Plan Review Details - Permit 19020678
Plan Review Stops For Permit 19020678
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-07 Cont ID  
Sent By jwitmer Date 2019-08-07 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2019-08-07 Time 13:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-13 Cont ID  
Sent By dbattles Date 2019-06-13 Time 15:17 Rev Time 0.00
Received By dbattles Date 2019-06-13 Time 10:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By jwitmer Date 2019-04-02 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2019-04-01 Time 13:12 Sent To  
Notes
2019-04-02 07:56:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020678
 ADD: 444 W. RAILROAD AVE. SUITE: 100
 CONT: K & M COMMERCIAL CONSTRUCTION LLC
 TEL: 561-383-2817 / CONTACT: KAREN HIBBERT
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 02/2018
 ACTION: DENIED
  
 1) SHEET 018_A-100 THE LIFE SAFETY SHEET BUILDING CODE
 ANALYSIS:
  
 1A) THE PLANS INDICATE THIS TENANT SPACE IS A LEVEL II
 ALTERATION. IN GOING THROUGH FILE NET (PERMITTING
 ARCHIVES) THIS SPACE HAS NEVER BEEN OCCUPIED, IT HAS
 BEEN A SHELL SPACE. PLEASE NOTE OCCUPATIONAL LICENSING
 HAS ISSUED EVENTS FOR THIS SPACE, BUT THERE HAS NEVER
 BEEN A PERMIT CHANGING IT FROM A SHELL SPACE TO AN
 OCCUPANCY TYPE. I HAVE WENT BACK THROUGH THE INTERIOR
 BUILD OUT PERMITS AND NOT FOUND A PERMIT FOR THIS SPACE
 ON THE 1ST FLOOR. THIS SPACE IS EITHER NEW CONSTRUCTION
 SINCE NO PERMIT WAS FOUND. PLEASE UPDATE PLANS.
 2017 EXISTING BUILDING CODE SECTION 101.2 SCOPE. THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, EXISTING
 BUILDING SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE
 OF OCCUPANCY, ADDITION TO AND RELOCATION OF EXISTING
 BUILDINGS.
 2017 EXISTING BUILDING CODE. 101.4.1 BUILDINGS NOT
 PREVIOUSLY OCCUPIED. A BUILDING OR PORTION OF A
 BUILDING THAT HAS NOT BEEN PREVIOUSLY OCCUPIED OR USED
 FOR ITS INTENDED PURPOSE IN ACCORDANCE WITH THE LAWS IN
 EXISTENCE AT THE TIME OF ITS COMPLETION SHALL BE
 PERMITTED TO COMPLY WITH THE PROVISIONS OF THE LAWS IN
 EXISTENCE AT THE TIME OF ITS ORIGINAL PERMIT UNLESS
 SUCH PERMIT HAS EXPIRED. SUBSEQUENT PERMITS SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING OR
 FLORIDA BUILDING CODE, RESIDENTIAL, AS APPLICABLE, FOR
 NEW CONSTRUCTION.
  
 1B) UNDER THE BUILDING CODE ANALYSIS # 9 THE PLAN
 STATES THE NUMBER OF EXITS REQUIRED AS 1. PLEASE NOTE
 THE PLAN DOES NOT INDICATE THE OCCUPANT LOAD. THE
 OCCUPANT LOAD IS SHOWN AS 87 PLEASE UPDATE TO 88
 420/300= 1.4 YOU ALWAYS ROUND UP OCCUPANTS TO 2
 OCCUPANTS, TOTAL 88 OCCUPANTS, REQUIRES 2 MEANS OF
 EGRESS. SEE THE 2017 FBC-BUILDING CODE TABLE 1006.2.1
 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAYS. FOR AN A3
 OCCUPANCY THE MAXIMUM OCCUPANT LOAD WITH ONE EXIT OR
 EXIT ACCESS DOORWAY IS 49 OCCUPANTS AND COMMON PATH OF
 TRAVEL OF 75 FEET.
  
