Plan Review Details - Permit 19020741
Plan Review Stops For Permit 19020741
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By jwitmer Date 2019-03-11 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2019-03-05 Time 06:33 Sent To  
Notes
2019-03-11 10:17:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020741
 ADD: 430 HAMPTON RD
 CONT: TBD/ TO BE DETERMINED
 TEL: 315-374-7292
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 11/ 2019
 ACTION: DENIED
  
 1) SHEET T-1.0:
  
 1A) ARCHITECT BHARAT R. PATEL SIGNATURE IS A COPIED
 SIGNATURE, (SIGNATURE IS PIXILATED). FLORIDA
 ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A SCANNED,
 FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE OF THE
 LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1B) THE COVERSHEET LIST THE APPLICABLE CODES WITH THE
 EXCEPTION OF THE 2017 FLORIDA BUILDING CODE-EXISTING
 BUILDING. ALL OF THE FLORIDA BUILDING CODES WERE
 ADOPTED STATEWIDE ON DEC. 31/ 2017.
  
 1C) THE COVERSHEET ALSO IS MISSING THE METHOD FROM
 WHICH THE PLANS WERE DEVELOPED. SEE THE 2017 FLORIDA
 BUILDING CODE, EXISTING BUILDING SECTION:
 301.1. THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2 WORK AREA COMPLIANCE METHOD.
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 1D) THE COVERSHEET LIST THIS BUILDING HAVING A SQUARE
 FOOTAGE OF 1548 SQ. FT. AND AN OCCUPANT LOAD OF 15
 OCCUPANTS.
 THE 2017 FBC-B TABLE 1004.1.2 LIST A BUSINESS OCCUPANCY
 AS 100 SQ. FT. GROSS. 1548/100 = 15.48 OCCUPANTS,
 OCCUPANTS ARE ALWAYS ROUNDED UP TO THE NEXT WHOLE
 NUMBER, NO PARTIAL OCCUPANTS. SEE BOAF INTERPRETATIONS.
 (BOAF- BUILDING OFFICIALS ASSOCIATION OF FLORIDA).
  
 1E) THE COVERSHEET LIST THE WIND DESIGN CRITERIA AS
 WELL AS SHEET S3 BUT THE ASSOCIATED PRESSURES FOR THIS
 WIND DESIGN ARE NOT GIVEN IN VULT OR VASD. WE WOULD
 PREFER TO SEE THE PRESSURES LISTED IN VASD SINCE ALL OF
 THE PRODUCT APPROVALS ARE ALSO IN VASD. 2017 FBC-B
 1603.1.4 WIND DESIGN DATA.(5.) DESIGN WIND PRESSURES TO
 BE USED FOR EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE
 STRUCTURE, PSF.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 1F) THE COVERSHEET LIST DESIGN LOADS, GIVEN ARE THE
 ROOF LOADS OF 25PSF DL + 30PSF LL BUT THERE ARE NO
 FLOOR LOADS GIVEN. SHEET S3 THE FLOOR LOADS ARE GIVEN
 AT 40 PSF LL + 25 PSF DL. SHEET S3 DOES NOT PROVIDE THE
 DEFLECTION LIMITATIONS FOR THE SUPPORTING FLOOR
 MEMBERS. SHEET S1 INDICATES THE FLOOR FRAMING MEMBERS
 AT 2-0 FEET ON CENTER BUT NOT THE DEPTH OF THE FRAMING
 MEMBERS. THE CONCERNS ARE UNDER THE 2017 FBC-EXISTING
 BUILDING CODE 1007.1:
 BUILDINGS OR PORTIONS THEREOF SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER UNIFORM OR CONCENTRATED LOADS BASED
 ON THE FLORIDA BUILDING CODE, BUILDING, TABLE 1607.1
 SHALL COMPLY WITH THE GRAVITY LOAD PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 EXCEPTION: STRUCTURAL ELEMENTS WHOSE STRESS IS NOT
 INCREASED BY MORE THAN 5 PERCENT.
  
