Plan Review Details - Permit 19030239
Plan Review Stops For Permit 19030239
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2019-08-15 Cont ID  
Sent By shill Date 2019-08-15 Time 12:29 Rev Time 0.00
Received By shill Date 2019-08-15 Time 12:29 Sent To  
Notes
2019-08-15 12:31:06ADDRESS REMAINS 1500 CENTREPARK
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2019-07-30 Cont ID  
Sent By jgomez Date 2019-07-30 Time 09:25 Rev Time 0.00
Received By jgomez Date 2019-07-30 Time 09:25 Sent To  
Notes
2019-07-30 09:30:19SEE BUILDING REVIEW COMMENTS FOR ART IN PUBLIC PLACES
 COMMENTS AND CONTACT MS. SYBILLE WALTER. SEE BELOW.
  
 PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 1- THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-09-16 Cont ID  
Sent By jgomez Date 2019-09-16 Time 18:36 Rev Time 0.00
Received By jgomez Date 2019-09-16 Time 12:55 Sent To  
Notes
2019-09-16 17:06:4909/16/19 REVISED ELEVATION CERTIFICATE WAS UPLOADED FOR
 REVIEW.
  
 MR. GOMEZ,
 AS PER OUR CONVERSATION, THIS IS TO CLARIFY THAT THE
 CLEAR WIDTH OF THE GRATE SHOWN ON SHEET A-2.1 IS 4.75?.
 PLEASE SEE ATTACHED SKETCH.
 REGARDS,
 JOSE L. DIAZ
 SENIOR ASSOCIATE ARCHITECT
 8950 S.W. 74 COURT I SUITE 1513 I MIAMI, FLORIDA 33156
 OFFICE 305.273.9911 I FAX 305.273.9424
  
  
  
 FOUNDATION PERMIT APPROVED WITH PROVISO
 1- SHEET A-2.1: REVISE TYPO ON SIZE OF GRATE ON THE
 GRATE DETAIL. CALCULATIONS SPECIFY 4.75' NOT 14.75'.
 AND PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE GRATES. SEE SEC. 2.7.2.1 ASCE/SEI
 24-14.
 NOTE: TAKE INTO CONSIDERATION ACCESS TO THE CREATED
 CRAWL SPACE.
 2- REVISE/CLARIFY "CONSTRUCTION DRAWINGS" ELEVATION
 CERTIFICATE. SEE REDLINED ELEVATION CERTIFICATE.
 ADDITIONAL ELEVATION CERTIFICATES WILL BE REQUIRED FOR
 BUILDING UNDER CONSTRUCTION AND FINISHED CONSTRUCTION.
 3- SURVEYOR'S NOTE #13 SPECIFIES BASE FLOOD ELEVATION
 OF 12.7 FEET. SPECIFY IF N.A.V.D 1988 OR N.G.V.D 1929.
 4- BASED ON THE HEIGHT OF THE BUILDING, A BARRIER AND
 COVERED WALKWAY FOR PROTECTION OF PEDESTRIANS WILL BE
 REQUIRED. SEC. 3306.1 FBC-BUILDING.
 5- ART IN PUBLIC PLACES. PLEASE CONTACT MS. SYBILLE
 WELTER ART IN PUBLIC PLACES COORDINATOR 822-1515
 E-MAIL: [email protected] FOR MORE INFORMATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date 2019-09-16 Cont ID  
Sent By jgomez Date 2019-09-16 Time 09:13 Rev Time 0.00
Received By jgomez Date 2019-09-13 Time 17:11 Sent To  
Notes
2019-09-13 19:08:13FOUNDATION PERMIT APPROVED WITH PROVISO (PROVIDE
 INFORMATION THAT REQUIRES PLAN REVIEW PRIOR TO
 INSPECTIONS TO AVOID CONFLICTS/DELAYS):
 1- SHEET A-2.1:
 A) REVISE SIZE OF GRATE SHOWN ON THE ENLARGED GRATE
 DETAIL. IT SHOULD BE 4.75' NOT 14.75' AND SPECIFY SIZE
 OF OPENINGS. NOT LESS THAN 3" MIN. SEC. 2.7.2.1
 ASCE/SEI 24-14.
 2- PROVIDE COMPLETE/REVISED PROPOSED "CONSTRUCTION
 DRAWINGS" ELEVATION CERTIFICATE. ADDITIONAL ELEVATION
 CERTIFICATES WILL BE REQUIRED FOR BUILDING UNDER
 CONSTRUCTION AND FINISHED CONSTRUCTION.
 NOTE: GARAGE IS CONSIDERED AN ATTACHED GARAGE.
 3- SURVEYOR'S NOTE #13 SPECIFIES BASE FLOOD ELEVATION
 OF 12.7 FEET. SPECIFY IF N.A.V.D 1988 OR N.G.V.D 1929.
 4- BASED ON THE HEIGHT OF THE BUILDING, A BARRIER AND
 COVERED WALKWAY FOR PROTECTION OF PEDESTRIANS WILL BE
 REQUIRED. SEC. 3306.1 FBC-BUILDING.
 5- ART IN PUBLIC PLACES. PLEASE CONTACT MS. SYBILLE
 WELTER ART IN PUBLIC PLACES COORDINATOR 822-1515
 E-MAIL: [email protected] FOR MORE INFORMATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-08-30 Cont ID  
Sent By jgomez Date 2019-08-30 Time 13:08 Rev Time 0.00
Received By jgomez Date 2019-08-29 Time 10:58 Sent To  
Notes
2019-08-30 13:08:48FOUNDATION PERMIT THIRD BUILDING PLAN REVIEW CHECKLIST.
 FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 SINCE I AM GOING TO BE AWAY FROM THE OFFICE, I TALKED
 TO MY MANAGERS AND THIS BUILDING REVIEW MAY BE APPROVED
 WITH PROVISO BY THEM ONCE THESE COMMENTS ARE RESOLVED.
  
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD
 ZONE WITH THE BASE FLOOD BFE: 12.7 FEET BASED ON NAVD
 1988.
 CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2)
 FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC.
 18-284 CITY ORDINANCE NO. 4729-17). THE GARAGE FINISH
 FLOOR ELEVATION IS BELOW THE TWO FEET FREE BOARD. IN
 ADDITION, THE GARAGE LOWEST LEVEL IS GOING TO BE BELOW
 THE BASE FLOOR ELEVATION (12.7 NAVD 88). PLEASE PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW TO MEET
 THE OPENING AND WET FLOODPROOFING REQUIREMENTS FOR
 ENCLOSURES AS REQUIRED BY SEC. 1612.4 FBC-BUILDING. THE
 OTHER OPTION IS TO RAISE THE FINISH FLOOR ELEVATION OF
 THE GARAGE AT THE LOWEST LEVEL.
  
 RESPONSE:
 THERE ARE ENGINEERED AND NON -ENGINEERED FLOOD VENTS
 SHOWN ON PLANS. PROVIDE COMPLETE CALCULATIONS SHOWING
 HOW THE ENGINEERED AND NON-ENGINEERED FLOOD VENTS SHOWN
 ON THE SHEET A-2.1 WILL WORK TOGETHER. SEE SEC. 2.7 OF
 ASCE/SEI 24-14.
  
 ORIGINAL COMMENT:
 3- PROPOSED ELEVATION CERTIFICATE SUBMITTED NEEDS TO BE
 COMPLETE AND NEEDS TO BE REVISED (SEC.107.3.5.1.1 CITY
 AMENDMENTS):
 A)NEED TO COMPLETE ITEMS A7 AND A9. SEE FEMA ELEVATION
 CERTIFICATE FOR INSTRUCTIONS.
 B) ITEM C2 NEEDS TO BE COMPLETE AND CORRECTED:
 (1) SPECIFY THE BENCHMARK UTILIZED AND THE VERTICAL
 DATUM.
 (2) TOP OF NEXT HIGHER FLOOR SPECIFIED ON ITEM C2(B) IS
 INCORRECT. REVISE AS REQUIRED.
 (3) ATTACHED GARAGE (TOP OF SLAB) SPECIFIED ON ITEM
 C2(D) IS INCORRECT. THIS IS NOT N/A. THERE IS AN
 ATTACHED GARAGE IN THIS BUILDING. IN ADDITION, SINCE
 THE GARAGE HAS SEVERAL ELEVATIONS, THEN THIS NEEDS TO
 BE ADDRESSED.
  
 RESPONSE:
 ELEVATION CERTIFICATED SUBMITTED NEEDS TO BE CLEAR. IS
 THIS AN ATTACHED OR DETACHED GARAGE?. FLOOD VENTS
 INFORMATION NEEDS TO BE COORDINATED WITH ITEM #2 ABOVE.
  
 4- OK.
  
 5- OK
  
 ORIGINAL COMMENT:
 6- NEW STRUCTURAL DRAWINGS WERE SUBMITTED, BUT I WAS
 UNABLE TO OPEN THEM UP. IT LOOKS LIKE THEY MAY BE
 CORRUPTED. PLEASE CHECK DRAWINGS 087-S2.1 DIM.
 FOUNDATION PLAN DIMENSION TO DRAWING 095-S2.1.CJ.G.
 PLEASE COORDINATE WITH LIBRARIANS LAURA MARCHANT AT
 (561)805-6658 OR CAROLINE PUELL AT (561)805-6659 TO
 MAKE SURE ALL DRAWINGS ARE PROPERLY DOWNLOADED AND
 READABLE. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 I AM STILL NOT ABLE TO OPEN THESE STRUCTURAL PLANS
 DRAWINGS. I AM ABLE TO SEE ALL OTHER DRAWINGS EXCEPT
 THESE ONES. PLEASE COORDINATE UPLOADING METHOD WITH
 LIBRARIANS SO ALL DRAWINGS ARE VISIBLE.
  
 ORIGINAL COMMENT:
 7- SURVEY SUBMITTED DOESN'T SPECIFY WHAT THE ELEVATIONS
 SHOWN ON THE SURVEY ARE BASED ON N.A.V.D 1988 OR NGVD
 1929. SEC. 107.2.1 CITY AMENDMENTS. PLEASE PROVIDE THIS
 INFORMATION.
  
 RESPONSE
 SURVEYOR'S NOTE #13 SPECIFIES A BASE FLOOD ELEVATION OF
 12.7 FEET BUT IT DOESN'T SPECIFY IF IT'S N.A.V.D 1988
 OR N.G.V.D 1929. IT JUST SPECIFIES BASE FLOOD
 ELEVATION.
  
 ORIGINAL COMMENT:
 8- PLEASE CLARIFY/REVISE SCOPE OF WORK OF THIS PERMIT
 APPLICATION. CLEARLY SPECIFY IF THE SCOPE OF WORK IS
 ONLY FOR THE FOOTINGS UP TO THE CONCRETE SLAB OR IF
 IT'S FOR FOOTINGS INCLUDING THE CONCRETE SLAB. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 RECEIVED E-MAIL FROM STEVE SEALY ON 08/23/19 STATING
 THAT THE SCOPE OF THE FOUNDATION PERMIT IS UP TO THE
 CONCRETE SLAB. I REVISED SCOPE OF WORK IN OUR SYSTEM.
  
 NOTE:
 THE VALUE APPLIED TO THIS FOUNDATION PERMIT WILL BE
 DEDUCTED FROM THE VALUE CALCULATED FOR THE CONSTRUCTION
 OF THE REST OF THE BUILDING. SEC. 109.3 CITY
 AMENDMENTS.
  
  
 INFORMATIONAL ONLY. NOT ACTION REQUIRED RIGHT NOW FOR
 THIS PERMIT ON THE FOLLOWING NOTES:
  
 9- BASED ON THE HEIGHT OF THE BUILDING, IT LOOKS LIKE A
 BARRIER AND COVERED WALKWAY FOR PROTECTION OF
 PEDESTRIANS WILL BE REQUIRED. THIS WILL BE REQUIRED
 PRIOR TO STARTING CONSTRUCTION. SEC. 3306.1
 FBC-BUILDING.
  
 10- ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. THIS WILL BE A PROVISO.
 PLEASE CONTACT MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected] FOR MORE
 INFORMATION.
  
 NOTE:
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-11 Cont ID  
Sent By jgomez Date 2019-07-11 Time 13:09 Rev Time 0.00
Received By jgomez Date 2019-07-10 Time 09:16 Sent To  
Notes
2019-07-11 13:10:3807/31/19 REVISED COMMENTS:
  
 FOUNDATION PERMIT SECOND BUILDING PLAN REVIEW
 CHECKLIST.
 FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SHEET LS-0.1 LIFE SAFETY PLAN GROUND LEVEL:
 TWO EXITS ARE REQUIRED FROM THE GARAGE. SEC. 1006.2.1
 FBC-BUILDING. FLOOR PLAN SHOWS AN EXIT SIGN AT STAIRWAY
 #4 AND AN EXIT SIGN LEADING TO THE ENTRY VEHICULAR
 RAMP. EGRESS FROM THE GARAGE THRU THE VEHICULAR RAMP IS
 NOT ALLOWED, UNLESS PEDESTRIAN FACILITIES ARE PROVIDED.
 SEC. 1006.2.2.5 FBC-BUILDING. PLEASE REVISE PLAN
 SHOWING HOW THE TWO REQUIRED EXITS WILL BE PROVIDED.
  
 2- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD
 ZONE WITH THE BASE FLOOD BFE: 12.7 FEET BASED ON NAVD
 1988.
 CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO (2)
 FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION (SEC.
 18-284 CITY ORDINANCE NO. 4729-17). THE GARAGE FINISH
 FLOOR ELEVATION IS BELOW THE TWO FEET FREE BOARD. IN
 ADDITION, THE GARAGE LOWEST LEVEL IS GOING TO BE BELOW
 THE BASE FLOOR ELEVATION (12.7 NAVD 88). PLEASE PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW TO MEET
 THE OPENING AND WET FLOODPROOFING REQUIREMENTS FOR
 ENCLOSURES AS REQUIRED BY SEC. 1612.4 FBC-BUILDING. THE
 OTHER OPTION IS TO RAISE THE FINISH FLOOR ELEVATION OF
 THE GARAGE AT THE LOWEST LEVEL.
  
