Plan Review Details - Permit 19030429
Plan Review Stops For Permit 19030429
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-20 Cont ID  
Sent By jgomez Date 2019-08-20 Time 11:10 Rev Time 0.00
Received By jgomez Date 2019-08-20 Time 07:55 Sent To  
Notes
2019-08-20 11:10:55BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 2- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF
 SPECIFYING ROOF TILE ADHESIVE, THEN NEED PRODUCT
 APPROVAL. IF SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE
 AND NUMBER OF SCREWS.
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)WINDOW MULLIONS AND SPECIFY MULLION SIZE.
 B) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. AND CLEARLY MARK PADDY SIZE.
 C) DOUBLE DOORS AS SHOWN FOR NEW STORAGE.
 D) RIDGE VENT SPECIFIED BY THE ENGINEER OF RECORD ON
 PAGE 9.0 OF DRAWINGS SUBMITTED.
 4- NEW ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
 5- ENGINEER OF RECORD SPECIFIES RIDGE VENT. SEE ATTIC
 SPACE VENTILATION CALCULATIONS ON PAGE 9.0. ENGINEER TO
 PROVIDE DETAILS/SPECIFICATIONS SHOWING HOW PROVIDING
 THE RIDGE VENT VENTILATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By jgomez Date 2019-06-20 Time 16:39 Rev Time 0.00
Received By jgomez Date 2019-06-20 Time 13:54 Sent To  
Notes
2019-06-20 16:43:57RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
 ****NEED ENERGY CALCULATIONS TO BE PROPERLY SIGNED BY
 THE OWNER AND ALL PLANS NEED THE ENGINEER'S SEAL AND
 SIGNATURE BEFORE APPROVAL.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE).
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- OK.
  
 3-OK
  
 ORIGINAL COMMENT:
 4- A)DESIGN PRESSURES SHOWN FOR NEW MASTER BEDROOM
 DOUBLE DOORS AND NEW FAMILY ROOM SINGLE DOOR DON'T
 CORRESPOND TO THE EFFECTIVE WIND AREA SHOWN ON
 COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1.
 REVISE AS REQUIRED. SEE SIZE OF DOORS AND REVISE AS
 REQUIRED.
  
 RESPONSE:
 PARTIALLY ADDRESSED. THE DOUBLE DOORS ARE CORRECT BUT
 SINGLE DOOR IS NOT. THE LOADS FOR SINGLE DOOR "01" NEED
 TO BE REVISED. NEED TO USE DESIGN PRESSURES FOR THE
 LOWER EFFECTIVE AREA AS REQUIRED BY FOOTNOTE "B" OF
 TABLE R301.2(2)FBC-RESIDENTIAL. SEE TABLE FOR DESIGN
 PRESSURES OF 20S.F. EFFECTIVE WIND AREA AND REVISE AS
 REQUIRED. REMEMBER THAT DESIGN PRESSURES ON THIS TABLE
 NEED TO BE ADJUSTED WITH THE EXPOSURE AND HEIGHT
 COEFFICIENT OF TABLE R301.2(3) FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 B) GARAGE DOORS DESIGN PRESSURES SHOWN ON THE
 COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1
 DON'T CORRESPOND TO THE ONES SHOWN ON TABLE 301.2(4)
 FBC-RESIDENTIAL WHEN MULTIPLIED BY THE COEFFICIENT FOR
 EXPOSURE "C". SEE TABLE R301.2(3) FBC-RESIDENTIAL AND
 REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER'S LEGALLY
 DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B)OK.
  
 C) OK.
  
 D) OK.
  
 E) OK.
  
 ORIGINAL COMMENT:
 6- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVICE IF SUBMITTING THIS
 INFORMATION LATER).
  
 ORIGINAL COMMENT:
 A)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)FIXED WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. COVER PAGE
 SUBMITTED IS FOR MANY DIFFERENT PRODUCT APPROVAL
 NUMBERS. UNABLE TO IDENTIFY THE ONE THAT CORRESPONDS TO
 DRAWING SUBMITTED.
  
 RESPONSE:
 PARTIALLY DONE. PROVIDE COMPLETE INFORMATION. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) DOUBLE DOORS AS SHOWN FOR NEW STORAGE.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS
  
 9- OK.
  
 10- OK.
  
 NEW COMMENT:
 11- ALL PLANS ON BOTH SETS NEED TO HAVE THE SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY
 CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS.
  
  
 12- WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 RESPONSE:
 ORIGINAL PLANS AND SUBMITTALS (ENERGY CALCULATIONS)
 WERE NOT RE-SUBMITTED. IN THE FUTURE PLEASE RES-SUBMIT
 EVERYTHING THAT WAS REVIEWED IN ORDER TO USE THEM FOR
 REFERENCE AND EXPEDITE THE REVIEW PROCESS.
  
 EVEN THOUGH RESPONSE LETTER IS NOT MANDATORY IT IT'S
 VERY HELPFUL TO PROVIDE ONE IN ORDER TO TO EXPEDITE THE
 REVIEW PROCESS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By jgomez Date 2019-04-16 Time 18:25 Rev Time 0.00
Received By jgomez Date 2019-04-16 Time 09:18 Sent To  
Notes
2019-04-16 18:26:26RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 SEC. R401.3 FBC-RESIDENTIAL (DRAINAGE).
 SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN).
 SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION).
  
 2- DESIGN PARAMETERS ON SHEET 3.1:
 A)ENGINEER OF RECORD IS SPECIFYING CONSTRUCTION TYPE
 IIIB. ACCORDING TO TABLE 601 FBC TYPE III CONSTRUCTION
 REQUIRES TWO HOURS FIRE RESISTANCE ON ALL EXTERIOR
 BEARING WALLS. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE EXTERIOR WALLS PROVIDE 2
 HOUR FIRE RATING. AND , PROVIDE MANUFACTURER'S
 SPECIFICATION FOR TWO HOUR FIRE RATED CONCRETE BLOCK.
 NOTE: TYPICALLY ONE AND TWO FAMILY STRUCTURES ARE
 CONSTRUCTION TYPE VB. CLARIFY WHY SPECIFYING
 CONSTRUCTION TYPE IIIB.
  
 B) ROOF LOADS ARE NOT CLEAR. DOES THE TOTAL ROOF LIVE
 INCLUDE THE TOP AND BOTTOM TRUSS CHORDS?.
 AND, DOES THE TOTAL ROOF DEAD LOAD INCLUDE THE TOP AND
 BOTTOM TRUSS CHORDS? ENGINEER OF RECORD TO CLARIFY.
 CLEARLY SPECIFY THE TOP AND BOTTOM LIVE AND DEAD CHORDS
 TO AVOID CONFLICTS/DELAYS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- ENGINEER OF RECORD TO SPECIFY INSULATION ON WALL
 BETWEEN THE NEW MASTER BEDROOM AND NEW STORAGE AS
 REQUIRED BY SEC. R103.2 AND R103.2.1 FBC-ENERGY
 CONSERVATION.
  
 4- A)DESIGN PRESSURES SHOWN FOR NEW MASTER BEDROOM
 DOUBLE DOORS AND NEW FAMILY ROOM SINGLE DOOR DON'T
 CORRESPOND TO THE EFFECTIVE WIND AREA SHOWN ON
 COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1.
 REVISE AS REQUIRED. SEE SIZE OF DOORS AND REVISE AS
 REQUIRED.
  
 B) GARAGE DOORS DESIGN PRESSURES SHOWN ON THE
 COMPONENTS AND CLADDING DESIGN PRESSURES ON SHEET 5.1
 DON'T CORRESPOND TO THE ONES SHOWN ON TABLE 301.2(4)
 FBC-RESIDENTIAL WHEN MULTIPLIED BY THE COEFFICIENT FOR
 EXPOSURE "C". SEE TABLE R301.2(3) FBC-RESIDENTIAL AND
 REVISE AS REQUIRED.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY
 DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) WALL TYPES ITEM #9 IS MISSING THE INFORMATION FOR
 THE WALL BETWEEN THE NEW MASTER BEDROOM AND THE NEW
 STORAGE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 TO
 MATCH PLANS AND PRODUCT APPROVAL SUBMITTED. THIS IS NOT
 SHINGLES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE
 RATIO IS 1/150 NOT 1/300. SEE SEC. R806.2
 FBC-RESIDENTIAL. OR, PERSON PREPARING THE ENERGY
 CALCULATIONS TO PROVIDE COMPLETE DOCUMENTATION SHOWING
 COMPLIANCE WITH THE 1/300 RATIO AS REQUIRED BY THE
 EXCEPTION ON SEC. R806.2.
  
