Plan Review Details - Permit 19021385
Plan Review Stops For Permit 19021385
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By fgiaquin Date 2019-03-11 Time 07:10 Rev Time 0.00
Received By fgiaquin Date 2019-03-11 Time 06:52 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By fgiaquin Date 2019-03-06 Time 06:48 Rev Time 0.00
Received By fgiaquin Date 2019-03-06 Time 06:35 Sent To M
Notes
2019-03-06 06:46:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-04 Cont ID  
Sent By scaldero Date 2019-03-04 Time 10:18 Rev Time 0.00
Received By scaldero Date 2019-03-04 Time 10:13 Sent To  
Notes
2019-03-04 10:18:31PERMIT #19021385
 FIRE REVIEW COMMENTS
  
 1) STAGE AREA MAY REQUIRE AN ADDITIONAL NOTIFICATION
 DEVICE FOR PROPER COVERAGE. TO BE DETERMINED IN THE
 FIELD AT TIME OF ALARM TESTING.
  
 SUE ELLEN CALDERON
 ASST, FIRE MARSHAL
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-18 Cont ID  
Sent By hmoser Date 2019-03-18 Time 13:22 Rev Time 0.00
Received By hmoser Date 2019-03-07 Time 09:04 Sent To  
Notes
2019-03-07 09:05:06RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-03-06 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-28 Time 12:57 Sent To  
Notes
2019-03-01 12:58:07ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-03-18 Cont ID  
Sent By hmoser Date 2019-03-18 Time 11:52 Rev Time 0.00
Received By hmoser Date 2019-03-18 Time 11:34 Sent To I
Notes
2019-03-18 11:52:01PASS PROVISO
 REFER TO SECTION 606.4.1 SUPERVISION 2017
 FBC (M) A DUCT SMOKE DETECTOR SHALL BE
 CONNECTED TO A FIRE ALARM SYSTEM.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By ccole Date 2019-03-06 Time 10:23 Rev Time 0.00
Received By ccole Date 2019-03-06 Time 10:19 Sent To I
Notes
2019-03-06 10:24:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19021385
 3/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SIGNATURE OF CONTRACTOR/QUALIFIER REQUIRED ON THE
 PLANS- SEE SECTION 107.2.1 WPB: ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  