|
 |
 |
 |
 |
 |
Plan Review Details - Permit 19021237
Plan Review Stops For Permit 19021237 |
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2019-04-02 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-04-02 |
Time |
07:08 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-04-02 |
Time |
06:54 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2019-03-26 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-03-26 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-03-26 |
Time |
15:52 |
Sent To |
I |
|
Notes |
2019-03-26 15:54:44 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. WAP NOT LISTED. ONLY LISTED IN CANADA (CE MARKED) | | MUST BE LISTED BY UL OR OTHER NATIONALLY RECOGNIZED | | TESTING LABORATORY (NRTL). NEC 90.7,110.2,110.3B | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-03-19 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-03-19 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-03-19 |
Time |
07:06 |
Sent To |
I |
|
Notes |
2019-03-19 07:08:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. CUT SHEETS PROVIDED FOR DUAL-RADIO ACCESS POINTS ARE | | NOT UL OR OTHER NRTL LISTED. ONLY FCC, IC, AND CE. MUST | | BE TESTED AND LISTED BY NRTL. NEC 90.7, 110.2, 110.3B | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-03-12 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-03-12 |
Time |
06:59 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-03-12 |
Time |
06:49 |
Sent To |
I |
|
Notes |
2019-03-12 06:59:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | 2. PROVIDE UL OR OTHER NRTL LISTINGS FOR WIFI WAP'S AND | | SPEAKERS. ONLY CAMERA AND SMART SWITCH LISTINGS HAVE | | BEEN PROVIDED. PROVIDE CORRECTION. FBC 107.2.1 NEC | | 90.7,110.2,110.3B | | | | 3. VALUE FOR PROJECT SEEMS LOW. PROVIDE COPY OF SIGNED | | CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL | | MATERIALS AND LABOR. SIGNED BY OWNER AND CONTRACTOR. | | FBC 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2019-04-02 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-04-02 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-03-27 |
Time |
14:01 |
Sent To |
|
|
Notes |
2019-03-28 14:01:46 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-03-26 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-03-26 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-03-21 |
Time |
14:44 |
Sent To |
|
|
Notes |
2019-03-22 14:44:59 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-03-19 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-03-19 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-03-15 |
Time |
14:34 |
Sent To |
|
|
Notes |
2019-03-18 14:35:03 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-03-12 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-03-12 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-02-26 |
Time |
14:46 |
Sent To |
|
|
Notes |
2019-02-27 14:47:04 | ELEC <5K |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |