Plan Review Details - Permit 19021070
Plan Review Stops For Permit 19021070
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-07-25 Cont ID  
Sent By shill Date 2019-07-25 Time 12:21 Rev Time 0.00
Received By shill Date 2019-07-25 Time 12:20 Sent To  
Notes
2019-07-25 12:26:47****PROVISO - REVISION REQUIRED****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THERE ARE DISCREPANCIES BETWEEN THE ISSUED PERMIT AND
 THE REVISION SUBMITTED. FOR INSTANCE, URINALS AND LAV
 WERE REMOVED FROM SCOPE PREVIOUSLY, BUT NOW APPEAR ON
 THE PLAN WITHOUT INDICATING THAT THIS IS A REVISION.
 THE ACCESSIBLE RESTROOM 108 HAS TWO TOILETS IN THE
 SINGLE USER TOILET ROOM.
  
 REVISE THE PLAN TO CORRELATE. ALL CHANGES TO THE ISSUED
 PERMIT SHOULD BE CLOUDED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-12 Cont ID  
Sent By dbattles Date 2019-07-12 Time 12:52 Rev Time 0.00
Received By dbattles Date 2019-07-12 Time 12:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-21 Cont ID  
Sent By pvalenti Date 2019-06-21 Time 07:37 Rev Time 0.00
Received By pvalenti Date 2019-06-21 Time 07:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By jduprey Date 2019-04-10 Time 11:10 Rev Time 0.00
Received By jduprey Date 2019-04-10 Time 08:17 Sent To  
Notes
2019-04-10 11:10:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DRAWINGS INDICATE A 1HR SEPARATION BETWEEN BOTH
 OCCUPANCIES. PLEASE INDICATE WHICH OCCUPANCY IS THE
 BUSSINESS NEXT TO THE PROPOSE WORK OR PROVIDE MORE
 INFORMATION IN REGARDS THE INTENTION WITH THE PROPOSED
 WORK. FBC 107; FBC 302.1
  
 2. INDICATE FIRE RESISTANCE FOR THE NEW PROPOSED DOOR
 SEPARATING BOTH OCCUPANCIES. FBC CHAPTER 7.
  
 3. PLEASE INDICATE ON THE NANA WALL PRODUCT APPROVAL
 THE SIZE, WIND LOAD RESISTANCE AND DETAILS APPLICABLE
 TO THIS SPECIFIC INSTALLATION. FBC 107; FBC 1609
  
 4. PROVIDE BAR DIMENSIONS AND HEIGHT. FBC 107; FBC
 ACCESSIBILITY 226

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By jleahy Date 2019-06-18 Time 16:35 Rev Time 0.00
Received By jleahy Date 2019-06-18 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-28 Cont ID  
Sent By jleahy Date 2019-03-28 Time 09:45 Rev Time 0.00
Received By jleahy Date 2019-03-28 Time 08:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-07-26 Cont ID  
Sent By pleduc Date 2019-07-26 Time   Rev Time 0.00
Received By pleduc Date 2019-07-26 Time 10:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2019-07-03 Cont ID  
Sent By pleduc Date 2019-07-03 Time   Rev Time 0.00
Received By pleduc Date 2019-07-03 Time 10:58 Sent To  
Notes
2019-07-03 11:02:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) IN READING THE RESPONSE TO FIRE COMMENTS FROM
 GLIDDEN SPINA, THERE APPEARS TO SOME
 MISCOMMUNICATIONS/MISUNDERSTANDINGS.
  
 THERE CAN NOT BE OPPOSING EXITS AS PROPOSED. EXITS
 SHALL BE IN ONE DIRECTION.
  
 THERE IS NO DOUBT THAT THERE IS A CHALLANGE TO COMPLY
 WITH THE EXITING CODE WITH THIS CONFIGURATION.
  