 1C) UNDER THE BUILDING CODE ANALYSIS # 11 INTERIOR
 FINISH REQUIREMENTS, TABLE 803.11 THE OCCUPANCY TYPE AS
 MERCANTILE. THE RATINGS ARE CORRECT WRONG OCCUPANCY
 TYPE. MAYBE A TYPO, PLEASE CORRECT. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1D) PLEASE IDENTIFY WHICH PIECES OF EQUIPMENT ARE GOING
 TO BE HANDICAPPED ACCESSIBLE AND IN COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE 1004.1 CLEAR FLOOR SPACE.
  
 EXERCISE MACHINES AND EQUIPMENT SHALL HAVE A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR TRANSFER
 OR FOR USE BY AN INDIVIDUAL SEATED IN A WHEELCHAIR.
 CLEAR FLOOR OR GROUND SPACES REQUIRED AT EXERCISE
 MACHINES AND EQUIPMENT SHALL BE PERMITTED TO OVERLAP.
  
 ADVISORY 1004.1 CLEAR FLOOR SPACE. ONE CLEAR FLOOR OR
 GROUND SPACE IS PERMITTED TO BE SHARED BETWEEN TWO
 PIECES OF EXERCISE EQUIPMENT. TO OPTIMIZE SPACE USE,
 DESIGNERS SHOULD CAREFULLY CONSIDER LAYOUT OPTIONS SUCH
 AS CONNECTING ENDS OF THE ROW AND CENTER AISLE SPACES.
 THE POSITION OF THE CLEAR FLOOR SPACE MAY VARY GREATLY
 DEPENDING ON THE USE OF THE EQUIPMENT OR MACHINE. FOR
 EXAMPLE, TO PROVIDE ACCESS TO A SHOULDER PRESS MACHINE,
 CLEAR FLOOR SPACE NEXT TO THE SEAT WOULD BE APPROPRIATE
 TO ALLOW FOR TRANSFER. CLEAR FLOOR SPACE FOR A BENCH
 PRESS MACHINE DESIGNED FOR USE BY AN INDIVIDUAL SEATED
 IN A WHEELCHAIR, HOWEVER, WILL MOST LIKELY BE CENTERED
 ON THE OPERATING MECHANISMS.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER19030471
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-03 Cont ID  
Sent By jpearson Date 2019-06-03 Time 15:52 Rev Time 0.00
Received By jpearson Date 2019-06-03 Time 15:52 Sent To  
Notes
2019-06-03 15:52:31PASSED WITH PROVISO ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-27 Cont ID  
Sent By jleahy Date 2019-03-27 Time 13:41 Rev Time 0.00
Received By jleahy Date 2019-03-26 Time 16:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-16 Cont ID  
Sent By pleduc Date 2019-07-16 Time   Rev Time 0.00
Received By pleduc Date 2019-07-16 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By pleduc Date 2019-05-17 Time   Rev Time 0.00
Received By pleduc Date 2019-05-17 Time 16:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-26 Cont ID  
Sent By scaldero Date 2019-02-26 Time 14:45 Rev Time 0.00
Received By scaldero Date 2019-02-25 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-14 Cont ID  
Sent By shill Date 2019-08-14 Time 18:10 Rev Time 0.00
Received By shill Date 2019-07-15 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-13 Cont ID  
Sent By dbattles Date 2019-06-13 Time 15:17 Rev Time 0.00
Received By dbattles Date 2019-05-14 Time 14:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-22 Time 09:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-04-02 Cont ID  
Sent By jwitmer Date 2019-04-02 Time 08:01 Rev Time 0.00
Received By jwitmer Date 2019-04-01 Time 13:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By ccole Date 2019-06-11 Time 08:07 Rev Time 0.00
Received By ccole Date 2019-06-07 Time 12:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By ccole Date 2019-04-09 Time 11:40 Rev Time 0.00
Received By ccole Date 2019-04-09 Time 11:40 Sent To  
Notes
2019-04-09 11:52:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020678
 4/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMP IN ACCORDANCE WITH SECTION C403.2.1 FBC
 EC.
  
 2) SHEET M201: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR THE LOCKER AND TOILET ROOMS- TABLE 403.3.1.1 FBC M.
  
 3) M101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SYSTEM OF THE NEW AHU-1- SECTION 606.2.1 FBC M.
  
