Plan Review Details - Permit 19020770
Plan Review Stops For Permit 19020770
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-23 Cont ID  
Sent By pvalenti Date 2019-04-23 Time 10:56 Rev Time 0.00
Received By pvalenti Date 2019-04-23 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-15 Cont ID  
Sent By pvalenti Date 2019-04-11 Time 17:41 Rev Time 0.00
Received By pvalenti Date 2019-04-11 Time 07:53 Sent To  
Notes
2019-04-11 17:50:57 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW PASSED BUILDING:
  
 1. OK;
 NOTES: AFTER RESEARCHING PRIOR IMPROVEMENTS TO THIS
 PARTICULAR STRUCTURE. IT APPEARS THAT NO IMPROVEMENTS
 HAVE HAPPENED WITH THIS STRUCTURE (PAVILLION) OTHER
 THAN INITIAL CONSTRUCTION UNDER PERMIT # 99100341. THIS
 IS NOT CONSIDERED A SUBSTANTIAL IMPROVEMENT.(THE
 INDIVIDUAL STRUCTURES WITHIN THE ZOO SHOULD BE
 IDENTIFIED WITH SEPERATE ADDRESSES OR UNIT NUMBERS
 ADDED TO THE ADDRESSES TO DISTINGUISH EACH STRUCTURE
 FOR PERMITTING/FEMA PURPOSES).
 2. OK
 3. OK
 4. OK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-26 Cont ID  
Sent By jwitmer Date 2019-02-26 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2019-02-25 Time 14:11 Sent To  
Notes
2019-02-26 07:37:502017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020770
 ADD: 1301 SUMMIT BLVD.
 CONT: GAST
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 26/ 2019
 ACTION: DENIED
 1) PLEASE BE AWARE THAT THE PAVILION/ ENCLOSURE THAT
 THIS PERMIT IS FOR IS LOCATED IN A AE FLOOD ZONE. THE
 BFE (BASE FLOOD ELEVATION IS 12.2 NAV88). SINCE ALL
 PERMITS PULLED FOR ALL BUILDINGS ARE UNDER THIS ONE
 ADDRESS (1301 SUMMIT) PLEASE PROVIDE DOCUMENTATION THAT
 IS AND ALL OTHERS BEFORE FOR THIS STRUCTURE ARE NOT A
 SUBSTANTIAL IMPROVEMENT.
 SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR
 FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR,
 RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE
 CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT
 OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF
 NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE. THE
 ORIGINAL PERMIT FOR THIS STRUCTURE IS 99100341 AND THE
 VALUE OF $100,000.00 DOLLARS IN VALUE.
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL. FBC BUILDING 1612 AND CITY OF WPB CODE OF
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION
 IF PERMIT APPLICATION AFTER SEPT. 12/2016, AFTER OCT.
 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE BOARD WILL BE
 REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 2) SHEET A-2.0:
  
 2A) SECTION 1 INDICATES A 2X6 LEDGER BUT THE PLAN DOES
 NOT INDICATE THE SIZE OF THE FRAMING MEMBERS. SHEET
 A-1-0 DOES PROVIDE THE SPACING OF THE FRAMING MEMBERS
 BUT NOT THE SIZE. SEE 2017 FBC-B TABLE 2308.7.
  
 2B)(1) PLEASE NOTE IN SECTION 1 OF THIS PLAN A LOUVER
 TO THE EXTERIOR IS SHOWN, PLEASE PROVIDE A PRODUCT
 APPROVAL FOR THIS LOUVER IN COMPLIANCE WITH: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31(C) WALL LOUVERS,
  
 2B)(2) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3)SHEET A-2-0, THE DETAILS 1, 3, 4 & 8 ALL SHOW WALL
 ELEVATIONS OF THE RESTROOMS WITH THE WATER CLOSET BUT
 THEY DO NOT PROVIDE THE DISTANCE FROM THE CORNER NOR
 THE LENGTH OF THE GRAB BARS OR COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTIONS:
 604.5 GRAB BARS.
 605.1 SIDE WALLS.
 605.2 REAR WALLS.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-05 Cont ID  
Sent By jpearson Date 2019-04-05 Time 09:11 Rev Time 0.00
Received By jpearson Date 2019-04-05 Time 09:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By jpearson Date 2019-02-27 Time 15:47 Rev Time 0.00
Received By jpearson Date 2019-02-27 Time 15:47 Sent To  
Notes
2019-02-27 15:47:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE (EXISTING MCB),
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-01 Cont ID  
Sent By pleduc Date 2019-04-01 Time   Rev Time 0.00
Received By pleduc Date 2019-04-01 Time 10:21 Sent To  
Notes
2019-04-01 10:26:244/1/19
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET E 1 0 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES/EQUIPMENT WITHIN THE PAVILION.
  
 IF THERE IS AN EXITING FIRE SYSTEM WITHIN THE PAVILION,
 THE NEW RESTROOMS SHALL HAVE SYSTEM DEVICES EXTENDED
 INTO THEM.
  
 ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMITTED SHOP DRAWINGS BY CERTIFIED FIRE
 ALARM CONSTRACTORS.
  
 IF THERE IS NO FIRE ALARM SYSTEM IN THE PALVILION,
 PLEASE DISREGARD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-21 Cont ID  
Sent By pleduc Date 2019-02-21 Time   Rev Time 0.00
Received By pleduc Date 2019-02-21 Time 13:42 Sent To  
Notes
2019-02-21 14:07:41THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET E 1 0 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES/EQUIPMENT WITHIN THE PAVILION.
  
 IF THERE IS AN EXITING FIRE SYSTEM WITHIN THE PAVILION,
 THE NEW RESTROOMS SHALL HAVE SYSTEM DEVICES EXTENDED
 INTO THEM.
  
 ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMITTED SHOP DRAWINGS BY CERTIFIED FIRE
 ALARM CONSTRACTORS.
  
 IF THERE IS NO FIRE ALARM SYSTEM IN THE PALVILION,
 PLEASE DISREGARD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-23 Cont ID  
Sent By pvalenti Date 2019-04-23 Time 11:05 Rev Time 0.00
Received By pvalenti Date 2019-04-18 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-18 Cont ID  
Sent By lmarchan Date 2019-04-18 Time 14:43 Rev Time 0.00
Received By lmarchan Date 2019-03-29 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-09 Cont ID  
Sent By gjohnson Date 2019-03-09 Time 07:36 Rev Time 0.00
Received By gjohnson Date 2019-02-19 Time 15:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-02-26 Cont ID  
Sent By jwitmer Date 2019-02-26 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2019-02-25 Time 14:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-22 Cont ID  
Sent By ccole Date 2019-04-22 Time 09:57 Rev Time 0.00
Received By ccole Date 2019-04-22 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-04-11 Cont ID  
Sent By ccole Date 2019-04-11 Time 09:19 Rev Time 0.00
Received By ccole Date 2019-04-11 Time 09:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-02-25 Cont ID  
Sent By ccole Date 2019-02-25 Time 16:20 Rev Time 0.00
Received By ccole Date 2019-02-25 Time 16:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 14:08 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-03 Cont ID  
Sent By thunt Date 2019-04-03 Time 15:16 Rev Time 0.00
Received By thunt Date 2019-04-03 Time 13:27 Sent To  
Notes
2019-04-03 15:15:56PLUMBING 2ND REVIEW**DENIED**
  
 EXISTING COMMECTS
  
 1) NOT ADDRESSED. PROVIDE FLOOR PLAN DETIAL OF
 BATHROOMS SHOW REAR GRAB BAR 12" FROM THE CENTERLINE OF
 TOILET 36" IN OVERALL LENGHT. FBC-A 604.5.2
  
 2) ADDRESSED
  
 3) ADDRESS
  
 4) NOT ADDRESSED. TANKLESS WATER HEATERS WITH FACTORY
 PRE SET TEMP ARE NOT PREMITTED. FBC-P 607.1.1. UNIT
 EITHER SHALL HAVE A ASSE 1070 VALVE BUILT IN OR A 1070
 DEVICE ADDED TO COMPLY WITH FBC-P 607.1.2. THE MODEL
 SPEC ON PLANS DOES NOT MEET THE INTENT OF THE PLUMBING
 CODE.
  
 NEW COMMENT
  
 5) SIDE GRAB BAR IS SHOWING 11" OFF REAR WALL 42" IN
 LENGTH GIVING AN OVERALL OF 53". THE MIN DISTANCE FROM
 THE BACKWALL ALLOWED IS 54". SEE FBC-A 604.5.1 FOR
 DETAIL. YOUR BAR MUST BE MOUNTED @ 12" OFF BACKWALL TO
 COMPLY. SEE PLAN DETAIL SHT. A2.0
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-09 Cont ID  
Sent By gjohnson Date 2019-03-09 Time 06:19 Rev Time 0.00
Received By gjohnson Date 2019-03-09 Time 06:19 Sent To  
Notes
2019-03-09 07:35:501ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. THE BAR SHOWN ON THE PLAN
 DOES NOT GIVE YOU THE 24" OFF CENTERLINE OF TOILET. PER
 FBC ACC 604.5.2
  
 2. THE OUTLET OF THE TOILET PAPER DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. THE DETAIL ON THE PLAN DOES NOT SHOW THE OUTLET
 DIMENSION. PER FBC ACC 604.7
  
 3. A WATER FOUNTAIN IS REQUIRED WITHIN 500' OF LOCATION
 SHOW ON THE PLAN OR PROVIDE ONE. PER FBC PL 403.5
  
 4.TEMPERED WATER SHALL BE DELIVERED BY A TEMPERATURE
 LIMITING DEVISE COMPILING WITH ASSE 1070. PER FBC ACC
 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-04-23 Cont ID  
Sent By ccole Date 2019-04-23 Time 11:05 Rev Time 0.00
Received By pvalenti Date 2019-04-23 Time 11:05 Sent To  
Notes
2019-04-11 10:31:13MECH PLAN OK- CCOLE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By shill Date 2019-03-11 Time 06:54 Rev Time 0.00
Received By shill Date 2019-03-11 Time 06:53 Sent To  
Notes
2019-03-11 06:54:17NEW PAGES SUBMITTED NEXT REVIEW CYCLE, IF APPLICABLE,
 NEED SIGNATURE REVIEW
2019-02-26 07:42:38ALL PLANS REVIEWED FOR ELECTRONIC SIGNATURES FOR 1ST
 REVIEW. OK/ JW

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-18 Cont ID  
Sent By jroach Date 2019-04-18 Time 14:35 Rev Time 0.00
Received By jroach Date 2019-04-18 Time 14:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jroach Date 2019-02-21 Time 16:41 Rev Time 0.00
Received By jroach Date 2019-02-21 Time 16:41 Sent To  
Notes
2019-02-21 16:49:54ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.21.2019
 PERMIT NO.: 19020770
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE LEASE AGREEMENT BETWEEN THE PALM
 BEACH ZOO AND THE CITY OF WEST PALM BEACH, INDIVIDUAL
 STRUCTURES OR IMPROVEMENTS IN EXCESS OF $5000 ARE TO BE
 SUBMITTED TO THE CITY COMMISSION FOR PRIOR APPROVAL AS
 SUCH IMPROVEMENTS WOULD OCCUR ON CITY-OWNED PROPERTY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  