2019-03-07 08:06:22 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 19021320 |
| REVIEWED: MARCH 7, 2019 |
| UPDATED MARCH 3, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,5TH EDITION (2010) |
| FBC[B] = FBC BUILDING |
| |
| 1) 806.1.2 THE PERMISSIBLE AMOUNT AMOUNT OF DECORATIVE |
| MATERIALS MEETING THE FLAME PROPAGATION PERFORMANCE |
| CRITERIA OF NFPA 701 SHALL NOT EXCEED 10% OF THE WALL |
| OR CEILING AREA TO WHICH IT IS ATTACHED. |
| I HAVE THE FLOOR PLANS SHOWING LOCATIONS, BUT HAS THE |
| PERCENTAGE OF WALL AREA BEEN CALCULATED TO MEET FBC |
| 806.1.2? |
| THE WALL AREA CALCULATIONS CAN BE ADDED TO THE FLOOR |
| PLANS, OR PROVIDE OTHER MEANS TO SHOW COMPLIANCE. |
| |
| 2) 806.2 ACCEPTANCE CRITERIA AND REPORTS. WHERE |
| REQUIRED BY 806.1, DECORATIVE MATERIALS SHALL BE TESTED |
| BY AN AGENCY AND MEET FLAME PROPAGATION PERFORMANCE |
| CRITERIA OF NFPA 701 OR SUCH MATERIALS SHALL BE |
| NONCOMBUSTIBLE. REPORTS OF TEST RESULTS SHALL BE |
| PREPARED IN ACCORDANCE WITH NFPA 701 AND FURNISHED TO |
| THE BUILDING OFFICIAL UPON REQUEST. |
| ARE THESE NFPA 701 TEST 1 AND CAN YOU SUPPLY THE |
| REPORTS? |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |