Plan Review Details - Permit 19020370
Plan Review Stops For Permit 19020370
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-28 Cont ID  
Sent By jgomez Date 2019-02-28 Time 11:03 Rev Time 0.00
Received By jgomez Date 2019-02-28 Time 10:51 Sent To  
Notes
2019-02-28 11:02:47MR. GOMEZ,
 PLEASE SEE THE BELOW COMMENTS AND PLEASE LET ME KNOW IF
 THEY WILL SUFFICE TO MOVE FORWARD WITH THIS PERMIT.
 THANK YOU FOR YOUR ASSISTANCE.
 KELLY
  
 GOOD AFTERNOON,
 BELOW PLEASE FIND THE COMMENTS
  
 RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ROOFING CONTRACTOR SUBMITTED FLORIDA PRODUCT
 APPROVAL FOR SKYLIGHTS. SCOPE OF WORK IS NOT CLEAR.
 ACCORDING TO CITY RECORDS, THIS HOUSE HAD NOT SKYLIGHTS
 AT TIME OF CONSTRUCTION AND THERE ARE NOT RECORDS FOR
 PERMIT APPLICATIONS FOR SKYLIGHT INSTALLATION. ALSO,
 PAPA AERIAL VIEW DOESN'T SHOW SKYLIGHTS EITHER. FRAMING
 AND INSTALLATION OF SKYLIGHTS CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSES A
 LICENSE TO DO SO. SEE SEC. 489.113 F.S. NEED TO PROVIDE
 COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE NEW
 SKYLIGHT, INCLUDING LOCATION ON THE ROOF. AND, NEED
 SEPARATE PERMIT OR SUB-PERMIT APPLICATION FOR THIS
 ADDITIONAL SCOPE OF WORK.
  
 -WE WOULD LIKE TO WITHDRAWAL THE PRODUCT APPROVAL FOR
 THE SKYLIGHTS PLEASE. WE WILL NOT BE COMPLETING ANY
 SKYLIGHT WORK. ***************
  
 ORIGINAL COMMENT:
 2- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL10450-R10 SUBMITTED. CLEARLY SPECIFY IF THE
 UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT
 OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING
 IS REQUIRED:
 A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC.
 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC.
 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT
 CAN NOT BE USED.
  
 5.6.1 UNDERLAYMENT IS GOING TO BE DIRECT-BOND TO DECK
 5.6.4
 #1 MAXIMUM DESIGN PRESSURE = -75.0 PSF: FIELD &
 PERIMETER *************************
 #2 MAXIMUM DESIGN PRESSURE = -120.0 PSF:
 CORNER************************************
  
 ROOFPRO
 6555 GARDEN ROAD, SUITE 18
 RIVIERA BEACH, FL 33404
 561-249-0247
  
 WWW.ROOFPRO411.COM
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-02-25 Cont ID  
Sent By pvalenti Date 2019-02-25 Time 13:08 Rev Time 0.00
Received By pvalenti Date 2019-02-25 Time 13:08 Sent To  
Notes
2019-02-25 13:14:56****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE ITEMS FROM LAST REVIEW (NOTED BELOW) HAVE NOT BEEN
 ADDRESSED. PLEASE REVIEW AND ADDRESS THE NOTED ITEMS:
  
 1 ROOFING CONTRACTOR SUBMITTED FLORIDA PRODUCT
 APPROVAL FOR SKYLIGHTS. SCOPE OF WORK IS NOT CLEAR.
 ACCORDING TO CITY RECORDS, THIS HOUSE HAD NOT SKYLIGHTS
 AT TIME OF CONSTRUCTION AND THERE ARE NOT RECORDS FOR
 PERMIT APPLICATIONS FOR SKYLIGHT INSTALLATION. ALSO,
 PAPA AERIAL VIEW DOESN'T SHOW SKYLIGHTS EITHER. FRAMING
 AND INSTALLATION OF SKYLIGHTS CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSES A
 LICENSE TO DO SO. SEE SEC. 489.113 F.S. NEED TO PROVIDE
 COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE NEW
 SKYLIGHT, INCLUDING LOCATION ON THE ROOF. AND, NEED
 SEPARATE PERMIT OR SUB-PERMIT APPLICATION FOR THIS
 ADDITIONAL SCOPE OF WORK.
  
 2 ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL10450 R10 SUBMITTED. CLEARLY SPECIFY IF THE
 UNDERLAYMENT IS GOING TO BE A DIRECT DECK UNDERLAYMENT
 OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING
 IS REQUIRED:
 A) FOR DIRECT BOND TO DECK SEE NOTE AT BOTTOM OF SEC.
 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC.
 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT
 CAN NOT BE USED.
 B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION
 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM
 FRSA/TRI APRIL 2012 (04 12), APPENDIX A, TABLE 1.
 CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-21 Cont ID  
Sent By jgomez Date 2019-02-21 Time 11:42 Rev Time 0.00
Received By jgomez Date 2019-02-21 Time 11:41 Sent To  
Notes
2019-02-21 11:42:24RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ROOFING CONTRACTOR SUBMITTED FLORIDA PRODUCT
 APPROVAL FOR SKYLIGHTS. SCOPE OF WORK IS NOT CLEAR.
 ACCORDING TO CITY RECORDS, THIS HOUSE HAD NOT SKYLIGHTS
 AT TIME OF CONSTRUCTION AND THERE ARE NOT RECORDS FOR
 PERMIT APPLICATIONS FOR SKYLIGHT INSTALLATION. ALSO,
 PAPA AERIAL VIEW DOESN'T SHOW SKYLIGHTS EITHER. FRAMING
 AND INSTALLATION OF SKYLIGHTS CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSES A
 LICENSE TO DO SO. SEE SEC. 489.113 F.S. NEED TO PROVIDE
 COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE NEW
 SKYLIGHT, INCLUDING LOCATION ON THE ROOF. AND, NEED
 SEPARATE PERMIT OR SUB-PERMIT APPLICATION FOR THIS
 ADDITIONAL SCOPE OF WORK.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
  
 ORIGINAL COMMENT:
 2- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL10450-R10 SUBMITTED. CLEARLY SPECIFY IF THE
 UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT
 OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING
 IS REQUIRED:
  
 A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC.
 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC.
 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT
 CAN NOT BE USED.
  
 B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION
 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM
 FRSA/TRI APRIL 2012 (04-12), APPENDIX A, TABLE 1.
 CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-11 Cont ID  
Sent By jgomez Date 2019-02-11 Time 17:55 Rev Time 0.00
Received By jgomez Date 2019-02-11 Time 17:55 Sent To  
Notes
2019-02-11 18:11:14RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ROOFING CONTRACTOR SUBMITTED FLORIDA PRODUCT
 APPROVAL FOR SKYLIGHTS. SCOPE OF WORK IS NOT CLEAR.
 ACCORDING TO CITY RECORDS, THIS HOUSE HAD NOT SKYLIGHTS
 AT TIME OF CONSTRUCTION AND THERE ARE NOT RECORDS FOR
 PERMIT APPLICATIONS FOR SKYLIGHT INSTALLATION. ALSO,
 PAPA AERIAL VIEW DOESN'T SHOW SKYLIGHTS EITHER. FRAMING
 AND INSTALLATION OF SKYLIGHTS CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSES A
 LICENSE TO DO SO. SEE SEC. 489.113 F.S. NEED TO PROVIDE
 COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE NEW
 SKYLIGHT, INCLUDING LOCATION ON THE ROOF. AND, NEED
 SEPARATE PERMIT OR SUB-PERMIT APPLICATION FOR THIS
 ADDITIONAL SCOPE OF WORK.
  
 2- ROOF TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL10450-R10 SUBMITTED. CLEARLY SPECIFY IF THE
 UNDERLAYMENT IS GOING TO BE A DIRECT-DECK UNDERLAYMENT
 OR MECHANICALLY ATTACHED BASE SHEET. THEN THE FOLLOWING
 IS REQUIRED:
  
 A) FOR DIRECT-BOND TO DECK SEE NOTE AT BOTTOM OF SEC.
 5.6.1 AND CLEARLY IDENTIFY WHICH ASSEMBLY FROM SEC.
 5.6.4 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN IT
 CAN NOT BE USED.
  
 B) FOR MECHANICALLY ATTACHED BASE SHEET SEE SECTION
 5.6.2 AND PROVIDE MINIMUM FASTENING REQUIREMENTS FROM
 FRSA/TRI APRIL 2012 (04-12), APPENDIX A, TABLE 1.
 CLEARLY MARK TABLE 1 WITH PROPOSED FASTENING.
  
 3- CLEARLY IDENTIFY ON PRODUCT APPROVALS THE ROOF TILE
 PROFILE AND PADDY SIZE AS REQUIRED BY CITY POLICY FOR
 ALL ROOFING PERMITS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-28 Cont ID  
Sent By jgomez Date 2019-02-28 Time 11:15 Rev Time 0.00
Received By jgomez Date 2019-02-28 Time 10:45 Sent To I
Notes
2019-02-28 10:51:03RECEIVED E-MAIL FROM KELLY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-21 Cont ID  
Sent By jgomez Date 2019-02-21 Time 11:46 Rev Time 0.00
Received By jgomez Date 2019-02-19 Time 15:38 Sent To I
Notes
2019-02-20 15:38:50RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-11 Cont ID  
Sent By jgomez Date 2019-02-11 Time 18:12 Rev Time 0.00
Received By jgomez Date 2019-02-08 Time 11:45 Sent To I
Notes
***NONE***