 UNDER THE TABLE 1607.1 THE LIVE LOADS FOR RESIDENTIAL
 BEDROOMS COULD HAVE BEEN DESIGNED TO 30 LBS. PER SQ.
 FT., THE OTHER HABITAL AREAS TO 40 LBS. PER SQ. FT.
 WITH THE CHANGE OF OCCUPANCY TO THE BUSINESS OCCUPANCY
 THE LIVE LOAD FLOOR LOADS ARE NOW 50 LBS. PER SQ. FT.
 WITH THE ADDITIONAL LIVE LOAD TO 50 LBS. IT EXCEEDS THE
 ALLOWABLE 0.05 PER CENT.
  
 IF YOU LOOK AT TABLE 2308.4.2.1(2) WITH THE JOIST
 SPACED AT 2.0 FT. C/C FOR SS SOUTHERN PINE FOR
 RESIDENTIAL LIVING AREAS 40 PSF DEFLECTION 360 YOU GET
 A SPAN OF 8 FT. 11 INCHES FOR 2X6. TAKEN AT 30 PSF
 (BEDROOMS) THE SPAN IS ONLY 9 FEET 9 INCHES. THE SPANS
 VERY FROM 13 FEET TO 13.5 FEET FOR 2X6. PLEASE VERIFY
 THE FLOOR JOIST SIZE AND SPACING. FOR STICK BUILT HOMES
 THEY MAY HAVE USED THE 2 FEET C/C OR 16 INCHES ON
 CENTER, IT IS CRUCIAL TO KNOW THE FLOOR SPACING AND
 SIZE OF THE FLOOR FRAMING MEMBERS.
  
 THE OTHER ISSUE WITH APPLYING FLOOR TILE TO A WOOD
 FLOOR JOIST SYSTEM, IF THERE IS TOO MUCH DEFLECTION IN
 THE FLOOR SYSTEMS THE AREAS WHERE THE DEFLECTION IS
 STRESSED FOR WOOD FLOORS IT WOULD NOT BE NOTICED BUT
 WHERE TILE IS INSTALLED, THE MORTAR JOINTS WILL CRACK
 BECAUSE OF THE FLOOR MOVEMENT!!!!
  
 2) SHEET A-0.3 THE LIFE SAFETY PLAN INDICATES THERE ARE
 TOO BE 2 EXITS FROM THE BUILDING, PLEASE SHOW
 COMPLIANCE WITH: EXISTING BUILDING CODE 1001.2.2 CHANGE
 OF OCCUPANCY CLASSIFICATION OR GROUP. WHERE THE
 OCCUPANCY CLASSIFICATION OF A BUILDING CHANGES, THE
 PROVISIONS OF SECTIONS 1002 THROUGH 1012 SHALL APPLY.
 THIS INCLUDES A CHANGE OF OCCUPANCY CLASSIFICATION AND
 A CHANGE TO ANOTHER GROUP WITHIN AN OCCUPANCY
 CLASSIFICATION.
 1001.2.2 CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT UNDERGO A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY.
  
 2017 ACCESS. CODE 206.2.2 WITHIN A SITE. AT LEAST ONE
 ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE. SHOW ON
 THE SITE PLAN THE ACCESSIBLE ENTRANCE, WALKWAYS AND
 ACCESSIBLE PARKING SPACE.
  
 3) ACCESSIBLE PARKING: NO SITE PLAN WAS SUBMITTED SHOW
 THE ACCESSIBLE PARKING NOR THE DIMENSIONS. PLEASE
 REVIEW ACCESS. CODE SECTION:
 502.3.3 MARKING.
  
 ACCESS AISLES SHALL BE MARKED SO AS TO DISCOURAGE
 PARKING IN THEM.
  
 THE ACCESS AISLE MUST BE STRIPED DIAGONALLY TO
 DESIGNATE IT AS A NO-PARKING ZONE.
  
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED.
 FLORIDA LAW, S. 553.5041(5)(C)1., REQUIRES DIAGONAL
 STRIPING OF ACCESS AISLES.
  
 PLEASE SEE WEST PALM MUNI CODE ARTICLE XV PARKING STALL
 PAINTING DETAIL.
  