 ONCE THE FRONT DOORS WERE REMOVED FROM THE EXPANSION
 AREA, IT CREATED A CONFLICT WITH THE CODE. I WAS
 ADVISED THAT THE BLDG. DEPT. REQUIRED THOSE DOORS TO BE
 REMOVED. I DO NOT SEE THOSE COMMENTS.
  
 PER THE PLANS, THERE IS A RATED WALL WITH THE DOOR
 OPENING BETWEEN THEM. ONCE THAT DOOR IS REMOVED IT
 CREATES ONE OCCUPANCY AND TWO EXITS ARE REQUIRED FROM
 THAT ONE OCCUPANCY.
  
 THE PROPOSED CONFLICTING DIRECTIONAL EXITS SIGNS ARE
 NONCOMPLIANT.
  
  
 THE FOLLOWING IS FOR RECOMMENDATION AND DISSCUSSION
 PURPOSES.
  
 1) REPLACE THE DOOR WITH A RATED DOOR CONSISTENT WITH
 THE WALL SEPARATION RATING. THIS CREATES IN ESSENCE.
 TWO OCCUPANCIES. ONE ASSEMBLY (THE ORIGINAL SPACE) AND
 ONE MERCANTILE(THE NEW SPACE, ASSEMBLY UNDER 50) PER
 THE FFPC, AND ONE EXIT IS ACCEPTABLE. REMOVE THE EXIT
 SIGN FROM THE NEW SSPACE. THE NEW RATED DOOR WOULD
 SWING INTO THE NEW SPACE AND WOULD BE THE 2ND EXIT FROM
 THAT ORIGINAL AREA.
  
  
 2) REMOVE THE EXIT SIGN FROM THE NEW SPACE AND REPLACE
 THE FRONT DOOR. TWO EXITS WOULD BE FROM EACH SPACE.
  
  
 RESPECTFULLY,
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-06-10 Cont ID  
Sent By pleduc Date 2019-06-10 Time   Rev Time 0.00
Received By pleduc Date 2019-06-10 Time 12:32 Sent To  
Notes
2019-06-10 12:46:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET ALS 1.1 - IT APPEARS THAT THE FRONT DOORS ON
 THE SOUTH BAR AREA HAVE BEEN CLOSED OFF, LEAVING ONLY
 ONE EXIT FROM THAT BAR AREA, TOW EXITS ARE REQUIRED.
  
 PER NFPA 101 CH 12 & 7
  
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE
 WITH SECTION 7.4, OTHER THAN EXITS FOR FENCED OUTDOOR
 ASSEMBLY
 OCCUPANCIES IN ACCORDANCE WITH 12.2.4.4.
  
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO,
 EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED
 IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE
 OR BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS
 OF
 CHAPTERS 11 THROUGH 43 ARE MET.
  
 ONE EXIT IS NOT ALLOWED IN CH 12.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-06 Cont ID  
Sent By pleduc Date 2019-03-06 Time   Rev Time 0.00
Received By pleduc Date 2019-03-06 Time 09:30 Sent To  
Notes
2019-03-06 10:11:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.1 - IS THIS ADDITION PROPOSED CLASSIFIED
 AS A MIXED OCCUPANCY, SEPARATED, OR NON-SEPARATED?
  
 PER NFPA 101, CH 6
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
  
 PLEASE CLARIFY.
  
  
 2) SHEET A 1.1.1- THERE IS AN INDICATION OF A 1 HOUR
 WALL BETWEEN THE TWO SPACES WITH A DOOR, 101A. THE DOOR
 SCHEDULE DOES NOT INDICATE ANY FIRE RATEING
  
 PLEASE CLARIFY THE SEPARATION FEATURES OR CORRECT AND
 PROVIDE A 1 HOUR FIRE RATED DOOR WITH APPLICABLE
 HARDWARE.
  
  
  
 3) SHEET A 1.1.1 - THERE IS A SHADED AREA INDICATED
 EAST OF THE PROPOSED ADDTION WITH A DOOR FROM THE
 ADDITION. WHAT IS THE OCCUPANCY CLASSIFICATION OF THIS
 SPACE?
  
