Plan Review Details - Permit 19020894
Plan Review Stops For Permit 19020894
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-04 Cont ID  
Sent By lcrespo Date 2019-03-04 Time 07:17 Rev Time 0.00
Received By lcrespo Date 2019-02-27 Time 15:53 Sent To  
Notes
2019-03-04 07:19:5503/04/19 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  
2019-02-28 15:54:09RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-21 Cont ID  
Sent By lcrespo Date 2019-02-21 Time 07:25 Rev Time 0.00
Received By lcrespo Date 2019-02-21 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-04 Cont ID  
Sent By lcrespo Date 2019-03-04 Time 07:17 Rev Time 0.00
Received By lcrespo Date 2019-03-04 Time 07:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By lcrespo Date 2019-02-21 Time 07:25 Rev Time 0.00
Received By lcrespo Date 2019-02-21 Time 07:25 Sent To  
Notes
2019-02-21 07:29:2802/21/19 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE
 (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED
 ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
  
 2. TWO COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
  
 3. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  