Plan Review Details - Permit 19021320
Plan Review Stops For Permit 19021320
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-01 Cont ID  
Sent By dbattles Date 2019-04-01 Time 15:03 Rev Time 0.00
Received By dbattles Date 2019-04-01 Time 15:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By dbattles Date 2019-03-07 Time 08:05 Rev Time 0.00
Received By dbattles Date 2019-03-05 Time 16:39 Sent To  
Notes
2019-03-07 08:06:22****CORRECTIONS****
 W.P.B. PERMIT: 19021320
 REVIEWED: MARCH 7, 2019
 UPDATED MARCH 3, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,5TH EDITION (2010)
 FBC[B] = FBC BUILDING
  
 1) 806.1.2 THE PERMISSIBLE AMOUNT AMOUNT OF DECORATIVE
 MATERIALS MEETING THE FLAME PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701 SHALL NOT EXCEED 10% OF THE WALL
 OR CEILING AREA TO WHICH IT IS ATTACHED.
  I HAVE THE FLOOR PLANS SHOWING LOCATIONS, BUT HAS THE
 PERCENTAGE OF WALL AREA BEEN CALCULATED TO MEET FBC
 806.1.2?
 THE WALL AREA CALCULATIONS CAN BE ADDED TO THE FLOOR
 PLANS, OR PROVIDE OTHER MEANS TO SHOW COMPLIANCE.
  
 2) 806.2 ACCEPTANCE CRITERIA AND REPORTS. WHERE
 REQUIRED BY 806.1, DECORATIVE MATERIALS SHALL BE TESTED
 BY AN AGENCY AND MEET FLAME PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701 OR SUCH MATERIALS SHALL BE
 NONCOMBUSTIBLE. REPORTS OF TEST RESULTS SHALL BE
 PREPARED IN ACCORDANCE WITH NFPA 701 AND FURNISHED TO
 THE BUILDING OFFICIAL UPON REQUEST.
  ARE THESE NFPA 701 TEST 1 AND CAN YOU SUPPLY THE
 REPORTS?
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-03-12 Cont ID  
Sent By fstal Date 2019-03-12 Time 14:01 Rev Time 0.00
Received By fstal Date 2019-03-12 Time 14:16 Sent To I
Notes
2019-03-12 14:05:50PROVIDE PERCENT OF AREA COVER FOR FIRE RATED COVERINGS
 ALSO SEE BUILDING COMMENTS.
  
  
 FRANK STALLWORTH FIRE INSPECTOR
 WEST PALM BEACH FIRE PREVENTION
 561-804-4724.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-13 Cont ID  
Sent By cpuell Date 2019-03-13 Time 13:16 Rev Time 0.00
Received By cpuell Date 2019-02-27 Time 16:10 Sent To  
Notes
2019-02-28 16:10:31ROUTED TO DBATTLES