 WHAT IS THE SEPARATION RATING REQUIRED FROM THIS SPACE
 PER NFPA 101, CH 6?
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE REVIEW AND CORRECT AND PROVIDE FOR THE
 REQUIREMENT.
  
  
  
  
 4) SHEET A 1.1.1 - DOOR 101 IS INDICATED AS HAVING A
 PASSAGE HANDLE AND DEAD BOLT.
  
 PER NFPA 101, CH 12
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 PER # 1 ABOVE WHAT IS THE COMBINED OCCUPANCY LOAD
 SERVED BY THIS EXIT?
  
 PLEASE CLARIFY OR CORRECT.
  
  
  
  
 5) SHEET A LS 1.1 - THERE IS AN OCCUPANCY LOAD
 INDICATED AS 62. IS THIS NUMBER REFLECTIVE OF JUST THIS
 PROPOSED ADDITION OR TOTAL FOR BOTH SPACES?
  
 PLEASE CLARIFY.
  
  
  
 6) SHEET A LS 1.1 - PER THE ABOVE, THE OCCUPANCY COUNT
 DOES NOT INDICATE/INCLUDE THE BAR SEATING, BAR AREA,
 FIXED SEATING, THE PIANO AREA, ETC. DOES THE SQ FT
 CALCULATION REFLECT THE REDUCTION OF THESE
 AREAS/INCLUDE THESE AREAS?
  
 PLEASE CLARIFY AS THE TOTAL OCCUPANCY LOAD COULD BE
 REDUCED/INCREASED AS APPLICABEL.
  
  
  
  
 7) SHEET A 1.1 & S 2.0 - AT DOOR 101A THERE IS AN
 INDICATION OF A RAMP AND A POSSIBLE STEP DOWN INTO THE
 PROPOSED SPACE. THERE ARE NO INDICATION OF HOW HIGH
 THIS POSSIBLE STEP IS?
  
 PLEASE CLARIFY AND CORRECT/SO DRAWING.
  
  
  
 8) SHEET S 2.0 - THERE ARE TWO RAMPS INDICATED, ONE
 INTERIOR & ONE EXTERIOR. THERE AR RAILINGS/GUARDS
 INDICATED; HOWEVER, THERE ARE NO DETAILS.
  
 PLEASE PROVIDE DETAILS FOR THE HANDRAILS AND GUARDS PER
 NFPA 101, CH 7.
  
 7.2.2.4.5* HANDRAIL DETAILS.
 7.2.2.4.5.1 NEW HANDRAILS ON STAIRS SHALL BE NOT LESS
 THAN 34 IN.
 (865 MM), AND NOT MORE THAN 38 IN. (965 MM), ABOVE THE
 SURFACE
 OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE
 RAIL FROM THE
 LEADING EDGE OF THE TREAD.
  
 7.2.2.4.6 GUARD DETAILS. SEE 7.1.8 FOR GUARD
 REQUIREMENTS.
 7.1.8* GUARDS. GUARDS IN ACCORDANCE WITH 7.2.2.4 SHALL
 BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS THAT
 EXCEED 30 IN.
 (760 MM) ABOVE THE FLOOR OR THE FINISHED GROUND LEVEL
 BELOW
 EXCEPT WHERE GUARDS ARE SPECIFICALLY EXEMPTED BY
 PROVISIONS OF
 CHAPTERS 11 THROUGH 43.
  
 PLEASE PROVIDE APPLICABLE DRAWING DETAILS IN
 COMPLIANCE.
  
  
  
 9) PER # 1 AND NFPA 101, CH 12 THIS IS AN ASSEMBLY
 OCCUPANCY WITH A POSSIBLE TOTAL OCCUPANCY LOAD OVER
 100.
  
 ADDITIONALLY, IT CAN BE CONSIDERED A NIGHTCLUB.
  
 12.3.5 EXTINGUISHMENT REQUIREMENTS.
 12.3.5.1 THE WHERE THE OCCUPANT LOAD EXCEEDS 100, THE
 FOLLOWING
 ASSEMBLY OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY
 AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH 9.7.1.1(1):
 (1) DANCE HALLS
 (2) DISCOTHEQUES
 (3) NIGHTCLUBS
 (4) ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING
  
 HOWEVER, THERE IS NO DEFINITION OF NIGHTCLUB IN NFPA
 101.
  
 PER NFPA 101, CH 3
  
 3.1.1 WHERE TERMS ARE NOT DEFINED IN THIS CHAPTER,
 WITHIN ANOTHER
 CHAPTER, OR THE FLORIDA BUILDING CODE, THEY SHALL BE
 DEFINED USING
 THEIR ORDINARILY ACCEPTED MEANINGS WITHIN THE CONTEXT
 IN WHICH
 THEY ARE USED. WEBSTER?S THIRD NEW INTERNATIONAL
 DICTIONARY OF
 THE ENGLISH LANGUAGE, UNABRIDGED, SHALL BE A SOURCE FOR
 ORDINARILY ACCEPTED MEANING.
  
 PER WEBSTERS
  
  
 DEFINITION OF NIGHTCLUB : A PLACE OF ENTERTAINMENT OPEN
 AT NIGHT USUALLY SERVING FOOD AND LIQUOR
 AND PROVIDING MUSIC AND SPACE FOR DANCING AND OFTEN
 HAVING A FLOOR SHOW
  
  
 PLEASE REVIEW AND CLARIFY, HOW THE PROPOSED WILL BE
 USED, SEPARATED, AND PROTECTED PER THE REQUIRMENTS OF
 THE CODE.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-30 Cont ID  
Sent By lmarchan Date 2019-07-30 Time 08:56 Rev Time 0.00
Received By lmarchan Date 2019-07-23 Time 08:23 Sent To  
Notes
2019-07-29 15:37:33ZONING PROVISO: TREES REMOVED FOR ADA RAMP SHALL BE
 MITIGATED THROUGH TREE ALTERATION PERMIT
 EL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-18 Cont ID  
Sent By elevesqu Date 2019-07-18 Time 14:17 Rev Time 0.00
Received By elevesqu Date 2019-06-30 Time 07:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-26 Cont ID  
Sent By hmoser Date 2019-06-26 Time 14:23 Rev Time 0.00
Received By hmoser Date 2019-06-07 Time 12:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-10 Cont ID  
Sent By jduprey Date 2019-04-10 Time 11:12 Rev Time 0.00
Received By jduprey Date 2019-02-26 Time 10:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-08-20 Cont ID  
Sent By lmarchan Date 2019-08-20 Time 11:39 Rev Time 0.00
Received By lmarchan Date 2019-07-30 Time 09:13 Sent To  
Notes
2019-08-15 16:03:55RECEIPT - MU-2019-0815-314 - $56.14 PAID
2019-07-30 09:13:597/30/19 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By jduprey Date 2019-04-10 Time 10:14 Rev Time 0.00
Received By jduprey Date 2019-04-10 Time 10:13 Sent To  
Notes
2019-04-10 10:14:15PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-26 Cont ID  
Sent By hmoser Date 2019-06-26 Time 14:22 Rev Time 0.00
Received By hmoser Date 2019-06-26 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By ccole Date 2019-04-09 Time 13:45 Rev Time 0.00
Received By ccole Date 2019-04-09 Time 12:56 Sent To  
Notes
2019-04-09 14:23:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19021070
 4/9/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 RTU-1 SYSTEM- SECTION C403.2.1 FBC EC
  
 2) SHEET M1.1.1: A DUCT SMOKE DETECTOR IS REQUIRED IN
 THE SUPPLY AIR SYSTEM OF THE 5-TON RTU PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE
 SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 3) M1.1.1 & M1.1.2: PROVIDE AN AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPER FOR THE RTU OUTDOOR AIR INTAKE- SECTION
 C403.2.4.3 FBC-EC.
  
 4) M2.1.1: THE VENTILATION CALCULATIONS ARE NOT IN
 COMPLIANCE WITHTABLE 403.3.1.1 FBC M. THE RATE IS
 CALCULATED AT 100 PWRSONS PER 1000 SF. AT 7.5 CFMS PER
 PERSON + 0.18 CFMS PER SF. PLEASE CORRECT.
  
 5) M1.1.2: STRUCTURAL ENGINEERING IS REQUIRED FOR THE
 NEW ROOF OPENING, AND INSTSALLATIONS OF THE NEW CURB
 AND RTU- SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-07-16 Cont ID  
Sent By gjohnson Date 2019-07-16 Time 17:28 Rev Time 0.00
Received By gjohnson Date 2019-07-16 Time 10:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By gjohnson Date 2019-06-20 Time 12:33 Rev Time 0.00
Received By gjohnson Date 2019-06-20 Time 11:34 Sent To  
Notes
2019-06-20 12:39:192ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SINKS IN THE BAR AREA SHALL BE REQUIRED TO HAVE
 A GREASE INTERCEPTOR EVEN THOUGH IT IS JUST DRINKS SOME
 WILL HAVE DAIRY AND THAT PRODUCES GREASE. PER FBC PL
 1003.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-08 Cont ID  
Sent By thunt Date 2019-04-08 Time 10:54 Rev Time 0.00
Received By thunt Date 2019-04-05 Time 15:22 Sent To  
Notes
2019-04-08 10:55:36PLUMBING 1ST REVIEW**DENIED**BACKFLOW AND INTERCEPTOR
 SUB PERMIT REQUIRED**# 19021070
  
 1) PROVIDE NOTES ON PLUMBING SHT.P1.1.1 BACKFLOW AND
 INTERCEPTOR REQUIRED SEPERATE PLUMBING PERMITS.
  
 2) TANKLESS WATER HEATER IS UNDERSIZED AND WILL NOT
 PROVIDE FIXTURES WITH HOT WATER. PROVIDE TANKLESS
 MANUFACTURES INSTALLATION MANUAL THAT WILL SUPPORT HOT
 WATER TO EACH FIXTURE. FBC-P 607.1
  
 3) SHOW RESTROOM FACUETS WATER WILL BE TEMPERED BY A
 ASSE 1070 DEVICE. FBC-P 607.1.2
  
 4) THE GREASE INTERCEPTOR SHALL BE REQUIRED TO HAVE 1
 VENT THAT EXTENDS TO THE OUTDOORS. THE INTERCEPTOR
 SHALL NOT BE AIR BOUND AND AAV'S NOT NOT RATED FOR
 POSITIVE PRESSURE. FBC-P 904.1, 1003.2
  
 5) PLAN IS MISSING THE REQUIRED SERVICE SINK. FBC-P
 403.1
  
 6) THE WATER SUPPLY DROPS ARE MISSING THE SHUT OFF
 SERVICE VALVES. FBC-P 606.1
  
 7) PROVIDE COMPLETE INSTALLATION MANUAL FOR THE GREASE
 INTERCEPTOR AND BOTH TANKLESS WATER HEATERS. FBC
 107.2.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-07-25 Cont ID  
Sent By shill Date 2019-07-25 Time 12:28 Rev Time 0.00
Received By shill Date 2019-07-25 Time 12:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-07-12 Cont ID  
Sent By dbattles Date 2019-07-12 Time 12:52 Rev Time 0.00
Received By dbattles Date 2019-07-12 Time 12:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-06-21 Cont ID  
Sent By shill Date 2019-06-21 Time 12:39 Rev Time 0.00
Received By shill Date 2019-06-21 Time 12:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-04-10 Cont ID  
Sent By ccole Date 2019-04-09 Time 14:26 Rev Time 0.00
Received By jduprey Date 2019-04-10 Time 11:12 Sent To  
Notes
2019-04-10 10:15:06ARCH AND STRUCTURAL SHEETS GOOD
2019-04-09 14:27:03MECH SHEETS GOOD.

Review Stop Z ZONING
Rev No 4 Status P Date 2019-07-29 Cont ID  
Sent By elevesqu Date 2019-07-29 Time 15:35 Rev Time 0.00
Received By elevesqu Date 2019-07-29 Time 15:35 Sent To  
Notes
2019-07-29 15:36:38PROVISO: TREES REMOVED FOR ADA RAMP SHALL BE MITIGATED
 THROUGH TREE ALTERATION PERMIT
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2019-07-18 Cont ID  
Sent By elevesqu Date 2019-07-18 Time 14:00 Rev Time 0.00
Received By elevesqu Date 2019-07-18 Time 14:00 Sent To  
Notes
2019-07-18 14:01:33REPEAT COMMENT:
 4. PLEASE SUBMIT THE TREE ALTERATION PERMIT FOR THE
 PALM TREES- REQUIRED PRIOR TO APPROVAL OF THIS PERMIT
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-06-24 Cont ID  
Sent By elevesqu Date 2019-06-24 Time 14:45 Rev Time 0.00
Received By elevesqu Date 2019-06-24 Time 14:44 Sent To  
Notes
2019-06-24 14:45:151. PLEASE CONFIRM WITH BUILDING DEPARTMENT FOR
 PROJECTION STANDARDS FOR NANA WALLS.
 2. THERE WERE NO DETAILS OF THE NEW DOORS PROVIDED.
 PLEASE PROVIDE THIS DETAIL
 3. DO YOU HAVE DETAIL OF THE PROPOSED EQUIPMENT
 SCREENING? PLEASE WORK WITH OWNER TO PROVIDE SCREENING
 THAT WILL BE CONSISTENT WITH THE BUILDING. PLEASE
 PROVIDE SCREENING DETAIL
 4. PLEASE SUBMIT THE TREE ALTERATION PERMIT FOR THE
 PALM TREES- REQUIRED PRIOR TO APPROVAL OF THIS PERMIT
 UNTIL SUBMITTED
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By aaponte Date 2019-03-15 Time 10:56 Rev Time 0.00
Received By elevesqu Date 2019-03-15 Time 10:32 Sent To  
Notes
2019-03-15 10:56:11IS THIS AN EXANSION OF THE 123 DATURA RESTAURANT?
 PLEASE CLARIFY
 THE TWO BUILDINGS ARE ON TWO SEPARATE PROPERTIES.
 PLEASE WORK WITH BUILDING DEPARTMENT- CANNOT COMBINE
 TWO BUILDINGS ON TWO SEPARATE PROPERTIES
  
 PLEASE PROVIDE ELEVATIONS OF SOUTH AND EAST FACADES FOR
 BOTH EXISTING (SHOWING DEMOLITION PLANS) AND PROPOSED
 ELEVATIONS (ILLUSTRATING PROPOSED CHANGES)
  
 PLEASE INCLUDE ROOF PLAN AND SHOW SCREENING OF ANY NEW
 PROPOSED ROOF MOUNTED EQUIPMENT.
 WILL THERE BE ANY GROUND MOUNTED EQUIPMENT? PLEASE
 ILLUSTRATE IF THERE WILL BE AND PROVIDE SCREENING.
  
 THERE ARE PALM TREES WHERE THE NEW RAMP IS PROPOSED.
 PLEASE PROVIDE INFORMATION OF WHAT WILL HAPPEN TO THE
 PALMS. IF NOT REQUIRED FOR ADA ACCESS, PLEASE CONSIDER
 NOT PROPOSING A RAMP, AND INSTEAD PROPOSING NEW
 LANDSCAPE ALONG THE EAST FACADE. PLEASE PROVIDE
 LANDSCAPE EXHIBIT
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]
  
  