Plan Review Details - Permit 19021325
Plan Review Stops For Permit 19021325
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-19 Cont ID  
Sent By dbattles Date 2019-04-19 Time 12:36 Rev Time 0.00
Received By dbattles Date 2019-04-19 Time 12:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By dbattles Date 2019-03-06 Time 16:52 Rev Time 0.00
Received By dbattles Date 2019-03-06 Time 16:52 Sent To  
Notes
2019-03-06 16:52:41****CORRECTIONS****
 W.P.B. PERMIT: 19021325
 REVIEWED: MARCH 6, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA OR PERFORMANCE)
  
 2) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
  THE PLANS STATE LEVEL 1, BUT THIS WOULD BE A LEVEL 2
 DUE TO THE RE-ARRANGEMENT OF SPACES AND POSSIBLE A
 LEVEL 3 IF OVER 50 % OF THE BUILDING IS INCLUDED IN THE
 WORK. PLEASE REVIEW AND REVISE TO MEET DEFINITION THAT
 APPLIES.
  
 3) 1004.1 FBC[B] DESIGN OCCUPANT LOAD. IN DETERMINING
 MEANS OF EGRESS REQUIREMENTS, THE NUMBER OF OCCUPANTS
 FOR WHOM MEANS OF EGRESS FACILITIES ARE PROVIDED SHALL
 BE DETERMINED IN ACCORDANCE WITH THIS SECTION.
  ADD OCCUPANT LOAD ON SHEET L1.01
  
 4) 302 FBC[B] WHAT IS THE EXISTING OCCUPANCY AND WHAT
 IS THE PROPOSED OCCUPANCY?
  PLEASE ADD TO SHEET L1.01
  
 5) 402.1 FBC[A] PROVIDE ACCESSIBLE ROUTE FROM PARKING
 LOT. IN ADDITION TO ACCESSIBLE ENTRANCES REQUIRED BY
 SECTIONS 1105.1.1 THROUGH 1105.1.7 (PARKING GARAGE
 ENTRANCES, ENTRANCES FROM TUNNELS OR ELEVATED WALKWAYS,
 RESTRICTED ENTRANCES, ENTRANCES FOR INMATES OR
 DETAINEES, SERVICE ENTRANCES AND ENTRANCES TO TENANT
 SPACES, DWELLING UNITS AND SLEEPING UNITS), AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL BE ACCESSIBLE.
 SEE THE EXCEPTIONS FOR ENTRANCES TO AREAS NOT REQUIRED
 TO BE ACCESSIBLE AND LOADING/SERVICE ENTRANCES THAT ARE
 NOT THE ONLY TENANT SPACE ENTRANCE. SHEET L1.01 SHOWS 4
 INCH STEP DOWN AT EACH EXIT. HOW IS ACCESSBLE ROUTE TO
 BE PROVIDED, OR WHAT EXEMPTION ALLOWS FOR NO ACCESSIBLE
 PATH TO BE PROVIDED?
  
 6) 1013.1 FBC[B] SHEET L1.01 SHOWS AN EGRESS PATH GOING
 THROUGH TWO EXISTING DOORS AND OUT THE BACK.
  PLEASE USE EXIT SIGNS TO INDICATE EGRESS PATH.
  
 7) 1017.2 FBC[B] LIMITATIONS. EXIT ACCESS TRAVEL
 DISTANCE SHALL NOT EXCEED THE VALUES GIVEN IN TABLE
 1017.2.
  
 8) 1017.3 FBC[B] MEASUREMENT. EXIT ACCESS TRAVEL
 DISTANCE SHALL BE MEASURED FROM THE MOST REMOTE POINT
 WITHIN A STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH
 OF HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE
 ENTRANCE TO AN EXIT.
  SHOW TRAVEL DISTANCE FROM THE MOST REMOTE POINT.
  
 9) 107.3.5 FBC[AMENDED] SHOW THE EXISTING BATHROOMS ON
 PLANS AND LABEL ROOMS ACCORDINGLY.
  ALSO, SHOW ANY ADA COMPLIANCE THAT IS PROVIDED IN THE
 BATHROOMS.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By jpearson Date 2019-04-22 Time 09:48 Rev Time 0.00
Received By jpearson Date 2019-04-22 Time 09:48 Sent To  
Notes
2019-04-22 09:49:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 2. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS TO CODE. NEC
 210.62 (NOT CORRECTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By jpearson Date 2019-03-06 Time 13:02 Rev Time 0.00
Received By jpearson Date 2019-03-06 Time 10:56 Sent To  
Notes
2019-03-06 13:02:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS TO CODE. NEC
 210.62
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By scaldero Date 2019-04-16 Time 10:17 Rev Time 0.00
Received By scaldero Date 2019-04-16 Time 10:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-04 Cont ID  
Sent By scaldero Date 2019-03-04 Time 11:26 Rev Time 0.00
Received By scaldero Date 2019-03-04 Time 11:09 Sent To  
Notes
2019-03-04 11:26:28PERMIT # 19021325
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) PER NFPA 101, CHAPTERS 36 & 37 - NEW AND
 EXISTINGMERCANTILE OCCUPANCY -
 IN MERCANTILE OCCUPANCIES CLASSIFIED AS ORDINARY
 HAZARD, TRAVEL DISTANCE SHALL NOT EXCEED 150 FT.
 IN MERCANTILE OCCUPANCIES CLASSIFIED AS ORDINARY HAZARD
 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 9.7.1.1(1), TRAVEL DISTANCE SHALL NOT EXCEED 250 FT.
  
 2) SHEET G1.01 INDICATES THE BUILDING IS "UNPROTECTED"
 WITH A FIRE ALARM. THEREFORE THE TRAVEL DISTANCE OF
 186' INDICATED ON SHEET L1.01 EXCEEDS THE PERMITTED
 TRAVEL DISTANCE AS OUTLINED IN NFPA 101. (SEE ABOVE.)
  
 3) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-04-22 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-11 Time 15:17 Sent To  
Notes
2019-04-12 15:17:54B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-06 Cont ID  
Sent By dbattles Date 2019-03-06 Time 16:52 Rev Time 0.00
Received By dbattles Date 2019-02-27 Time 15:25 Sent To  
Notes
2019-02-28 15:25:23B01