 4) M101: SHOW THE WATER SERVICE POINTS OF CONNECTIONS
 TO AHU-1
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-1-
 SECTION 307.2.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By shill Date 2019-08-14 Time 18:09 Rev Time 0.00
Received By shill Date 2019-08-09 Time 12:27 Sent To  
Notes
2019-08-14 18:10:20REVIEWED REMOTELY BY TIM HUNT
  
 APPROVED BUT REDLINE COMMENTS ON SHT. P-101
  
 1) CONDENSATE SHALL NOT DISCHARGE INTO THE STORM OR
 SANITARY SEWER. IT SHALL DISCHARGE OUTSIDE ONTO THE
 GROUND WITHOUT CAUSING A NUISANCE.
 2) ALL BATHROOM FIXTURES SHALL BE INDIVIDUALLY VENTED
 AS PER THESE PLANS. THE MOP SINK IS NOT PERMITTED TO
 DISCHARGE INTO THE BATHROOM WET VENT OTHERWISE. FBC-PLB
 912.2.1, CITY OF WPB ORD.
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-30 Cont ID  
Sent By thunt Date 2019-06-11 Time 14:11 Rev Time 0.00
Received By thunt Date 2019-05-22 Time 18:55 Sent To  
Notes
2019-05-30 14:12:33PLUMBING 2ND REVIEW**DENIED**
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
  
  
 1)**OK
  
  
  
 2)** THE PLUMBING ISOMETRIC NOW BEING COMPLETED SHOW
 THE MOP SINK DISCHARGING INTO THE BATHROOM GROUP WET
 VENT. MOP SINK SHALL DISCHARGE DOWNSTREAM OF THE
 BATHROOM GROUPS. FBC-PLB 912.1, 912.1.1
  
  
  
 3)**OK
  
  
  
 4) THE WATER ISOMETRIC IS NOW MISSING ALMOST ALL THE
 SHUT OFF VALVES REQUIRED ON THE DOWN FEEDS FROM THE
 CEILING. FBC-PLB 606.1 (5)
  
  
  
 5) THE PAN DRAIN ITSELF IS MISSING FROM THE WATER
 HEATER DETAIL. IT SHALL DISCHARGE TO THE HUB DRAIN.
 FBC-PLB 504.7.2
  
  
  
 6)**OK
  
  
  
 7)**OK
  
  
  
 8) I FEEL YOU HAVE CLEARLY FOLLOWED THE WORDING THAT
 THE ACCESSIBLE SHOWERS MEASUREMENT SHALL COME FROM THE
 CENTER AND BE A MIN 60" BUT I DO NOT FEEL THAT THE
 INTENT OF THE CODE WAS TO ONLY REQUIRE THE MIN 60" AT
 THE CENTER AND THE OPENING. WOULD IT BE POSSIBLE TO
 MAKE THE CENTER SHOWER IN EACH LOCKER ROOM THE
 ACCESSIBLE UNIT? THE MIDDLE SHOWER WOULD FOR SURE
 COMPLY WITH NO ISSUES. FBC 107.2.1
  
  
  
 9) 2ND REQUEST:PLEASE PROVIDE ALL REQUIRED CLEAR FLOOR
 SPACE AND TURNING SPACE ON 1 OF THE ARCHITECTURAL
 DRAWINGS. THIS SHOULD INCLUDE BOTH TOILET COMPARTMENTS,
 SHOWER, DRINKING FOUNTAIN, AND THE COMMON HAND WASH
 SINKS. FBC 107.3.5
  
  
  
 10) PLEASE NOTE ON PLAN ALL HAND WASH SINK SHALL BE
 TEMPERED TO MAX 110-F BY A ASSE 1070 DEVICE. FBC-PLB
 607.1.2
  
 11) NEW COMENT: SHEET P-101 SHOWS AHU CONDENSATE INTO
 HD-1. PLEASE ADD THIS TO YOUR COMMENT LIST. SEC. 90-126
 WPB CODE OF ORDINANCES PROHIBITS CONDENSATE FROM
 COOLING COILS TO DISCHARGE INTO THE CITY SANITARY.
  