 3- PROPOSED ELEVATION CERTIFICATE SUBMITTED NEEDS TO BE
 COMPLETE AND NEEDS TO BE REVISED (SEC.107.3.5.1.1 CITY
 AMENDMENTS):
  
 A)NEED TO COMPLETE ITEMS A7 AND A9. SEE FEMA ELEVATION
 CERTIFICATE FOR INSTRUCTIONS.
  
 B) ITEM C2 NEEDS TO BE COMPLETE AND CORRECTED:
 (1) SPECIFY THE BENCHMARK UTILIZED AND THE VERTICAL
 DATUM.
 (2) TOP OF NEXT HIGHER FLOOR SPECIFIED ON ITEM C2(B) IS
 INCORRECT. REVISE AS REQUIRED.
 (3) ATTACHED GARAGE (TOP OF SLAB) SPECIFIED ON ITEM
 C2(D) IS INCORRECT. THIS IS NOT N/A. THERE IS AN
 ATTACHED GARAGE IN THIS BUILDING. IN ADDITION, SINCE
 THE GARAGE HAS SEVERAL ELEVATIONS, THEN THIS NEEDS TO
 BE ADDRESSED.
  
 4- LEVEL 1 GARAGE FLOOR PLAN ON SHEET A-2.1 SHOWS VAN
 ACCESSIBLE PARKING AND "LEASING" PARKING SPACES.
 CLARIFY IF THESE PARKING SPACES ARE FOR THE LEASING
 OFFICE. ALSO, HOW DO PEOPLE HAVE ACCESS TO THE LEASING
 AREA?. WHERE IS THE ACCESSIBLE ROUTE?
 SEC. 206.2 FBC-ACCESSIBILITY. (ALSO, ACCESS ISLE IS
 REQUIRED. SEC. 206.2 FBC-ACCESSIBILITY).
  
 5- PLEASE NOTE A 7 STORY BUILDING QUALIFIES AS A
 THRESHOLD BUILDING / FL S. S. 553.71(7).
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND 633 FLORIDA STATUTES. ONLY THE
 ARCHITECTURAL PLANS HAVE THIS COMPLETE STATEMENT. THE
 STRUCTURAL PLANS DON'T HAVE THIS COMPLETE STATEMENT..
 THE STRUCTURAL PLANS ARE MISSING THE PART OF THE
 STATEMENT REFERRING TO THE APPLICABLE FIRE-SAFETY
 STANDARDS. PLEASE PROVIDE STRUCTURAL DRAWINGS WITH
 COMPLETE STATEMENT. SEC. 110.8.4.4 CITY AMENDMENTS.
  
 NOTE: PLEASE SEE SEPARATE THRESHOLD REVIEW STOP FOR
 COMMENTS. THE STATEMENT ABOVE IS REQUIRED TO BE ON
 PLANS IN ORDER TO PASS THE BUILDING REVIEW.
  
 6- NEW STRUCTURAL DRAWINGS WERE SUBMITTED, BUT I WAS
 UNABLE TO OPEN THEM UP. IT LOOKS LIKE THEY MAY BE
 CORRUPTED. PLEASE CHECK DRAWINGS 087-S2.1 DIM.
 FOUNDATION PLAN DIMENSION TO DRAWING 095-S2.1.CJ.G.
 PLEASE COORDINATE WITH LIBRARIANS LAURA MARCHANT AT
 (561)805-6658 OR CAROLINE PUELL AT (561)805-6659 TO
 MAKE SURE ALL DRAWINGS ARE PROPERLY DOWNLOADED AND
 READABLE. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- SURVEY SUBMITTED DOESN'T SPECIFY WHAT THE ELEVATIONS
 SHOWN ON THE SURVEY ARE BASED ON N.A.V.D 1988 OR NGVD
 1929. SEC. 107.2.1 CITY AMENDMENTS. PLEASE PROVIDE THIS
 INFORMATION.
  
 NOTE:
 ALL PLANS SUBMITTED ARE REFERENCING NGVD 1929. TO AVOID
 MAYOR ERRORS/CONFLICTS/DELAYS IT WILL BE VERY HELPFUL
 TO HAVE ALL THE FINISH FLOOR ELEVATIONS CONVERTED TO
 THE NAVD 1988 SINCE THE NEW FLOOD MAPS ARE BASED ON
 NAVD 1988.
  
 8- PLEASE CLARIFY/REVISE SCOPE OF WORK OF THIS PERMIT
 APPLICATION. CLEARLY SPECIFY IF THE SCOPE OF WORK IS
 ONLY FOR THE FOOTINGS UP TO THE CONCRETE SLAB OR IF
 IT'S FOR FOOTINGS INCLUDING THE CONCRETE SLAB. SEC.
 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 THE VALUE APPLIED TO THIS FOUNDATION PERMIT WILL BE
 DEDUCTED FROM THE VALUE CALCULATED FOR THE CONSTRUCTION
 OF THE REST OF THE BUILDING. SEC. 109.3 CITY
 AMENDMENTS.
  
  
 INFORMATIONAL ONLY. NOT ACTION REQUIRED RIGHT NOW FOR
 THIS PERMIT ON THE FOLLOWING NOTES:
  
 9- BASED ON THE HEIGHT OF THE BUILDING, IT LOOKS LIKE A
 BARRIER AND COVERED WALKWAY FOR PROTECTION OF
 PEDESTRIANS WILL BE REQUIRED. THIS WILL BE REQUIRED
 PRIOR TO STARTING CONSTRUCTION. SEC. 3306.1
 FBC-BUILDING.
  
 10- ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE. THIS WILL BE A PROVISO.
 PLEASE CONTACT MS. SYBILLE WELTER ART IN PUBLIC PLACES
 COORDINATOR 822-1515 E-MAIL: [email protected] FOR MORE
 INFORMATION.
  
 NOTE:
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By jwitmer Date 2019-04-15 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2019-04-15 Time 09:03 Sent To  
Notes
2019-04-15 14:07:362017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19030239 /CYAN APARTMENTS/ FOUNDATION
 PERMIT
 ADD: 1500 CENTREPARK BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-348-4805 CONTACT KARI NEVILLE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. APRIL 15/ 2019
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2A) THE LIFE SAFETY SHEET LS-0.0 PROVIDES THE ALLOWABLE
 TABLES FROM THE 2017 FBC-B TABLE 504.4 & TABLE 506.2.
 WHAT THIS SHEET DOES NOT PROVIDE IS THE ACTUAL SQUARE
 FEET PER FLOOR PER OCCUPANCY TYPE. WITHOUT THIS
 INFORMATION CODE DETERMINATION CANNOT BE DETERMINED.
 2B) THE LIFE SAFETY SHEET LS-0.0 PROVIDES THE ALLOWABLE
 TABLES FROM THE 2017 FBC-B TABLE 504.4 & TABLE 506.2.
 WHAT THIS SHEET DOES NOT PROVIDE IS THE ACTUAL SQUARE
 FEET PER FLOOR PER OCCUPANCY TYPE. WITHOUT THIS
 INFORMATION VALUATION OF THIS PROJECT CANNOT BE
 DETERMINED, NOR WILL THE COUNTY IMPACT FEES.
 109.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
 3) PLEASE NOTE A 7 STORY BUILDING QUALIFIES AS A
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS SENT TO: [email protected] ATTENTION: KARI
 NEVILLE
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA. FOR A JOBSITE
 REPRESENTATIVE IS NOT AN ARCHITECT OR ENGINEER THEN
 THEY MUST HAVE A BN LICENSE NUMBER UNDER
 F. S. 468.
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE
 E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED,
 THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED
 AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS,
 TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1)
 FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK
 & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 3G) 110.3.7.4.3. ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 3H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
 4) THE SUBMITTED GEOTECHNICAL REPORT BY ARDAMAN &
 ASSOCIATES FILE NO. 18-1735 OCT. 23/ 2018 APPEARS TO BE
 A PAPER REPORT THAT WAS UPLOADED, THE REPORT DOES NOT
 HAVE ELECTRONIC SIGNATURES.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 5) THIS PROPOSED BUILDING IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH THE BASE FLOOD BFE: 12.7 FEET NAV88.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 6) SHEET 024-LS-0.0 THE LIFE SAFETY CODE INFORMATION
 SHEET UNDER THE HEADING OF CODES, ORDNANCES &
 AUTHORITIES HAVING GOVERNING JURISDICTION REFERENCES:
 6A) CITY OF FORT LAUDERDALE LOCAL ORDNANCES
 6B) BROWARD COUNTY LOCAL ORDINANCES
 6C) CITY OF FORT LAUDERDALE FINAL (DRC) CERTIFICATE OF
 COMPLIANCE, CASE NO. R17044
 PLEASE REMOVE AND UPDATE PLANS ACCORDINGLY. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) SHEET 024-LS-0.0 THE LIFE SAFETY CODE INFORMATION
 SHEET UNDER THE HEADING OF OCCUPANCY SEPARATION
 REQUIREMENTS THE STATEMENT READS: DWELLING UNIT/
 DWELLING UNIT 1 HOUR F. R. RATING (PROVIDED) PER FBC
 708.3.2 TYPE I. PLEASE EXPLAIN THERE IS A CODE SECTION
 IN THE 2017 FBC-B 708.3 AND EXCEPTION 1 & 2. WHAT IS
 MEANT BY TYPE I? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED TO DETERMINE CODE COMPLIANCE.
  
 8) PLEASE NOTE THERE APPEARS TO BE MORE THAN ONE
 STRUCTURAL SHEET MISSING FOR THE FOUNDATION PERMIT.
 SUBMITTED IN THIS REVIEW. THE INDEX SHEET LIST A SERIES
 OF S2.1 A, B, C, G FOUNDATION GROUND FRAMING PLANS THAT
 ARE MISSING. SHEETS S-3 SCHEDULES, MISSING INCLUDING
 S3.7 & S3.8 WITHOUT SEEING WHAT ARE ON THE MISSING
 SHEETS A COMPLETE REVIEW OF THE FOUNDATION CANNOT BE
 MADE UNDER THE FIRST REVIEW. THE FOUNDATIONS WILL NEED
 THE INFORMATION ON WHAT SIZE AND NUMBER OF VERTICAL
 STEEL ARE TO COMING OUT OF THE TOP OF THE FOUNDATION.
  
 9) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-09-16 Cont ID  
Sent By jleahy Date 2019-09-16 Time 11:21 Rev Time 0.00
Received By jleahy Date 2019-09-16 Time 11:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-12 Cont ID  
Sent By jleahy Date 2019-06-12 Time 12:52 Rev Time 0.00
Received By jleahy Date 2019-06-12 Time 12:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-26 Cont ID  
Sent By jleahy Date 2019-03-26 Time 16:30 Rev Time 0.00
Received By jleahy Date 2019-03-26 Time 16:30 Sent To  
Notes
2019-03-26 16:31:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL PAGES INCLUDED WITH DOWNLOAD.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-08-15 Cont ID  
Sent By rrossano Date 2019-08-15 Time   Rev Time 0.00
Received By rrossano Date 2019-08-15 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 08:47 Rev Time 0.00
Received By shill Date 2019-07-03 Time 08:47 Sent To  
Notes
2019-07-03 08:47:13CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-22 Time 16:15 Rev Time 0.00
Received By shill Date 2019-03-22 Time 16:15 Sent To  
Notes
2019-03-22 16:15:35CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-28 Cont ID  
Sent By pleduc Date 2019-08-28 Time   Rev Time 0.00
Received By pleduc Date 2019-08-28 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-05 Cont ID  
Sent By pleduc Date 2019-06-05 Time   Rev Time 0.00
Received By pleduc Date 2019-06-04 Time 15:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-22 Cont ID  
Sent By pleduc Date 2019-03-22 Time   Rev Time 0.00
Received By pleduc Date 2019-03-22 Time 11:00 Sent To  
Notes
2019-03-22 11:30:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 7 - THERE IS AN INDICATION OF AN 8" D.I.P FIRE
 LINE WITH A COMMENT "INSTALLED BY A LICENSED FIRE
 SPRINKLER CONTRACTOR".
  
 ALL FIRE LINE UNDERGROUND SHALL BE DONE BY STATE OF
 FLORIDA LICENSED FIRE PROTECTION CONTRACTOR.
  
