Plan Review Details - Permit 19020201
Plan Review Stops For Permit 19020201
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-14 Cont ID  
Sent By jgomez Date 2019-05-14 Time 09:42 Rev Time 0.00
Received By jgomez Date 2019-05-14 Time 09:41 Sent To  
Notes
2019-05-14 10:15:02BUILDING REVIEW APPROVED WITH PROVISO:
 1- SUBMIT DRAINAGE PLAN FOR REVIEW PRIOR TO
 INSPECTIONS.
 2- SUBMIT COMPLETE PRODUCT APPROVAL FOR REVIEW
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGES (2
 COPIES) FOR:
 A) INSWING ENTRY DOOR AS SHOWN ON PLANS. CLEARLY MARK
 THE ENTRY DOOR AND THE GARAGE SIDE DOOR.
 B) GARAGE OUTSIDE SWING DOOR. CLEARLY MARK THE ENTRY
 DOOR AND THE GARAGE SIDE DOOR.
 3- ALL PRODUCT APPROVALS TO BE APPROVED BY ENGINEER OF
 RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-13 Cont ID  
Sent By jgomez Date 2019-05-13 Time 18:52 Rev Time 0.00
Received By jgomez Date 2019-05-13 Time 14:32 Sent To M
Notes
2019-05-13 14:45:56NEW SINGLE FAMILY RESIDENCE (R3), SECOND REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 RESPONSE:
 BASED ON DRAWINGS SUBMITTED WITH THE PROPOSED POOL AND
 BRICK PATIO, THE REAR PROPERTY REQUIRES MORE ATTENTION.
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN FOR
 ENTIRE LOT AS REQUIRED BY SEC. 110.9 CITY AMENDMENTS.
  
 2- OK.
  
 3- A) OK.
  
 B) THE TREAD DEPTH SHALL BE MEASURED HORIZONTALLY
 BETWEEN THE VERTICAL PLANES OF THE FOREMOST PROJECTION
 OF ADJACENT TREADS. REVISE DIMENSIONS SHOWN ON STAIR
 SECTION 'A' ON SHEET A-2. THEY ARE MEASURED FROM THE
 VERTICAL PLAN OF THE RISER TO THE END OF THE NOSING.
  
 RESPONSE:
 TREAD DIMENSION IS NOT MEASURED PROPERLY. NEED TO
 MEASURE FROM THE VERTICAL PLANES (RISER TO RISER). THE
 NOSING DIMENSION AND TREAD DIMENSION SHOWN ON BOTH
 STAIRS DETAILS DETAILS DON'T MATCH. REVISE AS REQUIRED
 TO MATCH.
  
 4- SHEET A-2:
 A) OK.
  
 B)OK.
  
 C)OK.
  
 D) OK.
  
 5- A)ACCORDING TO FIGURE R301.2(7) OF FBC-RESIDENTIAL
 THE MINIMUM DIMENSION "A" FOR WALL AND ROOF END ZONE IS
 4 FT NOT 3.5 FT. REVISE THIS DIMENSION ON SHEET A-3 AND
 S-3.
 NOTE: WALL ELEVATION ON SHEET A-3 SPECIFIES A=3'-6".
 REVISE AS REQUIRED.
  
 RESPONSE:
 NOT ADDRESSED.
  
 B) OK.
  
 C) OK.
  
 6- OK.
  
 7- A) PROVIDE SPECIFICATIONS FOR THE INSULATION BETWEEN
 THE GARAGE AND THE A/C AREA OF THE MAIN HOUSE. SEC.
 R103.2 FBC-ENERGY CONSERVATION. COORDINATE WITH ENERGY
 CALCULATIONS.
  
 RESPONSE:
 PLANS DON'T SHOW ANY INSULATION BETWEEN THE GARAGE AND
 A/C AREA.
  
 B) PROVIDE THE MANUFACTURER'S SPECIFICATION S FOR
 WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON
 ITEM #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 INFORMATION SUBMITTED DOESN'T MATCH PRODUCT APPROVALS
 SUBMITTED. THE INFORMATION SUBMITTED IS FOR ANOTHER
 WINDOW MODEL. IT DOESN'T MATCH THE MODEL SHOWN ON THE
 PRODUCT APPROVAL SUBMITTED.
  
 8- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE CEILING AT THE PATIO AREA. SEC.
 R703.1.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 PLANS DON'T SHOW ANY DETAILS.
  
 9- OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13-
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) INSWING ENTRY DOOR AS SHOWN ON PLANS. FLORIDA
 PRODUCT APPROVAL FL22383-R1 SUBMITTED WAS DENIED. NEED
 TO PROVIDE CURRENT PRODUCT APPROVAL AND ALSO PROVIDE
 THE INSTALLATION DRAWINGS THAT CORRESPOND TO THIS
 PRODUCT APPROVAL.
  
 RESPONSE:
 INFORMATION FROM TWO DIFFERENT MANUFACTURER'S WAS
 SUBMITTED. CLEARLY MARK THE ENTRY DOOR AND THE GARAGE
 SIDE DOOR AND PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 CORRESPONDING DRAWINGS.
  
 B) GARAGE OUTSIDE SWING DOOR. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE (TWO COPIES) THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
  
 RESPONSE:
 INFORMATION FROM TWO DIFFERENT MANUFACTURER'S WAS
 SUBMITTED. CLEARLY MARK THE ENTRY ODOR AND THE GARAGE
 SIDE DOOR AND PROVIDE COMPLETE PRODUCT APPROVAL,
 INCLUDING THE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 CORRESPONDING DRAWINGS.
  
 C)OK.
  
 D)OK.
  
 E) OK.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 (A)ENGINEER'S LETTER LISTING ALL THE PRODUCT APPROVALS
 IS MISSING THE ENGINEER'S TITLE BLOCK WITH ALL HIS
 INFORMATION. CHAPTER 471 F.S.
  
 (B)PRODUCT APPROVALS LISTED DON'T MATCH PRODUCT
 APPROVALS SUBMITTED. REVISE AS REQUIRED TO MATCH.
  
 16- OK.
  
 17 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-03-04 Cont ID  
Sent By jgomez Date 2019-03-04 Time 16:59 Rev Time 0.00
Received By jgomez Date 2019-03-04 Time 08:50 Sent To  
Notes
2019-03-04 17:00:02NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 NOTE: SITE PLAN ON SHEET SP-1 TO SHOW HOW DRAINAGE AT
 THE REAR OF PROPERTY AND ON THE SIDES IS CONTROLLED.
 SHOW HOW THE WATER IS RETAINED WITHIN THE PROPERTY AND
 AWAY FROM BUILDING FOUNDATION AND WITHOUT GOING TO THE
 NEIGHBOR'S PROPERTY. ARE SWALES PROPOSED. PROVIDE
 DETAILS AND SPECIFICATIONS.
  
 2- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH SEC.
 R310.2.1 FBC-RESIDENTIAL. REVISE SPECIFICATIONS ON
 FIRST AND SECOND FLOOR PLAN, EXTERIOR ELEVATIONS AND
 WINDOW SCHEDULE.AS REQUIRED.
 37"X60" SINGLE HUNG WINDOWS DON'T PROVIDE THE MIN.
 CLEAR HEIGHT AND MIN. TOTAL CLEAR OPENING OF 5.7S.F.
 NOTE: CONTACT PGT WINDOWS FOR SIZES THAT COMPLY.
  
 3- A) STAIR TREADS DEPTH SHALL BE NO LESS THAN 10".
 SEC. R311.7.5.2 FBC-RESIDENTIAL. REVISE SPECIFICATIONS
 ON FIRST AND SECOND FLOOR PLANS ON SHEETS A-2.1 AND
 A-2.
  
 B) THE TREAD DEPTH SHALL BE MEASURED HORIZONTALLY
 BETWEEN THE VERTICAL PLANES OF THE FOREMOST PROJECTION
 OF ADJACENT TREADS. REVISE DIMENSIONS SHOWN ON STAIR
 SECTION 'A' ON SHEET A-2. THEY ARE MEASURED FROM THE
 VERTICAL PLAN OF THE RISER TO THE END OF THE NOSING.
  
 4- SHEET A-2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INTERIOR HANDRAILS AND GUARDRAIL AND FOR BALCONY
 GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE
 DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS
 THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW
 PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 B) REVISE HANDRAIL HEIGHT SHOWN ON STAIR SECTION 'A' AT
 THE BOTTOM HANDRAIL. HEIGHT SHALL BE NO LESS THAN 34"
 AND MORE THAN 38". SEC. R311.7.8.1 FBC-RESIDENTIAL.
  
 C) PROVIDE SPECIFICATIONS FOR THE STAIR FIREBLOCKING AT
 TOP AND BOTTOM OF STRINGERS AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 STAIR CONSTRUCTION. SPECIFY SIZE SIZE AND NUMBER OF
 STRINGERS, TOP AND BOTTOM CONNECTORS, ETC. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- A)ACCORDING TO FIGURE R301.2(7) OF FBC-RESIDENTIAL
 THE MINIMUM DIMENSION "A" FOR WALL AND ROOF END ZONE IS
 4 FT NOT 3.5 FT. REVISE THIS DIMENSION ON SHEET A-3 AND
 S-3.
 NOTE: WALL ELEVATION ON SHEET A-3 SPECIFIES A=3'-6".
 REVISE AS REQUIRED.
  
 B) REVISE THE DESIGN PRESSURES FOR DOORS AND WINDOWS ON
 SHEET A-3 AND A-4. PROVIDE THE DESIGN PRESSURES FOR THE
 ACTUAL TRIBUTARY AREA OR PROVIDE THE DESIGN PRESSURES
 FOR THE LOWEST TRIBUTARY AREA SHOWN ON THE WIND
 PRESSURE DESIGN TABLES ON SHEET A-3. FOR EXAMPLE THE
 TRIBUTARY AREA FOR END WINDOW ON MASTER BEDROOM
 IS NOT 20 S.F. IT IS LESS THAN 20 S.F. BUT THE
 SPECIFIED DESIGN PRESSURES ARE FOR 20 S.F. SEE FOOTNOTE
 "B" ON TABLE R301.2(2) FBC-RESIDENTIAL AND REVISE AS
 REQUIRED.
  
 C) CLARIFY WHAT ARE THE DESIGN PRESSURES ON ROOF GIVEN
 ON SHEET S-3 FOR ZONE O AND ZONE 1. WHAT ARE THESE
 DESIGN PRESSURES AND WHY NOT ALL THE ROOF ZONES ARE
 CONSIDERED?. SEC. 107.2.1 CITY AMENDMENTS
  
 6- WINDOWS LOCATED ON THE STAIRWAY NEED TO COMPLY WITH
 THE WINDOW FALL PROTECTION SEC. R312.2 FBC-RESIDENTIAL.
 PROVIDE COMPLETE DETAIL AND SPECIFICATIONS SHOWING
 COMPLIANCE.
 NOTE: WINDOWS SHOWN ON THE EXTERIOR ELEVATION ON-SHEET
 A-4 ARE NOT DRAWN TO SCALE. CLEARLY IDENTIFY IF THERE
 ARE ANY WINDOWS WITH THE WINDOW SILL LESS THAN 24" FROM
 THE FINISHED FLOOR. THEY NEED TO COMPLY WITH THE WINDOW
 FALL PROTECTION. COORDINATE WITH SIZE OF EGRESS WINDOWS
 ITEM #2 ABOVE.
  
 7- A) PROVIDE SPECIFICATIONS FOR THE INSULATION BETWEEN
 THE GARAGE AND THE A/C AREA OF THE MAIN HOUSE. SEC.
 R103.2 FBC-ENERGY CONSERVATION. COORDINATE WITH ENERGY
 CALCULATIONS.
 NOTE: COORDINATE CEILING INSULATION R-VALUE AND
 EXTERIOR WALL INSULATION R-VALUE WITH ENERGY
 CALCULATIONS SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 B) PROVIDE THE MANUFACTURER'S SPECIFICATION S FOR
 WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON
 ITEM #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION.
  
 8- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE CEILING AT THE PATIO AREA. SEC.
 R703.1.2.1 FBC-RESIDENTIAL.
  
 9- SECOND FLOOR FRAMING PLAN. PROVIDE DETAILS AND
 SPECIFICATIONS FOR DRAFTSTOPPING AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL. AND, SHOW LOCATION.
  
 10- NEED ATTIC ACCESS ABOVE GARAGE, ABOVE PATIO AREA
 AND ABOVE SECOND FLOOR AS REQUIRED BY SEC. R807
 FBC-RESIDENTIAL. SHOW LOCATION AND SIZE.
  
 11- SPECIFY CARBON MONOXIDE ALARMS AT THE LOCATION
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 12- PROVIDE FIRE RATING SPECIFICATIONS FOR GARAGE DOOR
 LEADING TO THE MAIN HOUSE AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL.
  
 13- PROVIDE ICC EVALUATION REPORT (2 COPIES) FOR THE
 SPRAYED CEILING R-19 INSULATION TO VERIFY COMPLIANCE
 WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) INSWING ENTRY DOOR AS SHOWN ON PLANS. FLORIDA
 PRODUCT APPROVAL FL22383-R1 SUBMITTED WAS DENIED. NEED
 TO PROVIDE CURRENT PRODUCT APPROVAL AND ALSO PROVIDE
 THE INSTALLATION DRAWINGS THAT CORRESPOND TO THIS
 PRODUCT APPROVAL.
  
 B) GARAGE OUTSIDE SWING DOOR. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE (TWO COPIES) THAT CORRESPONDS TO
 DRAWINGS SUBMITTED.
  
 C)ROOF TILE ADHESIVE. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE (TWO COPIES) THAT CORRESPONDS TO DRAWINGS
 SUBMITTED.
  
 D)ROOF TILE UNDERLAYMENT. BORAL TILE SEAL NOA
 17-0530.10 SUBMITTED EXPIRED ON 07/31/18. NEED CURRENT
 NOA.
  
 E) 8" AND 12" PRECAST LINTELS. NOA 14-0903.03 FOR 12"
 PRECAST LINTEL SUBMITTED EXPIRED ON 09/11/2018. NEED
 CURRENT NOA AND NEED NOA FOR 8" PRECAST LINTELS.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: ENGINEER TO REVISE PRODUCT APPROVAL LETTER
 SUBMITTED. SOME NOA'S DON'T MATCH NOA'S SUBMITTED AND
 SOME PRODUCT APPROVALS ARE EXPIRED. ALSO, CLEARLY
 IDENTIFY FLORIDA PRODUCT APPROVAL OR NOA NUMBER FOR
 EACH REVIEWED PRODUCT APPROVAL. THERMA-TRU FIBERGLASS
 DOOR NEED THE FLORIDA PRODUCT APPROVAL NUMBER. OR
 ENGINEER MAY PROVIDE REVIEW STAMP OR BY HAND ON EACH
 PRODUCT APPROVAL COVER PAGE.
  
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $299,994. THE
 PERMIT FEE BALANCE IS $5159.20.
  
  
 17 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-26 Cont ID  
Sent By jpearson Date 2019-04-26 Time 13:59 Rev Time 0.00
Received By jpearson Date 2019-04-25 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By jpearson Date 2019-02-27 Time 12:45 Rev Time 0.00
Received By jpearson Date 2019-02-26 Time 12:37 Sent To  
Notes
2019-02-27 12:45:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS, BASED ON FORMULA PROVIDED IN FBC RESIDENTIAL.
 NEC 220; FBC RE E3602.2
 3. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 4. EXTERIOR RECEPTACLE ON PATIO IS REQUIRED TO BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.3
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 7. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 8. NO PARTS OF CORD-CONNECTED LUMINAIRES, CHAIN-,
 CABLE-, OR CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK,
 PENDANTS, OR CEILING-SUSPENDED (PADDLE) FANS SHALL BE
 LOCATED WITHIN A ZONE MEASURED 3 FEET HORIZONTALLY AND
 8 FEET VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR
 SHOWER STALL THRESHOLD. PROVIDE CORRECTION FOR MASTER
 BATH. NEC 410.10(D); FBC RE E4003.11
 9. PLEASE PROVIDE ORIGINAL SIGNATURE ON PLAN OF PERSON
 RESPONSIBLE FOR DESIGN, A PHOTOCOPY OF SIGNATURE IS NOT
 ACCEPTABLE. WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 09:55 Rev Time 0.00
Received By jgomez Date 2019-05-22 Time 15:45 Sent To I
Notes
2019-05-23 15:46:01IMPACT FEES ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-14 Cont ID  
Sent By cthroop Date 2019-05-14 Time 11:12 Rev Time 0.00
Received By cthroop Date 2019-04-09 Time 16:22 Sent To  
Notes
2019-04-10 16:22:33R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-12 Cont ID  
Sent By cpuell Date 2019-03-12 Time 12:37 Rev Time 0.00
Received By cpuell Date 2019-02-06 Time 14:56 Sent To  
Notes
2019-02-07 14:57:12R23

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-05-24 Cont ID  
Sent By jgomez Date 2019-05-24 Time 09:55 Rev Time 0.00
Received By jgomez Date 2019-05-24 Time 09:50 Sent To  
Notes
2019-05-24 09:55:41$10,003.08 PAID. MU-2019-015111.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-05-13 Cont ID  
Sent By jgomez Date 2019-05-13 Time 18:53 Rev Time 0.00
Received By jgomez Date 2019-05-13 Time 18:53 Sent To  
Notes
2019-05-13 18:53:36IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-03-04 Cont ID  
Sent By jgomez Date 2019-03-04 Time 09:46 Rev Time 0.00
Received By jgomez Date 2019-03-04 Time 09:45 Sent To  
Notes
2019-03-04 09:46:43IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-14 Cont ID  
Sent By jgomez Date 2019-05-14 Time 08:17 Rev Time 0.00
Received By cthroop Date 2019-05-14 Time 11:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-11 Cont ID  
Sent By cthroop Date 2019-03-11 Time 13:49 Rev Time 0.00
Received By cthroop Date 2019-03-11 Time 10:24 Sent To Z
Notes
2019-03-11 13:53:01MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONTRACTOR SHALL SIGN PLAN.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 2. IDENTIFY LOCATION OF CONDENSATE LINE PER FBC
 M1411.3.
  
 3. LOCKING ACCESS PORT CAPS REQUIRED PER FBC M1411.8.
  
 4. PROVIDE DETAIL FOR EXTERIOR INSTALLATION OF
 CONDENSING UNIT PER FBC M1401.4.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-18 Cont ID  
Sent By jesmith Date 2019-04-18 Time 11:20 Rev Time 0.00
Received By jesmith Date 2019-04-18 Time 11:18 Sent To  
Notes
2019-04-18 11:19:08APPROVED
 PROVISO
  
 1. VENT FOR WATER CLOSET AND TUB/SHOWER IN SECOND BATH
 SHALL RISE VERTICALLY FROM THE FIXTURE DRAIN TO WHICH
 IT IS CONNECTED TO A POINT 6" ABOVE THE FLOOD LEVEL RIM
 OF THE FIXTURES BEING VENTED PER FBC RES P3104.3. SEE
 RED LINED COMMENT AND CORRECTED SECTION ON P-1 SANITARY
 RISER DIAGRAM
  
 NOTE: A SEPARATE APPLICATION FOR GAS PERMIT IS REQUIRED
 PER WPB FBC 105.1.PROVIDE WITH SEPARATE GAS PERMIT
 APPLICATION THE FOLLOWING PER WPB FBC 107.2.1
 A. SUBMIT GAS RISER DIAGRAM THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES
 G2413.4.1 AND G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF ANY
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE.
 3. TYPE OF GAS (LP OR NATURAL).
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO FBC FG SECS. 401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR FBC RES
 SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH
 G2413.4 (21). PROVIDE ON THE PLANS THE TABLES USED FOR
 CALCULATIONS AND/OR TWO COPIES OF SAID TABLES..
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER FBC FG
 SEC.402.4.1, 402.4.2, FBC RES. SEC. G 2413.4.1 AND
 G2413.4.2.
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR IF APPLICABLE
 (IE. A RANGE OR CLOTHES DRYER) PER FBC FG SEC.304.1 AND
 614.6 (CLOTHES DRYERS) OR FBC RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS AND
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 SEC. 402.2, AND 301.3 OR FBC RES SEC. G2404.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 9. SHOW THE LOCATIONS OF THE GAS METER AND THE WATER
 HEATER ON PLAN SHEET A-1.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-07 Cont ID  
Sent By jesmith Date 2019-03-07 Time 10:01 Rev Time 0.00
Received By jesmith Date 2019-03-07 Time 08:22 Sent To  
Notes
2019-03-07 10:01:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 A SEPARATE GAS PERMIT IS REQUIRED PER WPB FBC 105.1.
 PEASE SEE NOTES LISTED AFTER PLUMBING COMMENTS.
  
 1ST REVIEW
 PLUMBING COMMENTS:
 DENIED
 PLAN SHEET P-1
 1. PLAN SHALL INCLUDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN PER WPB FBC 107.2.1
 2. SANITARY RISER DIAGRAM
 A. POWDER ROOM WATER CLOSET FIXTURE DRAIN SHALL BE
 VENTED PER FBC RES P3102.2.1.
 B. VENT FOR WATER CLOSET AND TUB/SHOWER IN SECOND BATH
 SHALL RISE VERTICALLY FROM THE FIXTURE DRAIN TO WHICH
 IT IS CONNECTED TO A POINT 6" ABOVE THE FLOOD LEVEL RIM
 OF THE FIXTURES BEING VENTED PER FBC RES P3104.3.
 C. SANITARY RISER CALLS OUT A SHOWER IN THE SECOND
 BATH. PLAN SHEET A-2 SHOWS A BATHTUB. PIEASE CLARIFY
 PER WPB FBC 107.2.1.
 D. PROVIDE AN INDIVIDUAL VENT FOR THE WASHER PER FBC
 RES P3102.2.1 AND P3107.1 WHICH LIMITS COMMON VENTING
 TO TWO (2) TRAPS OR TRAPPED FIXTURES.
 E. EACH OF THE TWO (2) LAVATORIES IN THE MASTER BATHIS
 S-TRAPPED WHICH IS PROHIBITED PER FBC RES P3105.1 AND
 P3201.5. PROVIDE INDIVIDUAL VENTS FOR P3101.2.1,
 P3104.1 AND P3114.
 F. PROVIDE DRAIN AND VENT FOR THE KITCHEN SINK SHOWN ON
 A-1.
 3. PROVIDE WITH THE APPLICATION FOR A GAS PERMIT THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUAL
 FOR THE GAS WATER HEATER SHOWN ON PLAN SHEET A/C-1 PER
 WPB FBC 107.2.1.
  
 END OF PLUMBING COMMENTS
  
 RE: GAS PERMIT APPLICATION.
 PROVIDE WITH SEPARATE GAS PERMIT APPLICATION THE
 FOLLOWING PER WPB FBC 107.2.1
 1. SUBMIT GAS RISER DIAGRAM THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES
 G2413.4.1 AND G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF ANY
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE.
 3. TYPE OF GAS (LP OR NATURAL).
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO FBC FG SECS. 401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) OR FBC RES
 SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH
 G2413.4 (21). PROVIDE ON THE PLANS THE TABLES USED FOR
 CALCULATIONS AND/OR TWO COPIES OF SAID TABLES..
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER FBC FG
 SEC.402.4.1, 402.4.2, FBC RES. SEC. G 2413.4.1 AND
 G2413.4.2.
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR IF APPLICABLE
 (IE. A RANGE OR CLOTHES DRYER) PER FBC FG SEC.304.1 AND
 614.6 (CLOTHES DRYERS) OR FBC RES. SEC. G 2407.1 AND
 G2439.4 (CLOTHES DRYERS).
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 SEC. 402.2, AND 301.3 OR FBC RES SEC. G2404.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 9. SHOW THE LOCATIONS OF THE GAS METER AND THE WATER
 HEATER ON PLAN SHEET A-1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-05-13 Cont ID  
Sent By jgomez Date 2019-05-13 Time 18:55 Rev Time 0.00
Received By jgomez Date 2019-05-13 Time 18:55 Sent To  
Notes
2019-05-13 18:58:19 
 APPROVED:
 A)BORAL ROOF TILE NOA 18-0509.17
  
 B) ROOF TILE ADHESIVE NOA 17-0322.03.
  
 C)ROOF TILE UNDERLAYMENT. NOA 18-0502.03.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-03-04 Cont ID  
Sent By jgomez Date 2019-03-04 Time 17:01 Rev Time 0.00
Received By jgomez Date 2019-03-04 Time 17:00 Sent To  
Notes
2019-03-04 17:02:121- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) ROOF TILE ADHESIVE. PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE (TWO COPIES) THAT CORRESPONDS TO DRAWINGS
 SUBMITTED.
  
 B)ROOF TILE UNDERLAYMENT. BORAL TILE SEAL NOA
 17-0530.10 SUBMITTED EXPIRED ON 07/31/18. NEED CURRENT
 NOA.
  
 APPROVED:
 BORAL ROOF TILE NOA 18-0509.17
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By awooten Date 2019-05-08 Time   Rev Time 0.00
Received By awooten Date 2019-05-08 Time   Sent To  
Notes
2019-05-08 16:44:34***********************ZONING
 PROVISO**********************
  
 PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY, THE
 FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-07 Cont ID  
Sent By awooten Date 2019-05-07 Time   Rev Time 0.00
Received By awooten Date 2019-05-07 Time   Sent To  
Notes
2019-05-07 14:00:51***************************ZONING REVIEW
 FAILED***************************
  
 REPEAT COMMENTS FROM 3/12/19
  
 SEPARATE LANDSCAPE PERMIT REQUIRED, BEFORE
 ZONING APPROVAL CAN BE ISSUED.
  
 SEPARATE PERMITS REQUIRED FOR THE POOL, DRIVEWAY AND
 ANY FENCING/WALL PROPOSED.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-12 Cont ID  
Sent By ajones Date 2019-03-12 Time 11:23 Rev Time 0.00
Received By ajones Date 2019-03-12 Time 11:21 Sent To I
Notes
2019-03-12 11:23:323/12/19- SEPERATE LANDSCAPE PERMIT REQUIRED, BEFORE
 ZONING APPROVAL CAN BE ISSUED.
 SEPERATE PERMITS REQUIRED FOR THE POOL, DRIVEWAY AND
 ANY FENCING/WALL PROPOSED.
  
 ANGELLA VANN
 561-822-1441
 [email protected]