Plan Review Details - Permit 19030149
Plan Review Stops For Permit 19030149
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-14 Cont ID  
Sent By tklarge Date 2019-03-14 Time 14:13 Rev Time 0.00
Received By tklarge Date 2019-03-14 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-07 Cont ID  
Sent By tklarge Date 2019-03-07 Time 10:41 Rev Time 0.00
Received By tklarge Date 2019-03-05 Time 13:43 Sent To  
Notes
2019-03-06 13:43:44ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-14 Cont ID  
Sent By tklarge Date 2019-03-14 Time 14:13 Rev Time 0.00
Received By tklarge Date 2019-03-14 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By tklarge Date 2019-03-07 Time 10:40 Rev Time 0.00
Received By tklarge Date 2019-03-07 Time 10:33 Sent To  
Notes
2019-03-07 10:40:431) THE PLANS ARE SOMEWHAT CONFUSING AS TO THE SCOPE OF
 WORK.IF THE PIPING AND TOILET FLANGES ARE BEING
 REPLACED, WHERE ARE THE 3 INCH LINES TO THE WATER
 CLOSETS? THE PLAN ONLY SHOWS 2 INCH PIPING BEING
 REPLACED. CLARIFY.
 2) SUBMIT A SANITARY RISER DIAGRAM THAT CLEARLY
 REFLECTS THE SCOPE OF WORK TO BE DONE. WPB AMEND. TO
 FBC SEC. 107.3.5.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  