Plan Review Details - Permit 19030451
Plan Review Stops For Permit 19030451
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By skennedy Date 2019-05-30 Time 12:07 Rev Time 0.00
Received By skennedy Date 2019-05-30 Time 12:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By jgomez Date 2019-03-28 Time 18:29 Rev Time 0.00
Received By jgomez Date 2019-03-28 Time 18:18 Sent To  
Notes
2019-03-28 18:38:29RESIDENTIAL (R3) INTERIOR DEMOLITION PERMIT, BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SHEET 1 OF 2 SUBMITTED WAS SIGNED AND SEALED BY A
 FLORIDA REGISTERED ARCHITECT. ARCHITECT NEED TO PROVIDE
 A TITLE BLOCK WITH ALL THE INFORMATION REQUIRED BY SEC.
 61G-16.004 FAC.
  
 2- MISSING SHEET 2 OF 2 AS NOTED ON NOTE LOCATED ON THE
 TOP OF SHEET 1 OF 2 SUBMITTED. PROVIDE COMPLETE
 DRAWINGS. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PERMIT APPLICATION SUBMITTED IS "TO DEMO THE
 EXISTING AREA THAT WERE NOT PERMITTED ORIGINALLY". THIS
 PERMIT IS FOR INTERIOR DEMOLITION ONLY NOT FOR
 CONSTRUCTION. COORDINATE WITH THE ELECTRICAL AND
 PLUMBING TRADES FOR CAPPING OF LINES. NEED PERMIT
 APPLICATION AND PLANS FOR ANY PROPOSED WORK. SEC. 105.1
 CITY AMENDMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By skennedy Date 2019-05-30 Time 12:06 Rev Time 0.00
Received By skennedy Date 2019-05-30 Time 12:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By jpearson Date 2019-03-26 Time 11:07 Rev Time 0.00
Received By jpearson Date 2019-03-26 Time 11:07 Sent To  
Notes
2019-03-26 11:07:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COMPLETE PLAN FOR REVIEW WITH DETAILED SCOPE
 OF WORK FOR ELECTRICAL. SHEET 2 IS MISSING, NO
 ELECTRICAL WORK IS DETAILED ON PLAN SUBMITTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-30 Cont ID  
Sent By skennedy Date 2019-05-30 Time 12:07 Rev Time 0.00
Received By skennedy Date 2019-05-09 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-28 Cont ID  
Sent By jgomez Date 2019-03-28 Time 18:56 Rev Time 0.00
Received By jgomez Date 2019-03-11 Time 11:10 Sent To  
Notes
2019-03-12 11:11:33R02

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By skennedy Date 2019-05-30 Time 12:07 Rev Time 0.00
Received By skennedy Date 2019-05-30 Time 12:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By thunt Date 2019-03-26 Time 07:08 Rev Time 0.00
Received By thunt Date 2019-03-26 Time 07:08 Sent To  
Notes
2019-03-26 07:08:24PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE ADDRESS ON PLAN. FBC 107.3.5
  
 2) PLAN INCOMPLETE MISSING PAGE 2. FBC 107.3.5
  
 3) PROVIDE SCOPE OF WORK. IS IT YOUR INTENT TO REMOVE
 ALL UN-PERMITTED PLUMBING WORK UP TO AND INCLUDING
 SANITARY UNDERGROUD? FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR/ PLUMBING PLANS EXAMINER