 6- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 7-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 B)FIXED WINDOWS. PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED. COVER PAGE
 SUBMITTED IS FOR MANY DIFFERENT PRODUCT APPROVAL
 NUMBERS. UNABLE TO IDENTIFY THE ONE THAT CORRESPONDS TO
 DRAWING SUBMITTED.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 D) DOUBLE DOORS AS SHOWN FOR NEW STORAGE.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 9- PROVIDE SURVEY OR SITE PLAN SHOWING LOCATION OF
 ADDITION, PROPERTY LINES, SETBACKS AS REQUITED BY SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 10- FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST
 ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS
 PUBLISHED BY INTERNATIONAL CODE CONGRESS. VALUATION WAS
 UPDATED TO $241,657. THE PERMIT FEE BALANCE IS
 $4339.51.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-09-12 Cont ID  
Sent By ppetty Date 2019-09-12 Time 11:52 Rev Time 0.00
Received By ppetty Date 2019-09-12 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-07-31 Cont ID  
Sent By ppetty Date 2019-07-31 Time 13:04 Rev Time 0.00
Received By ppetty Date 2019-07-31 Time 13:04 Sent To  
Notes
2019-07-31 12:59:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.
 2.
 3.PROVIDE LOCATION OF METER AND MAINS ON PLAN NEC
 230.72
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER/CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-18 Cont ID  
Sent By ppetty Date 2019-06-18 Time 11:07 Rev Time 0.00
Received By ppetty Date 2019-06-18 Time 11:07 Sent To  
Notes
2019-06-18 11:07:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.OK
 2.ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION.
 WPB FBC 107.1
 3.OK
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER/CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By ppetty Date 2019-04-04 Time 11:14 Rev Time 0.00
Received By ppetty Date 2019-04-04 Time 10:17 Sent To  
Notes
2019-04-04 11:13:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 2.ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.15
 3.PROVIDE LOCATION OF METER AND MAINS ON PLAN NEC
 230.72
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER/CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-09-23 Cont ID  
Sent By jgomez Date 2019-09-23 Time 18:52 Rev Time 0.00
Received By jgomez Date 2019-09-20 Time 15:03 Sent To I
Notes
2019-09-23 15:03:27ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-09-13 Cont ID  
Sent By hmoser Date 2019-09-13 Time 10:12 Rev Time 0.00
Received By hmoser Date 2019-08-28 Time 13:27 Sent To  
Notes
2019-09-13 06:23:22TO HM DESK
  
2019-08-29 13:27:58R13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-20 Cont ID  
Sent By jgomez Date 2019-08-20 Time 18:28 Rev Time 0.00
Received By jgomez Date 2019-07-29 Time 16:01 Sent To I
Notes
2019-07-30 16:02:06R13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-20 Cont ID  
Sent By jgomez Date 2019-06-20 Time 16:45 Rev Time 0.00
Received By jgomez Date 2019-05-28 Time 10:24 Sent To I
Notes
2019-05-30 10:25:08R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-16 Cont ID  
Sent By ppetty Date 2019-04-16 Time 18:30 Rev Time 0.00
Received By jgomez Date 2019-03-11 Time 14:46 Sent To I
Notes
2019-03-12 14:46:18R16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2019-09-23 Cont ID  
Sent By jgomez Date 2019-09-23 Time 18:52 Rev Time 0.00
Received By jgomez Date 2019-09-23 Time 18:41 Sent To  
Notes
2019-09-23 18:52:38$417.24 PAID. MU-2019-028915

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2019-08-20 Cont ID  
Sent By jgomez Date 2019-08-20 Time 13:29 Rev Time 0.00
Received By jgomez Date 2019-08-20 Time 13:29 Sent To  
Notes
2019-08-20 13:29:47IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By jgomez Date 2019-06-20 Time 14:19 Rev Time 0.00
Received By jgomez Date 2019-06-20 Time 14:19 Sent To  
Notes
2019-06-20 14:20:21IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By jgomez Date 2019-04-16 Time 18:30 Rev Time 0.00
Received By jgomez Date 2019-04-16 Time 18:26 Sent To  
Notes
2019-04-16 18:30:14IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-09-13 Cont ID  
Sent By hmoser Date 2019-09-13 Time 10:12 Rev Time 0.00
Received By hmoser Date 2019-09-13 Time 10:06 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-08-20 Cont ID  
Sent By cmontell Date 2019-08-20 Time 14:25 Rev Time 0.00
Received By cmontell Date 2019-08-20 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-17 Cont ID  
Sent By cmontell Date 2019-06-17 Time 13:46 Rev Time 0.00
Received By cmontell Date 2019-06-17 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By cmontell Date 2019-04-04 Time 13:26 Rev Time 0.00
Received By cmontell Date 2019-04-04 Time 13:23 Sent To  
Notes
2019-04-04 13:26:48MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED RETURNS IN ALL BEDROOMS PER FBC RESIDENTIAL
 SEC M1602.3 BALANCED RETURN AIR., PLEASE PROVIDE SIZE
 FOR ALL FLEX DUCT AND RETURNS.
  
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-19 Cont ID  
Sent By gjohnson Date 2019-08-19 Time 11:49 Rev Time 0.00
Received By gjohnson Date 2019-08-19 Time 11:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-17 Cont ID  
Sent By thunt Date 2019-06-17 Time 08:37 Rev Time 0.00
Received By thunt Date 2019-06-17 Time 06:42 Sent To  
Notes
2019-06-17 08:19:38PLUMBING 2ND REVIEW**DENIED**FL ST 553.80 (B)2B WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST.PROVIDE WATER HEATER INSTALLATION
 MANUAL/ SPEC SHOWING THE EFFICIENCY RATING OF E.F .97
 AS CALLED OUT IN THE R405 FORM. FBC 107.2.1.
  
 2) 2ND REQUEST. PROVIDE A SHOWER DETAIL AND PROVIDE
 WHAT SHOWER PAN MATERIAL IS BEING USED. FBC 107.2.1
 (A) FLOOR SHALL BE PRE-PITCH @ MIN 2% BEFORE SHOWER PAN
 MATERIAL IS INSTALLED. YOUR DETAIL ONLY SHOWS THE
 ACTUAL TILE BEING PITCHED @ 2%. FBC-R P2709.3
  
 3) 2ND REQUEST. PLUMBING ISOMETRIC DRAWING PROVIDE ON
 SHT. 7.1 HAS THE WASHING MACHINE AND LAUNDRY TUB
 DISCHARGING INTO THE BATHROOM GROUP WET VENT. FIXTURES
 OUTSIDE OF THE BATHROOM GROUP ARE NOT PERMITTED TO
 DISCHARGE INTO THE BATHROOM GROUPS HORIZONTAL WET VENT
 AND SHALL DISCHARGE DOWNSTREAM OF THE BATHROM GROUP.
 FBC-R P3108.1
  
 4) ALL SHEETS SHALL BE SIGN AND SEALED. F.S 471,481,
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 THUNT@CGA SOLUTIONS.COM
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-27 Cont ID  
Sent By thunt Date 2019-03-27 Time 07:02 Rev Time 0.00
Received By thunt Date 2019-03-27 Time 07:02 Sent To  
Notes
2019-03-27 07:01:54PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE WATER HEATER INSTALLATION MANUAL/ SPEC
 SHOWING THE EFFICIENCYRATING OF E.F .97 AS CALLED OUT
 IN THE R405 FORM. FBC 107.2.1.
  