 PER FS 633.102
 (1)??BOARD? MEANS THE FLORIDA FIRE SAFETY BOARD.
 (2)??CONTRACTING? MEANS ENGAGING IN BUSINESS AS A
 CONTRACTOR.
 (3)(A)?CONTRACTOR I? MEANS A CONTRACTOR WHOSE BUSINESS
 INCLUDES THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER,
 REPAIR, AND SERVICE ALL TYPES OF FIRE PROTECTION
 SYSTEMS, EXCLUDING PRE-ENGINEERED SYSTEMS.
 (B)??CONTRACTOR II? MEANS A CONTRACTOR WHOSE BUSINESS
 IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER,
 REPAIR, AND SERVICE WATER SPRINKLER SYSTEMS, WATER
 SPRAY SYSTEMS, FOAM-WATER SPRINKLER SYSTEMS, FOAM-WATER
 SPRAY SYSTEMS, STANDPIPES, COMBINATION STANDPIPES AND
 SPRINKLER RISERS, ALL PIPING THAT IS AN INTEGRAL PART
 OF THE SYSTEM BEGINNING AT THE POINT OF SERVICE AS
 DEFINED IN THIS SECTION, SPRINKLER TANK HEATERS, AIR
 LINES, THERMAL SYSTEMS USED IN CONNECTION WITH
 SPRINKLERS, AND TANKS AND PUMPS CONNECTED THERETO,
 EXCLUDING PRE-ENGINEERED SYSTEMS.
 (C)??CONTRACTOR III? MEANS A CONTRACTOR WHOSE BUSINESS
 IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO FABRICATE, INSTALL, INSPECT, ALTER, REPAIR,
 AND SERVICE CARBON DIOXIDE SYSTEMS, FOAM EXTINGUISHING
 SYSTEMS, DRY CHEMICAL SYSTEMS, AND HALON AND OTHER
 CHEMICAL SYSTEMS, EXCLUDING PRE-ENGINEERED SYSTEMS.
 (D)??CONTRACTOR IV? MEANS A CONTRACTOR WHOSE BUSINESS
 IS LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO LAY OUT, FABRICATE, INSTALL, INSPECT, ALTER,
 REPAIR, AND SERVICE AUTOMATIC FIRE SPRINKLER SYSTEMS
 FOR DETACHED ONE-FAMILY DWELLINGS, DETACHED TWO-FAMILY
 DWELLINGS, AND MOBILE HOMES, EXCLUDING PRE-ENGINEERED
 SYSTEMS AND EXCLUDING SINGLE-FAMILY HOMES IN CLUSTER
 UNITS, SUCH AS APARTMENTS, CONDOMINIUMS, AND ASSISTED
 LIVING FACILITIES OR ANY BUILDING THAT IS CONNECTED TO
 OTHER DWELLINGS. A CONTRACTOR IV IS LIMITED TO THE
 SCOPE OF PRACTICE SPECIFIED IN NFPA 13D.
 (E)??CONTRACTOR V? MEANS A CONTRACTOR WHOSE BUSINESS IS
 LIMITED TO THE EXECUTION OF CONTRACTS REQUIRING THE
 ABILITY TO FABRICATE, INSTALL, INSPECT, ALTER, REPAIR,
 AND SERVICE THE UNDERGROUND PIPING FOR A FIRE
 PROTECTION SYSTEM USING WATER AS THE EXTINGUISHING
 AGENT BEGINNING AT THE POINT OF SERVICE AS DEFINED IN
 THIS ACT AND ENDING NO MORE THAN 1 FOOT ABOVE THE
 FINISHED FLOOR.
  
 PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE.
  
  
  
 2) SHEET 7 - THERE IS AN INDICATION OF AN 8" D.D.C.V. -
 IS THIS DDCV A FIRE LINE DDCV?
  
 ALL FIRE LINE UNDERGROUND SHALL COMPLY WITH NFPA 24 AND
 IF THIS IS A FIRE LINE DDCV IT IS WITHIN THE FOOTPRINT
 OF THE BUILDING AND IS NOT IN COMPLIANCE WITH THE CODE.
  
 PER NFPA 24
  
 6.2.11 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS
 FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE
 OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)*A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FT (12 M)
 FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FT (12 M) BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR
 VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH
 SECTION 6.4
 (4)*A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT
 LESS THAN 40 FT (12 M) FROM THE BUILDING
 (A) FOR BUILDINGS LESS THAN 40 FT (12 M) IN HEIGHT, A
 BACKFLOW
 PREVENTER WITH AT LEAST ONE INDICATING VALVE SHALL
 BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FT (12 M)
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES.
 6.5.1 WHERE USED IN ACCORDANCE WITH 6.2.11(4), BACKFLOW
 PREVENTION
 ASSEMBLIES SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 INSTALLATION INSTRUCTIONS.
 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED,
 THEY
 SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE
 NEEDED.
  
 PLEASE REVIEW AND CORRECT THE LOCATION PER THE
 REQUIREMENT.
  
  
 3) THERE ARE NO INDICATIONS OF A FIRE PUMP ROOM AND IF
 THAT FIRE PUMP ROOM HAS A FLOOR DRAIN AS REQUIRED.
  
 PER NFPA 20
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
 PLEASE REVIEW AND CORRECT OR CONFIRM AND PROVIDE A NOTE
 THAT IT SHALL BE INSTALLED WITH THE FOUNDATION.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
2019-03-20 13:30:07PLANS ARE STAMPED I JUST PLACED RESULTS INTO THE SYSTEM
 JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-09-16 Cont ID  
Sent By jgomez Date 2019-09-16 Time 18:38 Rev Time 0.00
Received By jgomez Date 2019-09-13 Time 13:35 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-11 Cont ID  
Sent By shill Date 2019-09-11 Time 08:18 Rev Time 0.00
Received By shill Date 2019-08-27 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-17 Cont ID  
Sent By lmarchan Date 2019-07-17 Time 10:14 Rev Time 0.00
Received By lmarchan Date 2019-05-28 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-15 Cont ID  
Sent By lmarchan Date 2019-04-15 Time 14:49 Rev Time 0.00
Received By lmarchan Date 2019-03-07 Time 12:25 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-08-28 Cont ID  
Sent By rmcdouga Date 2019-08-28 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2019-08-28 Time 18:00 Sent To  
Notes
2019-08-28 18:10:48THE OWNER'S REQUEST TO DEFER THE PAYMENT OF IMPACT FEES
 FOR THE FOUNDATION PERMIT UNTIL PRIOR TO ISSUANCE OF
 THE VERTICAL BUILDING PERMIT #19030235 HAS BEEN
 APPROVED BY THE BUILDING OFFICIAL AND PALM BEACH COUNTY
 IMPACT FEE OFFICE. A HOLD HAS BEEN PLACED ON THE
 ISSUANCE OF PERMIT #19030235 UNTIL THE IMPACT FEES HAVE
 BEEN PAID.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-07-11 Cont ID  
Sent By jgomez Date 2019-07-11 Time 13:17 Rev Time 0.00
Received By jgomez Date 2019-07-11 Time 13:17 Sent To  
Notes
2019-07-11 13:18:15IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM 2W01-2W14 WEST PALM BEACH, FL.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By jwitmer Date 2019-04-15 Time 14:08 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2019-04-15 14:08:02IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2019-09-16 Cont ID  
Sent By jgomez Date 2019-09-16 Time 09:23 Rev Time 0.00
Received By jgomez Date 2019-09-16 Time 09:23 Sent To  
Notes
2019-09-16 09:25:16PROVISO:
 1) THIS PROPOSED BUILDING IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH THE BASE FLOOD BFE: 12.7 FEET NAV88.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2019-09-11 Cont ID  
Sent By shill Date 2019-09-11 Time 08:18 Rev Time 0.00
Received By shill Date 2019-09-11 Time 08:18 Sent To  
Notes
2019-09-11 08:18:34SEE BUILDING REVIEW
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2019-07-11 Cont ID  
Sent By jgomez Date 2019-07-11 Time 13:14 Rev Time 0.00
Received By jgomez Date 2019-07-11 Time 13:14 Sent To  
Notes
2019-07-11 13:17:06 
 1) THIS PROPOSED BUILDING IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH THE BASE FLOOD BFE: 12.7 FEET NAV88.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By jwitmer Date 2019-04-15 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2019-04-15 Time 09:03 Sent To  
Notes
2019-04-15 14:14:212017 FBC- NFIP PLAN REVIEW
 W. P. B. PERMIT: 19030239 /CYAN APARTMENTS/ FOUNDATION
 PERMIT
 ADD: 1500 CENTREPARK BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-348-4805 CONTACT KARI NEVILLE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. APRIL 15/ 2019
  
 1) THIS PROPOSED BUILDING IS GOING TO BE BUILT IN A AE
 FLOOD ZONE WITH THE BASE FLOOD BFE: 12.7 FEET NAV88.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-09-16 Cont ID  
Sent By gjohnson Date 2019-09-16 Time 14:04 Rev Time 0.00
Received By gjohnson Date 2019-09-16 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-13 Cont ID  
Sent By shill Date 2019-08-13 Time 16:27 Rev Time 0.00
Received By gjohnson Date 2019-08-13 Time 16:27 Sent To  
Notes
2019-08-13 16:27:38REVIEWED REMOTELY BY T.HUNT
  
 PROVISO: ISSUED AT APPLICANT'S RISK
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-12 Cont ID  
Sent By thunt Date 2019-06-12 Time 12:17 Rev Time 0.00
Received By thunt Date 2019-06-12 Time 10:13 Sent To  
Notes
2019-06-12 12:18:46PLUMBING 2ND REVIEW**DENIED**PLAN REVIEW WAS LIMITED TO
 THE FOUNDATION AND 1ST FLOOR ONLY. A COMPLETE PLAN
 REVIEW WAS NOT PERFORMED.
  
 1) PROVIDE A 1ST FLOOR SANITARY AND WATER RISER
 DRAWING. FBC 107.3.5
  
 2) FILE 087, 088, AND 089 SEEM TO BE CORRUPTED AND
 UNABLE TO OPEN. PLEASE RESUBMIT. FBC 107.3.5
  
 3) PROVIDE 1ST FLOOR PLAN SHOWING ALL FAIR HOUSING
 (FHA) REQUIRED ELEMENTS IN EACH UNIT( CLEAR FLOOR
 SPACE, TURNING SPACE) AND LIST WHAT DESIGN SPEC EACH
 UNIT WILL BE. FBC 107.3.5
  
 4) PROVIDE 1ST FLOOR PLAN SHOWING ACCESSIBILITY
 REQUIREMENTS ARE BEING MEET IN THE PUBLIC RESTROOMS.
 CLEAR FLOOR SPACE, TURNING RADIUS, AND ACCESSIBLE
 ROUTES. FBC 107.3.5
  
 5) PROVIDE STORM WATER RISER ISOMETRIC IF ANY. FBC
 107.3.5
  
 *****PLAN REVIEW WAS LIMITED TO THE FOUNDATION AND 1ST
 FLOOR ONLY. A COMPLETE PLAN REVIEW WAS NOT
 PERFORMED*****
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-27 Cont ID  
Sent By thunt Date 2019-03-27 Time 06:38 Rev Time 0.00
Received By thunt Date 2019-03-26 Time 15:03 Sent To  
Notes
2019-03-27 06:38:14PLUMBING 1ST REVIEW**DENIED**
  
  
 A PLUMBING PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A PLUMBING PLAN REVIEW HAS NOT BEEN PERFORMED
 AT THIS TIME. PLUMBING PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF
 PLUMBING WORK TO BE DONE AT THIS TIME. WPB AMEND. TO
 FBC SEC. 107.2.1.YOUR COVER SHEET CALLS OUT FOR
 PLUMBING BUT NO PAGES FOUND.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 THUNT@CGA SOLUTIONS.COM
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-09-16 Cont ID  
Sent By shill Date 2019-09-16 Time 07:24 Rev Time 0.00
Received By shill Date 2019-09-16 Time 07:20 Sent To  
Notes
2019-09-16 07:26:30STRUCTURAL PAGES PREPARED BY EDUARDO GONZALEZ, PE ARE
 SHOWN AS "INVALID" IN ADOBE AND IT IS NOT POSSIBLE TO
 OPEN THE SIGNATURE PROPERTIES.
 THE SIGNATURE IS OK WHEN OPENED WITH PDF-XCHANGE
 EDITOR. THIS IS AN ONGOING ISSUE WHICH HAS NOT BEEN
 RESOLVED; SIGNATURE REVIEW PASSED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-09-11 Cont ID  
Sent By shill Date 2019-09-11 Time 08:17 Rev Time 0.00
Received By shill Date 2019-09-11 Time 08:17 Sent To  
Notes
2019-09-11 08:18:09SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SOILS REPORT IS NOT DIGITALLY SIGNED; DANIEL J.
 ZRALLACK, PE HAS PROVIDED DIGITALLY SIGNED DOCUMENTS
 WHICH HAVE BEEN FORWARDED TO THE PERMIT PROCESSOR TO
 UPLOAD.
  
 3RD REVIEW - THE DIGITALLY SIGNED SOILS REPORT WAS NOT
 UPLOADED; PLEASE UPLOAD WHEN RESUBMITTING.
  
 2. THE FOLLOWING PAGES ARE DIGITALLY SIGNED AND SEALED
 IN ACCORDANCE WITH FS471, 481. NEW PAGES SUBMITTED NEXT
 REVIEW CYCLE REQUIRE REVIEW:
  
 SURVEY
 CIVIL
 LANDSCAPE
 ARCHITECTURAL PAGES SIGNED AND SEALED BY BEATRIZ
 HERNANDEZ, MSA ARCHITECTS
 STRUCTURAL PAGES AND CALCULATIONS SIGNED AND SEALED BY
 J. EDUARDO GONZALEZ, PE
 ELECTRICAL PAGES SIGNED AND SEALED BY VIVIANA FRANYIE,
 PE
  
 2. SHEET 095 - S2.1.CJ.G CONTROL JOINT PLAN GARAGE.PDF
 WAS UPLOADED TO THE "SIGNATURES" FOLDER, BUT IT IS NOT
 DIGITALLY SIGNED. THIS DOCUMENT WILL BE REMOVED FROM
 THE "SIGNATURES" FOLDER; PLEASE DO NOT ADD ANY FILES TO
 THIS FOLDER. UPLOAD THE MOST CURRENT VERSION OF ALL
 PAGES TO THE "DRAWINGS" FOLDER. THIS PAGE IS ALREADY IN
 THE "DRAWINGS" FOLDER, DIGITALLY SIGNED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 09:03 Rev Time 0.00
Received By shill Date 2019-07-03 Time 09:03 Sent To  
Notes
2019-07-03 09:03:25SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SURVEY - OK
  
 2. CIVIL PAGES SIGNED AND SEALED BY ZACHARY D. TODD, PE
 ARE SELF CERTIFIED. FAC61G15-23 THIRD PARTY DIGITAL
 SIGNATURE REQUIRED. CHANGE ALL BUT ONLY RESUBMIT PAGES
 WHICH ARE SUBMITTED DUE TO CODE RELATED COMMENTS.
  
 3. SOILS REPORT IS NOT DIGITALLY SIGNED; DANIEL J.
 ZRALLACK, PE HAS PROVIDED DIGITALLY SIGNED DOCUMENTS
 WHICH HAVE BEEN FORWARDED TO THE PERMIT PROCESSOR TO
 UPLOAD. ENGINEER HAS BEEN ADVISED THAT A 3RD PARTY
 DIGITAL SIGNATURE IS REQUIRED FOR FUTURE SUBMITTALS.
  