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
  
  
  
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-03 Cont ID  
Sent By thunt Date 2019-04-03 Time 08:21 Rev Time 0.00
Received By thunt Date 2019-04-03 Time 07:13 Sent To  
Notes
2019-04-03 08:21:52PLUMBING 1ST REVIEW**DENIED**
  
 1) SEE BUILDING REVIEWERS COMMENTS REGARDING OCCUPANCY
 AND OCCUPANCY LOAD. FBC 107.3.5
  
 2) BOTH PLUMBING SANITARY FLAT DRAWING ON SHT. P-101
 AND SANITARY ISOMETRIC ON SHT. P-301 SHOW'S WOMENS ADA
 SHOWER AS DRY VENTED AND ARE NOT COMPLETED DRAWINGS FOR
 THE MENS RESTROOM. FBC-P 912.2, FBC 107.3.5
  
 3) PROVIDE OVERALL DEVELOPED LENGHT OF THE HOT WATER
 LINE FROM THE WATER HEATER TO THE FIXTURES. IF OVER 50'
 DEVELOPED LENGTH A RECIRCULATION SYSTEM SHALL BE USED
 AND PIPING INSULATED TO MIN 1" WALL. FBC-P 607.2, 607.5
  
 4) SHT. P-301 WATER ISOMETRIC IS MISSING THE VALVES ON
 THE WOMENS ADA SHOWER, MENS URINAL, AND 2ND LAV SINK.
 FBC-P 606.1
  
 5) PROVIDE A DRAIN PAN AND DRAIN LINE FOR THE WATER
 HEATER ON SHT. P401. FBC -P504.7
  
 6) SHT.A-106 CALLS OUT FOR THE GRAB BARS IN DETAIL (B)
 & (J) TO BE 33"-36" TO THE CENTER LINE OF THE GRAB BAR.
 THE MEASUREMENT SHALL BE TO THE TOP OF THE GRIPPING
 SURFACE AS CALL OUT IN FBC-A 609.4
  
 7) PROVIDE SHOWER VALVE AND HAND HELD INSTALLATION
 HEIGHT DETAIL ON SHT. A-106. FBC 107.3.5
  
 8) PROVIDE PLAN SHOWING THE REQUIRED CLEAR FLOOR SPACES
 AS REQUIRED IN THE FLORIDA ACCESSIBILITY CODE. IT
 DOESNT APPEAR THAT THE ADA MENS AND WOMENS SHOWER WILL
 HAVE THE REQUIRED CLEAR FLOOR SPACE AND THE ABILITY TO
 TRANSFER TO THE SHOWER SEATS. PLEASE CLARIFY. FBC-A
 SECTION 608, CHAPTER 2,3,6
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-08-09 Cont ID  
Sent By shill Date 2019-08-09 Time 17:28 Rev Time 0.00
Received By shill Date 2019-08-09 Time 17:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By ccole Date 2019-06-11 Time 08:24 Rev Time 0.00
Received By ccole Date 2019-06-11 Time 08:24 Sent To  
Notes
2019-06-11 08:25:17ALL SHEETS OK
2019-06-03 15:52:14ELECTRIC SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By ccole Date 2019-04-09 Time 11:57 Rev Time 0.00
Received By ccole Date 2019-04-09 Time 11:57 Sent To  
Notes
2019-04-09 11:58:28ELECTRICAL PLANS ARE NOT SEALED- SECTION 61G15.23,005
 FAC.
2019-04-02 08:06:15ARCHITECTURAL SHEETS CHECKED FOR SIGNATURES. OK! JW
 04/02/2019

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-07 Cont ID  
Sent By aaponte Date 2019-08-07 Time 14:28 Rev Time 0.00
Received By aaponte Date 2019-08-07 Time 14:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-23 Cont ID  
Sent By aaponte Date 2019-05-23 Time 15:24 Rev Time 0.00
Received By aaponte Date 2019-05-23 Time 15:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-15 Cont ID  
Sent By aaponte Date 2019-03-15 Time 15:24 Rev Time 0.00
Received By aaponte Date 2019-03-15 Time 15:24 Sent To  
Notes
***NONE***