 2) PROVIDE A SHOWER DETAIL AND PROVIDE WHAT SHOWER PAN
 MATERIAL IS BEING USED. FBC 107.2.1
  
 3) PLUMBING ISOMETRIC DRAWING PROVIDE ON SHT. 7.1 HAS
 THE WASHING MACHINE AND LAUNDRY TUB DISCHARGING INTO
 THE BATHROOM GROUP WET VENT. FIXTURES OUTSIDE OF THE
 BATHROOM GROUP ARE NOT PERMITTED TO DISCHARGE INTO THE
 BATHROOM GROUPS HORIZONTAL WET VENT AND SHALL DISCHARGE
 DOWNSTREAM OF THE BATHROM GROUP. FBC-R P3108.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 THUNT@CGA SOLUTIONS.COM
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-08-20 Cont ID  
Sent By jgomez Date 2019-08-20 Time 13:24 Rev Time 0.00
Received By jgomez Date 2019-08-20 Time 13:24 Sent To  
Notes
2019-08-20 13:24:39PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 B) RIDGE VENT AS SPECIFIED BY THE NEW ENGINEER OF
 RECORD ON PAGE 9.0 OF DRAWINGS SUBMITTED.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
  
 APPROVED ROOF TILE NOA 16-0112.07
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By jgomez Date 2019-06-20 Time 16:44 Rev Time 0.00
Received By jgomez Date 2019-06-20 Time 16:44 Sent To  
Notes
2019-06-20 16:45:131- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 B)
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 APPROVED ROOF TILE NOA 16-0112.07
  
  
  
  
 1- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 APPROVED ROOF TILE NOA 16-0112.07

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By jgomez Date 2019-04-16 Time 18:26 Rev Time 0.00
Received By jgomez Date 2019-04-16 Time 18:26 Sent To  
Notes
2019-04-16 18:26:491- ENGINEER OF RECORD TO SPECIFY ROOF TILE FASTENING IN
 THE CONSTRUCTION DOCUMENTS. SEC. 107.2.1.1 CITY
 AMENDMENTS. IF SPECIFYING ROOF TILE ADHESIVE, THEN
 SPECIFY PADDY SIZE AND PROVIDE PRODUCT APPROVAL. IF
 SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE AND NUMBER
 OF SCREWS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF
 RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED
 ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 APPROVED ROOF TILE NOA 16-0112.07

Review Stop Z ZONING
Rev No 4 Status P Date 2019-08-29 Cont ID  
Sent By awooten Date 2019-08-29 Time   Rev Time 0.00
Received By awooten Date 2019-08-29 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2019-08-13 Cont ID  
Sent By awooten Date 2019-08-13 Time   Rev Time 0.00
Received By awooten Date 2019-08-13 Time   Sent To  
Notes
2019-08-13 15:15:46***************************************ZONING REVIEW
 FAILED*****************************************
  
 THE STREET SIDE SETBACK ON OLIVE IS 12.5 FEET, SETBACK
 LINE ON SITE PLAN HAS 10 FEET. (THE PROPOSED SETBACK
 FOR THE ADDITION MEETS THE REQUIREMENT.)
  
 THE VALUE OF PROJECT TRIGGERS THE LANDSCAPE CODE. A
 SEPARATE LANDSCAPE AND IRRIGATION PERMIT IS REQUIRED.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISON
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-06-12 Cont ID  
Sent By awooten Date 2019-06-12 Time   Rev Time 0.00
Received By awooten Date 2019-06-12 Time   Sent To  
Notes
2019-06-12 15:08:54**************************************************ZONIN
 G REVIEW FAILED****************************************
 ************
  
 THE LANDSCAPE AND IRRIGATION PLAN SUBMITTED WITH THIS
 PERMIT HAS TO BE SUBMITTED AS A SEPARATE PERMIT.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 [email protected]
 561-822-1449

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By awooten Date 2019-03-19 Time   Rev Time  
Received By awooten Date 2019-03-19 Time   Sent To  
Notes
2019-03-19 14:37:14********************************ZONING REVIEW
 FAILED**********************************************
  
 PLEASE PROVIDE A SITE PLAN WITH ADDITION AND SETBACKS.
  
 ADDITION IS MORE THAN HALF THE PROPERTY VALUE OF HOME,
 SO THE LANDSCAPE CODE HAS BEEN TRIGGERED.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
  
 PLEASE DIMENSION THE OVERHANGS. THEY ARE NOT PERMITTED
 TO EXCEED 3 FEET.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]