 3) UNDER THE CHANGE OF OCCUPANCY IN THE EXISTING
 BUILDING CODE SECTION 1012.8 REQUIRES YOU TO GO THE
 2017 ACCESS. CODE SECTION:
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 THIS SECTION WILL REQUIRE THE CONTRACTOR TO USE UP TO
 20% OF THE CONTRACT VALUE FOR ACCESSIBLE UPGRADES. IF
 THE BUILDING AND SITE CANNOT BE MADE 100% ACCESSIBLE,
 THEN WE NEED A LETTER ON EITHER THE DESIGN PROFESSIONAL
 OR CONTRACTORS LETTER HEAD ITEMIZING WHERE THE FUNDS
 WERE TO BE SPENT AND IN THE ORDER LISTED ABOVE UNDER
 SECTION 202.4.2 UNTIL THEY MEET DISPROPORTIONALITY.
  
 4) BOTH SHEETS A-0.1 AND A-4.0 BOTH SHOW THE RESTROOM
 GRAB BAR BEING MEASURED FROM THE CENTERLINE OF THE GRAB
 BAR TO THE FINISH FLOOR. PLEASE BE AWARE OF A CHANGE IN
 THE 2010 ACCESSIBILITY CODE AND CURRENT VERSION OF THE
 2017 FBC-ACCESS. CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 5) THE SUBMITTED PRODUCT APPROVAL NOA 16-0218.03 PGT
 MULLION TUBE WAS INITIALED Y THE DESIGN PROFESSIONAL
 BUT NONE OF THE MULLION SECTIONS WERE IDENTIFIED WITHIN
 THE REPORT.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: HT
 TP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTF
 EES/FORMS/QUESTIONNAIRE.PDF
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-15 Cont ID  
Sent By jpearson Date 2019-03-15 Time 15:47 Rev Time 0.00
Received By jpearson Date 2019-03-15 Time 15:47 Sent To  
Notes
2019-03-15 15:47:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A COPY OF THE SIGNATURE IS NOT ACCEPTABLE.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 4. GENERAL ELECTRICAL NOTE # 10 STATES THAT ALL WIRING
 WILL BE IN CONDUITS. PROVIDE EXPLANATION OF EXISTING NM
 WIRING TO BE REMOVED. WPB FBC 107.2.1
 5. PROVIDE CORRECTED RISER DIAGRAM. THE FEED TO THE
 INTERIOR PANEL IS SHOWN FROM METER CAN, BUT THERE IS
 ALSO A MAIN DISCONNECT SHOWN. WILL THE FEED TO THE
 INTERIOR PANEL BE DIRECTLY FROM METER CAN, OR FROM
 DISCONNECT. PROVIDE CLARIFICATION. THERE IS AN
 EQUIPMENT GROUNDING CONDUCTOR SIZED # 8 SHOWN TO
 INTERIOR PANEL. THIS IS NOT THE PROPER SIZE FOR A 200
 AMP FEEDER. PROVIDE CORRECTION. NEC 215.5, 250.122; WPB
 FBC 107.2.1
 6. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-16 Cont ID  
Sent By jpearson Date 2019-03-16 Time 07:14 Rev Time 0.00
Received By jpearson Date 2019-03-15 Time 10:56 Sent To  
Notes
2019-03-16 07:14:48SEE REVISION STOP 2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-27 Cont ID  
Sent By pleduc Date 2019-02-27 Time   Rev Time 0.00
Received By pleduc Date 2019-02-27 Time 10:47 Sent To  
Notes
2019-02-27 11:03:58THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET A 0.3 - TWO EXITS ARE INDICATED; HOWEVER, A
 SITE PLAN IS NOT PROVIDED SHOWING THAT THESE EXITS LEAD
 TO A PUBLIC WAY.
  
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN
 7.7.1.2 THROUGH 7.7.1.4.
  
 PLEASE NSURE THAT THESE EXITS HAVE A CLEAR UNOBSTRUCTED
 PATH TO A PUBLIC WAY PER NFPA 101 CH 7 MEANS OF EGRESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-06 Cont ID  
Sent By hmoser Date 2019-04-02 Time 07:22 Rev Time 0.00
Received By shill Date 2019-02-20 Time 12:34 Sent To  
Notes
2019-02-21 12:34:58B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By jwitmer Date 2019-03-11 Time 10:16 Rev Time 0.00
Received By jwitmer Date 2019-03-05 Time 06:33 Sent To  
Notes
2019-03-11 10:16:12IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW BY
 THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: HT
 TP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTF
 EES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By hmoser Date 2019-03-19 Time 10:34 Rev Time 0.00
Received By hmoser Date 2019-03-19 Time 10:23 Sent To I
Notes
2019-03-19 10:34:37PLAN DENIED
 1) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S
 2017 FBC (M) PAGE A-5.0 SHAW'S WOOD DOOR ON
 AIR HANDLER CLOSET.
 2) REFER TO SECTION 601.6 BALANCED RETURN AIR
 2017 FBC (M)
 3) PROVIDE OUTDOOR AIR TO MEET TABLE 403.3.1.1
 MINIMUM VENTILATION RATES 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By thunt Date 2019-03-13 Time 14:53 Rev Time 0.00
Received By thunt Date 2019-03-13 Time 12:43 Sent To  
Notes
2019-03-13 14:55:06PLUMBING 1ST REVIEW**DENIED**03/13/2019
  
 1) SEE BUILDING PLAN REVIEWERS COMMENTS 1A, 1B, 1C. IF
 THE OCCUPANT LOAD IS 16 THEN 2 RESTROOMS WILL BE
 REQUIRED TO COMPLY WITH FBC-P403. A MOP SINK AND HI-LOW
 DRINKING FOUNTAIN WOULD ALSO BE REQUIRED UNDER FBC-P
 410.3 AND FBC-A 211.2
  
 2) BREAK ROOM SINK MUST BE ACCESSIBLE. SHOW CLEAR FLOOR
 SPACE 30" BY 48" FOR FRONT APPROACH AND COUNTER TOP MAX
 HEIGHT WOULD BE 34". FBC-A 305, 306. SHT. A-4.0 CALLS
 OUT 36" MIN.
  
 3) PROVIDE CLEAR FLOOR SPACE FOR THE TOILET AND
 LAVATORY ON THE PLAN. FBC-A 305, 306. FBC 107.3.5
  
 4) SHT A-4.0 #1 TOP LEFT CALLS OUT TOILET 1" 1 1/2" (13
 1/2") FROM SIDE WALL. THE TOILET SHALL BE 16" TO 18"
 FBC-A 604.2
  
 5) LAVATORY CALLED OUT ON SHT.P-1 IS 21 1/4" BY 22" AND
 MAY ENCROACH INTO THE TOILETS CLEAR FLOOR SPACE AND NOT
 ALLOW THE MIN 15" FROM THE SIDE WALL WITH THE ROOM
 OVERALL ROUGH @ 7' 2". MIN SINK SIZE ALLOWED IS 19" BY
 21. FBC-A604.8.1.6 AND FBC-P 405.3.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561-248-2703
  
 SAMANTHA HILL
 CHIEF PLANS EXAMINER
 561-805-6724
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By pgreilic Date 2019-04-02 Time 11:25 Rev Time 0.00
Received By pgreilic Date 2019-04-02 Time 11:25 Sent To  
Notes
2019-04-02 11:26:461.) PROVIDE SURVEY OR SITE PLAN WITH A NOTE INDICATING
 BUILDING FOOTPRINT WILL NOT BE ALTERED BY PROPOSED
 INTERIOR MODIFICATIONS
 2.) LANDSCAPE PERMIT AND TREE ALTERATION PERMIT
 REQUIRED FOR ANY PROPOSED CHANGES TO LANDSCAPE ON SITE.
 MAKE SURE LANDSCAPE PLANS ARE REMOVED FROM PLAN SET AND
 SUBMITTED AS A SEPARATE PERMIT.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]