04-02 Time 17:56 Rev Time 0.00
Received By pvalenti Date 2019-04-02 Time 17:48 Sent To  
Notes
2019-04-02 18:04:08***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC ER = FBC ENERGY RESIDENTIAL
  
 ROOFING REVIEW DENIED:
  
 1. A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF WORK.
  
 NOTE: PROVIDE CLEAR DETAILS AND INDICATE WHICH SYSTEMS
 WITHIN THE PRODUCT APPROVALS ARE TO BE USED.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By fmittner Date 2019-03-22 Time 15:44 Rev Time 0.00
Received By fmittner Date 2019-03-22 Time 15:44 Sent To  
Notes
2019-03-22 15:49:44SITE ADDRESS DOES NOT MATCH SITE PLAN


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved