Plan Review Details - Permit 19020268
Plan Review Stops For Permit 19020268
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-13 Cont ID  
Sent By fgiaquin Date 2019-03-13 Time 17:42 Rev Time 0.00
Received By fgiaquin Date 2019-03-13 Time 17:11 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-15 Cont ID  
Sent By fgiaquin Date 2019-02-15 Time 06:41 Rev Time 0.00
Received By fgiaquin Date 2019-02-15 Time 06:24 Sent To M
Notes
2019-02-15 06:28:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE IS LOW FOR AMOUNT OF WORK SHOWN. RAISE VALUE.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 INFORMATIONAL NOTE: FIRE ALARM DESIGNS OVER $5000 MUST
 BE DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL.
 FBC 105.3.1.2 #4
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By scaldero Date 2019-03-11 Time 10:47 Rev Time 0.00
Received By scaldero Date 2019-03-11 Time 10:46 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-11 Cont ID  
Sent By scaldero Date 2019-02-11 Time 09:18 Rev Time 0.00
Received By scaldero Date 2019-02-11 Time 09:09 Sent To E
Notes
2019-02-11 09:18:26PERMIT #19020268
 FIRE REVIEW COMMENTS
  
 REVIEW COMPLETED BY FRANK STALLWORTH, FIRE INSPECTOR I.
  
 APPROVED WITH COMMENTS:
 INSTALLATION SHALL COMPLY WITH ALL REQUIREMENTS AS
 LISTED UNDER NFPA 72.
 INSTALLATION SHALL MEET THE REQUIREMENTS OF NFPA 72:
 13.7.3.2.3.8 VERIFICATION OF COMPLIANT INSTALLATION.
 13.7.3.2.3.8.1 WHERE REQUIRED BY THE AHJ, COMPLIANCE OF
 THE COMPLETED INSTALLATION WITH THE REQUIREMENTS OF
 NFPA 72, AS
 IMPLEMENTED VIA THE REFERRING CODE(S), SPECIFICATIONS,
 AND/OR OTHER CRITERIA APPLICABLE TO THE SPECIFIC
 INSTALLATION, SHALL BE
 CERTIFIED BY A QUALIFIED AND IMPARTIAL THIRD-PARTY
 ORGANIZATION ACCEPTABLE TO THE AHJ. [72: 7.5.8.1]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-13 Cont ID  
Sent By fgiaquin Date 2019-03-13 Time 17:42 Rev Time 0.00
Received By fgiaquin Date 2019-03-08 Time 14:55 Sent To  
Notes
2019-03-08 14:55:17RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-07 Cont ID  
Sent By hmoser Date 2019-03-07 Time 08:17 Rev Time 0.00
Received By hmoser Date 2019-02-06 Time 13:47 Sent To  
Notes
2019-02-07 13:48:00ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2019-03-07 Cont ID  
Sent By hmoser Date 2019-03-07 Time 08:17 Rev Time 0.00
Received By hmoser Date 2019-03-07 Time 08:17 Sent To I
Notes
***NONE***