Plan Review Details - Permit 19020881
Plan Review Stops For Permit 19020881
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-30 Cont ID  
Sent By jpearson Date 2019-04-30 Time 07:18 Rev Time 0.00
Received By jpearson Date 2019-04-30 Time 07:18 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-23 Cont ID  
Sent By fgiaquin Date 2019-04-23 Time 16:44 Rev Time 0.00
Received By fgiaquin Date 2019-04-23 Time 16:27 Sent To I
Notes
2019-04-23 16:42:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLANS, LOAD CALCS, AND VOLTAGE DROP CALCS SUBMITTED
 ARE SIGNED DIGITALLY. PRINTED COPIES OF DIGITALLY
 SIGNED DOCUMENTS ARE NOT CONSIDERED TO BE SIGNED/SEALED
 PER FLORIDA STATUTES. PLEASE SEE BELOW:
  
 COPIES OF SIGNATURES ARE NOT CONSIDERED TO BE SIGNED
 AND SEALED PER FLORIDA STATUTES. PLEASE SEE
 REQUIREMENTS BELOW FOR SIGNATURE AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By fgiaquin Date 2019-03-07 Time 07:35 Rev Time 0.00
Received By fgiaquin Date 2019-03-07 Time 06:36 Sent To I
Notes
2019-03-07 07:23:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 1. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF LIGHT
 POLES, LIGHT FIXTURES, AND CONTACTOR. FBC 107.2.1 NEC
 90.7,110.2,110.3B
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 3. CITY OF WPB WANTS AN ADDITIONAL CIRCUIT PULLED IN
 CONDUIT FOR UNSWITCHED RECEPTACLE LOCATED AT TOP OF
 EVERY NEW LIGHT POLE.
  
 4. PROVIDE PULL BOX LOCATIONS ON PLANS. FBC 107.2.1
  
 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LIGHTING AND RECEPTACLES. NEC 220.
  
 INFORMATIONAL NOTE:
  
 1. L.E.D. LIGHING LOADS ARE TO BE CALCULATED BY AMPS
 NOT WATTS NEC 220.18
  
 2. CONTINUOUS LOADS WILL BE CALCULATED AT 125% NEC
 210.19A1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-01 Cont ID  
Sent By lmarchan Date 2019-05-01 Time 13:10 Rev Time 0.00
Received By lmarchan Date 2019-04-26 Time 15:14 Sent To  
Notes
2019-04-29 15:14:42RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-23 Cont ID  
Sent By fgiaquin Date 2019-04-23 Time 16:44 Rev Time 0.00
Received By fgiaquin Date 2019-04-04 Time 13:50 Sent To  
Notes
2019-04-04 13:51:01RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-07 Cont ID  
Sent By fgiaquin Date 2019-03-07 Time 07:35 Rev Time 0.00
Received By fgiaquin Date 2019-02-20 Time 13:12 Sent To  
Notes
2019-03-05 12:36:30TO LMARCHAN
2019-02-21 13:12:42ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-01 Cont ID  
Sent By aaponte Date 2019-05-01 Time 12:12 Rev Time 0.00
Received By aaponte Date 2019-05-01 Time 12:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-17 Cont ID  
Sent By aaponte Date 2019-04-17 Time 09:50 Rev Time 0.00
Received By aaponte Date 2019-04-17 Time 09:49 Sent To  
Notes
2019-04-17 09:50:51PROVISO: LIGHT POLES ON NORTH SIDE OF OKEECHOBEE BLVD
 SHALL BE LOCATED MAXIMUM 4 FEET FROM THE FACE OF CURB.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By aaponte Date 2019-03-05 Time 12:29 Rev Time 0.00
Received By aaponte Date 2019-03-05 Time 12:29 Sent To E
Notes
2019-03-05 12:35:511. LIGHT POLES ON NORTH SIDE OF OKEECHOBEE BLVD SHALL
 BE LOCATED MAXIMUM 4 FEET FROM THE FACE OF CURB.
 2. PER CONVERSTIONS WITH CITYPLACE, TEH LIGHT FIXTURE
 BEING INSTALLED ALONG ROSEMARY AVENUE IS GRAPHITE
 METALLIC. THE ONE PROPOSED AT THE INTERSECTION BY THE
 CITY IS BRUSHED ALUMINUM. WE NEED TO MATCH THE COLOR OF
 THE TWO FIXTURES AS THEY ARE GOING TO BE THE SAME.
 FOR ADDITINAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved