Plan Review Details - Permit 19020308
Plan Review Stops For Permit 19020308
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-24 Cont ID  
Sent By pvalenti Date 2019-02-24 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2019-02-24 Time 14:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By pvalenti Date 2019-02-08 Time 08:36 Rev Time 0.00
Received By pvalenti Date 2019-02-08 Time 08:36 Sent To  
Notes
2019-02-08 08:41:48****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107.2.1 PLEASE PROVIDE MORE INFORMATION; CLEARLY
 INDICATE THE SELECTED OPTIONS, ON THE PRODUCT APPROVAL,
 FOR EACH OPENING.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By pleduc Date 2019-02-15 Time   Rev Time 0.00
Received By pleduc Date 2019-02-15 Time 13:25 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-02-08 Cont ID  
Sent By pleduc Date 2019-02-08 Time   Rev Time 0.00
Received By pleduc Date 2019-02-08 Time 10:10 Sent To I
Notes
2019-02-08 10:17:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS A FIRE ALARM PLAN SUBMITTED WITH THIS
 PACKET THAT IS UNREADALBE.
  
 PLEASE CLARIFY IF THIS IS FOR FIRE ALARM OR DOOR
 REPLACEMENT. IF THIS IS NOT A FIRE ALARM MODIFICATION,
 DO NOT USE FIRE ALARM PLANS.
  
  
  
 2) THERE IS NO DOOR SCHEDULE THAT CLEARLY INDICATES
 DOOR SIZE, HARDWARE, TYPE, SWING, ETC.
  
  
  
 3) PLEASE ENLARGE THE DOOR AREA DRAWING TO CLEARLY
 DEFINE SWING AND PATH OF TRAVEL.
  
  
  
 4) CARD READER ACCESS IS INDICATED, PLEASE CLARIFY AT
 WHICH DOORS.
  
 LOW VOLTAGE FOR CARD READER SHALL BE UNDER SEPARATE
 SHOP DRAWINGS AND PERMIT.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-24 Cont ID  
Sent By pvalenti Date 2019-02-24 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2019-02-14 Time 09:42 Sent To  
Notes
2019-02-15 09:42:53RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-08 Cont ID  
Sent By cpuell Date 2019-02-08 Time 10:35 Rev Time 0.00
Received By cpuell Date 2019-02-07 Time 11:38 Sent To  
Notes
***NONE***