2019-02-11 18:40:54 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PERMIT APPLICATION INDICATES THAT THERE IS A FLAT |
| ROOF AREA TO BE RE-ROOFED ALSO. THERE WAS NO |
| INFORMATION SUBMITTED FOR THE FLAT ROOF. PROVIDE |
| PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF AND CLEARLY |
| MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| R301.1 FBC-RESIDENTIAL. NOTE: IF THE SELECTED ASSEMBLY |
| DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE |
| REQUIRED. |
| FAC 61G20-3.001. |
| |
| 2- SPECIFY SHINGLES ROOF PITCH AS REQUIRED BY CITY |
| POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| WITH SEC. R905.2.2 FBC-RESIDENTIAL. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |