Plan Review Details - Permit 19020512
Plan Review Stops For Permit 19020512
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-20 Cont ID  
Sent By jleahy Date 2019-03-20 Time 11:07 Rev Time 0.00
Received By jleahy Date 2019-03-20 Time 11:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2020-02-07 Cont ID  
Sent By tklarge Date 2020-02-07 Time 05:40 Rev Time 0.00
Received By tklarge Date 2020-02-07 Time 05:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2019-09-16 Cont ID  
Sent By tklarge Date 2019-09-16 Time 11:22 Rev Time 0.00
Received By tklarge Date 2019-09-16 Time 11:09 Sent To  
Notes
2019-09-16 11:14:541) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2. THE FLAT DRAWING THAT
 HAS BEEN SUBMITTED IS UNACCEPTABLE AS IT IS EXTREMELY
 DIFFICULT TO TELL WHERE THE LINES START AND END.
 SEC.107.3.5.3 OF WPB AMEND. TO FBC. 2ND REQUEST.
 2.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21). 2ND REQUEST
 3.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.2ND REQUEST.
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 THE GAS PLAN NOTES 5 PSI AND 1/2 LB. CLARIFY.2ND
 REQUEST.
 5) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM. IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM.
 6) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC
 SEC. 107.2.1. 2ND REQUEST. THE FLOOR PLAN THAT WAS
 SUBMITTED NEEDS TO BE REDONE SO THAT IT CLEARLY
 REFLECTS THE LOCATION OF THE TANKLESS WATER HEATER.2ND
 REQUEST.
 7) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.2ND REQUEST.
 8) THE PLANS INDICATE AN EXISTING GAS METER/LP TANK AND
 CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS
 ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST
 BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.2ND REQUEST.
 9) SUBMIT ONE ADDITIONAL COPY OF THE INSTALLATION
 MANUAL. WPB AMEND. TO FBC SEC. 107.2.1.
 10) INDICATE ON THE MANUFACTURER'S SPECIFICATIONS WHICH
 MODEL OF THE WATER HEATER IS BEING INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 11) PLACE A NOTE ON THE PLAN HOW THE WINDOW IS
 NON-OPERATIONAL. SCREWING THE WINDOW SHUT IS NOT
 ACCEPTABLE. IF THIS IS A FIXED WINDOW, THEN NOTE SUCH
 ON THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-08-30 Cont ID  
Sent By tklarge Date 2019-08-30 Time 12:39 Rev Time 0.00
Received By tklarge Date 2019-08-30 Time 12:21 Sent To  
Notes
2019-08-30 12:39:431) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES,
 3.) TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
 4.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 7) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM. IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM.
 8) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC
 SEC. 107.2.1.
 9) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK.
 10) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 11) THE PLANS INDICATE AN EXISTING GAS METER/LP TANK
 AND CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS
 ADDRESS. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST
 BE ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO
 ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. IF
 UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.
  
 NOTE: THIS IS A RE-REVIEW OF THE LAST SUBMITTAL AND
 THESE COMEENTS TAKE PRECEDENCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 07:40 Rev Time 0.00
Received By thunt Date 2019-04-01 Time 07:40 Sent To  
Notes
2019-04-01 07:46:03GAS 1ST REVIEW***DENIED** NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
  
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2
  
 2) ANSWERED*****SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3) TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.\
  
 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. YOU SUBMITTED 37 DIFFERENT
 SIZING CHARTS. WHICH ONE?
  
 5) PAGE 21 CALLS OUT 4' MIN FOR A NON DIRECT VENT UNIT.
 YOU PLAN CALLS OUT FOR 28". PROVIDE A PLAN WITH A NEW
 LOCATION.SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1
  
 6) ANSWERED****** INDICATE ON THE PLAN IF THE TANKLESS
 WATER HEATER IS THE ONLY GAS APPLIANCE ON THIS SYSTEM?
 IF NOT, SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE
 SIZES, TYPE OF PIPE, THE DEVELOPED LENGTH TO THE
 FURTHEST GAS OUTLET, THE BTU LOAD OF EACH APPLIANCE,
 THE PSI OF THE SYSTEM, THE TYPE OF GAS AND THE TOTAL
 BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS ALSO APPLY
 TO A NEW GAS SYSTEM. NOTE CITY RECORDS SHOW OTHER GAS
 APPLIANCES. LIST THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21).
  
 7) PROVIDE WHICH OF THE 3 DIFFERENT MODELS ON THE
 INSTALLATION MANUAL YOU ARE USING.STATE WHICH
 MODELTANKLESS YOU PLAN TO INSTALLED. SUBMIT FULL
 MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED.
  
 8) ANSWERED******SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2
  
 9) NEW COMMENT: PLANS/ DOCUMENTS SHALL BE DRAWN UPON
 SUITABLE MATERIAL. PENCIAL IS NOT PERMITTED. FBC
 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By thunt Date 2019-03-15 Time 06:59 Rev Time 0.00
Received By thunt Date 2019-03-15 Time 06:59 Sent To E
Notes
2019-03-15 07:08:39GAS 1ST REVIEW***DENIED** NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
  
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2
  
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3) TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.\
  
 4) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3
  
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1
  
 6) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. NOTE
 CITY RECORDS SHOW OTHER GAS APPLIANCES. LIST THE BTU
 LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE
 SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS.401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR 2017
 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1 )
 THROUGH G2413.4 (21).
  
 7) STATE WHICH MODELTANKLESS YOU PLAN TO INSTALLED.
 SUBMIT FULL MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 8) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-02-07 Cont ID  
Sent By tklarge Date 2020-02-07 Time 05:40 Rev Time 0.00
Received By tklarge Date 2020-02-05 Time 16:26 Sent To  
Notes
2020-02-06 16:26:12RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-09-16 Cont ID  
Sent By tklarge Date 2019-09-16 Time 11:24 Rev Time 0.00
Received By tklarge Date 2019-09-12 Time 13:47 Sent To  
Notes
2019-09-13 13:47:51RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-30 Cont ID  
Sent By tklarge Date 2019-08-30 Time 12:39 Rev Time 0.00
Received By tklarge Date 2019-08-30 Time 12:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 07:46 Rev Time 0.00
Received By thunt Date 2019-03-28 Time 12:54 Sent To I
Notes
2019-03-29 12:55:06RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-20 Cont ID  
Sent By jleahy Date 2019-03-20 Time 11:07 Rev Time 0.00
Received By jleahy Date 2019-03-13 Time 13:21 Sent To  
Notes
2019-03-14 13:21:20ROUTED TO PLUMBING INBOX
2019-02-13 06:43:07TANKLESS WATER HEATER, NEEDS REVIEW.

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-16 Cont ID  
Sent By tklarge Date 2019-09-16 Time 11:24 Rev Time 0.00
Received By tklarge Date 2019-09-16 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-01 Cont ID  
Sent By thunt Date 2019-04-01 Time 07:30 Rev Time 0.00
Received By thunt Date 2019-04-01 Time 07:29 Sent To  
Notes
2019-04-01 07:30:12PLUMBING 2NDT REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 SEE GAS REVIEW COMMENTS
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-15 Cont ID  
Sent By thunt Date 2019-03-15 Time 06:56 Rev Time 0.00
Received By thunt Date 2019-03-15 Time 06:56 Sent To G
Notes
2019-03-15 06:59:17PLUMBING 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 SEE GAS REVIEW COMMENTS
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 561-248-2703