 THE FOLLOWING PAGES ARE DIGITALLY SIGNED AND SEALED IN
 ACCORDANCE WITH FS471, 481. NEW PAGES SUBMITTED NEXT
 REVIEW CYCLE REQUIRE REVIEW:
  
 LANDSCAPE PAGES SIGNATURE OK - SUBMIT A SEPARATE
 LANDSCAPE PERMIT.
 ARCHITECTURAL PAGES SIGNED AND SEALED BY BEATRIZ
 HERNANDEZ, MSA ARCHITECTS
 STRUCTURAL PAGES AND CALCULATIONS SIGNED AND SEALED BY
 J. EDUARDO GONZALEZ, PE
 ELECTRICAL PAGES SIGNED AND SEALED BY VIVIANA FRANYIE,
 PE
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By shill Date 2019-04-18 Time 06:24 Rev Time 0.00
Received By shill Date 2019-04-18 Time 06:24 Sent To  
Notes
2019-04-18 06:30:58SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SURVEY IS NOT DIGITALLY SIGNED. IT INCLUDES A SCAN
 OF A SIGNATURE AND A PRINTOUT OF THE DIGITAL SIGNATURE.
 PROVIDE DIGITALLY SIGNED SURVEY.
  
 2. SOILS REPORT IS NOT DIGITALLY SIGNED; EITHER PROVIDE
 A DIGITALLY SIGNED REPORT OR PROVIDE ONE PAPER ORIGINAL
 AFTER ALL REVIEWS HAVE PASSED. (SEE J.WITMER NOTES)
  
 THE FOLLOWING PAGES ARE DIGITALLY SIGNED AND SEALED IN
 ACCORDANCE WITH FS471, 481. NEW PAGES SUBMITTED NEXT
 REVIEW CYCLE REQUIRE REVIEW:
  
 CIVIL PAGES SIGNED AND SEALED BY ZACHARY D. TODD, PE
 LANDSCAPE PAGES SIGNATURE OK - SUBMIT A SEPARATE
 LANDSCAPE PERMIT.
 ARCHITECTURAL PAGES SIGNED AND SEALED BY BEATRIZ
 HERNANDEZ, MSA ARCHITECTS
 STRUCTURAL PAGES AND CALCULATIONS SIGNED AND SEALED BY
 J. EDUARDO GONZALEZ, PE
  
  
  
2019-04-15 14:16:57) THE SUBMITTED GEOTECHNICAL REPORT BY ARDAMAN &
 ASSOCIATES FILE NO. 18-1735 OCT. 23/ 2018 APPEARS TO BE
 A PAPER REPORT THAT WAS UPLOADED, THE REPORT DOES NOT
 HAVE ELECTRONIC SIGNATURES.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. JAMES A.
 WITMER BN, PX, SFP, CBO
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2019-08-29 Cont ID  
Sent By pvalenti Date 2019-08-29 Time 14:32 Rev Time 0.00
Received By pvalenti Date 2019-08-29 Time 14:32 Sent To  
Notes
2019-09-11 14:44:58PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 THE THRESHOLD/SPECIAL INSPECTOR'S AGREEMENT HAS BEEN
 APPROVED FOR THIS PERMIT (FOUNDATION) ONLY. A SEPERATE
 APPLICATION IS REQUIRED FOR THE MASTER PERMIT
 (#19030235). WE ARE WAITING FOR THE PERMIT APPLICATION,
 AS THE CONTRACTOR'S SIGNATURE (CONTRACTOR HAS NOT BEEN
 DETERMINED) IS REQUIRED.
  
  
 THRESHOLD COMPANY:
 ONM&J
  
 THRESHOLD INSPECTOR:
 JOSEPH F. MINCUZZI PE 38162/THRESHOLD REGISTRATION 952
  
 THRESHOLD INSPECTOR REPRESENTATIVES:
 CHARLES MOCK BN 3682
 ERIC HERNANDEZ BN 3465
 VICTOR DAVIS BN 4790
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2019-08-08 Cont ID  
Sent By pvalenti Date 2019-08-08 Time 08:59 Rev Time 0.00
Received By pvalenti Date 2019-08-08 Time 08:59 Sent To  
Notes
2019-08-08 09:18:19***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW THRESHOLD INSPECTOR AGREEMENT DENIED:
  
 1. COMPLETE THE UPDATED "GUIDELINES AND POLICIES FOR
 PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND
 RESIDENT INSPECTORS" FORM, THE AGREEMENT THAT WAS
 FILLED OUT IS NO LONGER IN USE.
 2. PROVIDE RESUMES FOR ALL INDIVIDUALS ON THE SUBMITTED
 AGREEMENT.
 3. THIS AGREEMENT IS FOR THE FOUNDATION ONLY (PERMIT #
 19030239). IF THIS AGREEMENT IS INTENDED FOR THE MAIN
 BUILDING PERMIT, PLEASE ADD NUMBER.
 4. PLEASE PROVIDE A SIGNED LETTER FROM OWNER STATING
 THAT ONM&J IS TO PERFORM THE THRESHOLD INSPECTIONS.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-07-11 Cont ID  
Sent By jgomez Date 2019-07-10 Time 13:37 Rev Time 0.00
Received By jgomez Date 2019-07-10 Time 13:37 Sent To  
Notes
2019-07-10 13:37:4807/31/19 REVISED COMMENTS:
  
 1- PLEASE NOTE A 7 STORY BUILDING QUALIFIES AS A
 THRESHOLD BUILDING / FL S. S. 553.71(7) THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) THRESHOLD INSPECTOR: CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 RESPONSE:
 (1)THE THRESHOLD INSPECTION FORM SUBMITTED IS OLD. NEED
 TO USE REVISED FORM. ALSO, THE FORM NEEDS TO BE SIGNED
 AND SEALED BY THE ENGINEER AS REQUIRED BY CHAPTER 471
 AND CITY THRESHOLD BUILDINGS SPECIAL INSPECTOR PROGRAM.
 SEE REVISED CITY THRESHOLD BUILDINGS SPECIAL INSPECTOR
 PROGRAM DATED OCTOBER 2018 AND USE PROPER FORMS.
  
 (2)THRESHOLD INSPECTOR QUALIFICATIONS ARE REQUIRED TO
 BE REVIEWED/ACCEPTED BY THE ENGINEER OF RECORD WHO
 PREPARED THE THRESHOLD INSPECTION PLAN. SEE SECTION B
 OF PART I OF THRESHOLD INSPECTION PLAN ON SHEET S-1.1.
 SEC. 110.8.1 CITY AMENDMENTS.
  
 B) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTES.
  
 RESPONSE:
 ONLY THE ARCHITECTURAL PLANS HAVE THIS STATEMENT. THE
 STRUCTURAL PLANS DON'T HAVE THIS STATEMENT.
  
 C) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA. FOR A JOBSITE
 REPRESENTATIVE IS NOT AN ARCHITECT OR ENGINEER THEN
 THEY MUST HAVE A BN LICENSE NUMBER UNDER
 F. S. 468.
  
 RESPONSE:
 MISSING THE RESUME FOR ONE OF THE THRESHOLD INSPECTOR'S
 REPRESENTATIVE. PROVIDE THE RESUME FOR CHARLES MOCK.
  
 D) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-09-16 Cont ID  
Sent By jroach Date 2019-09-16 Time 10:52 Rev Time 0.00
Received By jroach Date 2019-09-16 Time 10:52 Sent To  
Notes
2019-09-16 10:52:37ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 09.16.2019
 PERMIT NO.: 19030239
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE SCOPE OF THIS REVIEW IS LIMITED TO THE BUILDING
 FOUNDATION ONLY!
  
 2. SEPARATE PERMITS REQUIRED FOR THE BUILDING
 STRUCTURE, SURROUNDING SITE WORK, HARDSCAPE, FENCING,
 PARKING, LANDSCAPING, SIGNAGE, ETC.
  
 3. THE PROJECT IS SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 22-19, AS
 APPROVED BY THE CITY COMMISSION ON FEBRUARY 25, 2019,
 AND AS MAY BE AMENDED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-09-10 Cont ID  
Sent By jroach Date 2019-09-10 Time 15:42 Rev Time 0.00
Received By jroach Date 2019-09-10 Time 15:25 Sent To  
Notes
2019-09-10 15:42:14ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 09.10.2019
 PERMIT NO.: 19030239
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE SCOPE OF THIS REVIEW IS LIMITED TO THE BUILDING
 FOUNDATION ONLY!
  
 2. SEPARATE PERMITS REQUIRED FOR THE BUILDING
 STRUCTURE, SURROUNDING SITE WORK, HARDSCAPE, FENCING,
 PARKING, LANDSCAPING, SIGNAGE, ETC.
  
 3. THE PROJECT IS SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 22-19, AS
 APPROVED BY THE CITY COMMISSION ON FEBRUARY 25, 2019,
 AND AS MAY BE AMENDED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-17 Cont ID  
Sent By jroach Date 2019-07-17 Time 10:06 Rev Time 0.00
Received By jroach Date 2019-07-17 Time 10:06 Sent To  
Notes
2019-07-17 10:07:55ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.17.2019
 PERMIT NO.: 19030239
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 THE SCOPE OF THIS REVIEW IS LIMITED TO THE FOUNDATION
 OF THE BUILDING AND THE SURROUNDING SITE WORK. COMMENTS
 RELATING TO THE BUILDING WILL BE ISSUED SEPARATELY WITH
 THE BUILDING PERMIT REVIEW. PLEASE PROVIDE A WRITTEN
 RESPONSE TO THE FOLLOWING PLAN REVIEW COMMENTS:
  
 1. PLEASE REMOVE THE LANDSCAPE PLANS FROM THE
 FOUNDATION PERMIT SUBMITTAL AS THE LANDSCAPE PLANS ARE
 TO BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION.
  
 2. CIVIL PLANS DO NOT REFLECT THE CORRECT SCOPE OF WORK
 THAT IS REQUIRED WITHIN THE CENTREPARK DRIVE
 RIGHT-OF-WAY, INCLUDING THE PROVISION OF ON-STREET
 PARKING, PROTECTED BIKE LANE, ETC.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By jroach Date 2019-04-04 Time 10:27 Rev Time 0.00
Received By jroach Date 2019-04-04 Time 10:26 Sent To  
Notes
2019-04-04 10:27:12ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.03.2019
 PERMIT NO.: 19030239
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 THE SCOPE OF THIS REVIEW IS LIMITED TO THE FOUNDATION
 OF THE BUILDING AND THE SURROUNDING SITE WORK. COMMENTS
 RELATING TO THE BUILDING WILL BE ISSUED SEPARATELY WITH
 THE BUILDING PERMIT REVIEW. PLEASE PROVIDE A WRITTEN
 RESPONSE TO THE FOLLOWING PLAN REVIEW COMMENTS:
  
 1. PLEASE CLARIFY WHY A DIFFERENT SITE PLAN WAS
 DEVELOPED FOR PERMITTING, AS OPPOSED TO USING THE SITE
 PLAN PREPARED BY SCHMIDT NICHOLS, WHICH WAS APPROVED BY
 THE CITY COMMISSION? THE SITE PLAN SUBMITTED FOR
 PERMITTING DOES NOT MATCH THAT WHICH WAS APPROVED AND A
 SIGNIFICANT AMOUNT OF INFORMATION IS NOW MISSING.
  
 2. PLEASE REMOVE THE LANDSCAPE PLANS FROM THE
 FOUNDATION PERMIT SUBMITTAL AS THE LANDSCAPE PLANS ARE
 TO BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION.
  
 3. PURSUANT TO RESOLUTION NO. 98-17 (CENTREPARK
 AFFORDABLE AND WORKFORCE HOUSING POLICY), THE DEVELOPER
 SHALL CONTRIBUTE $150 PER DWELLING UNIT TO THE CITY?S
 WORKFORCE HOUSING TRUST FUND UPON OBTAINING SITE PLAN
 APPROVAL. PLEASE PROVIDE PROOF THAT SUCH CONTRIBUTION
 HAS BEEN SATISFIED.
  
 4. CIVIL PLANS DO NOT REFLECT THE SCOPE OF WORK THAT IS
 REQUIRED WITHIN THE CENTREPARK DRIVE RIGHT-OF-WAY,
 INCLUDING THE PROVISION OF ON-STREET PARKING, PROTECTED
 BIKE LANE, ETC.
  
 5. THE CIVIL PLANS INDICATE THAT DRAINAGE IS OCCURRING
 OFF-SITE WITHIN THE CENTREPARK?S POA PARCEL LOCATED AT
 THE CORNER OF AUSTRALIAN AVENUE AND CENTREPARK DRIVE.
 PLEASE PROVIDE PROOF OF AN EASEMENT.
  
 6. THE FLOOR PLANS DO NOT MATCH THAT WHICH WAS APPROVED
 BY THE CITY COMMISSION (RESOLUTION NO. 22-19). ALL
 PLANS SUBMITTED FOR PERMITTING SHALL BE CONSISTENT WITH
 THE APPROVED PLANS. MODIFICATIONS TO THE APPROVED PLANS
 SHALL REQUIRE AN AMENDMENT TO THE CENTREPARK COMMERCIAL
 PLANNED DEVELOPMENT (CPD). ONE AREA OF SPECIFIC CONCERN
 IS THE FRONT STOOPS LEADING INTO THE GROUND FLOOR
 UNITS/ENTRANCES. STEPS/STOOPS ENCROACHING INTO THE
 SETBACK SHALL NOT EXCEED THREE (3) FEET IN HEIGHT.
 PLEASE CONFIRM THAT ALL STEPS/STOOPS ENCROACHING INTO
 THE SETBACK ARE LESS THAN THREE (3) FEET IN HEIGHT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy