Plan Review Details - Permit 19020136
Plan Review Stops For Permit 19020136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By jduprey Date 2019-03-11 Time 08:35 Rev Time 0.00
Received By jduprey Date 2019-03-11 Time 08:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-28 Cont ID  
Sent By jduprey Date 2019-02-28 Time 10:05 Rev Time 0.00
Received By jduprey Date 2019-02-28 Time 09:59 Sent To  
Notes
2019-02-28 10:05:41BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ENGINEERED CALCULATIONS FOR WIND LOADS PER
 FBC CHAPTER 16. FBC 107
  
 2. THE DRAWINGS PROVIDED ARE NOT SIGNED BY THE
 DESIGNER. PLEASE PROVIDE DRAWINGS WITH ORGINAL
 SIGNATURE BY DESIGNER.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL
 SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN.
 CODE RULE 61G15-23.001.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-11 Cont ID  
Sent By jduprey Date 2019-03-11 Time 08:35 Rev Time 0.00
Received By jduprey Date 2019-03-04 Time 15:29 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-28 Cont ID  
Sent By cpuell Date 2019-02-28 Time 13:50 Rev Time 0.00
Received By cpuell Date 2019-02-05 Time 11:04 Sent To  
Notes
2019-02-06 11:05:07ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By jduprey Date 2019-03-11 Time 08:35 Rev Time 0.00
Received By mcruz Date 2019-03-07 Time 16:22 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-02-13 Cont ID  
Sent By mcruz Date 2019-02-13 Time 13:42 Rev Time 0.00
Received By mcruz Date 2019-02-11 Time 15:28 Sent To B
Notes
2019-02-13 13:42:39ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) INDICATE DIMENSIONS (LXW) OF NORTH FACADE (AREA OF
 WALL FACING WINTERS AS WELL AS PORTION OF WALL WHERE
 SIGN IS GOING ON EAST SIDE OF BUILDING FACING NORTH).
  
 NOTE: A MAXIMUM OF 3 SIGNS ON BUOLDING ARE PERMITTED.
 NO OTHER SIGNS WILL BE PERMITTED ONCE YOU RECEIVE
 APPROVAL OF THIS PERMIT, THAT INCLUDES SIGNAGE ON THE
 WINDOWS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]