Plan Review Details - Permit 19020091
Plan Review Stops For Permit 19020091
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-04-29 Cont ID  
Sent By jduprey Date 2019-04-29 Time 11:49 Rev Time 0.00
Received By jduprey Date 2019-04-29 Time 11:48 Sent To  
Notes
2019-04-29 11:49:16INSPECTIONS MUST BE SCHEDULED WITH THE CITY FOR THE
 SAME TIME OF THE SPECIAL INSPECTOR IS SCHEDULED.
  
 FOR ANY QUESTION CONTACT KEN CONRAD (CHIEF BUILDING
 INSPECTOR) 561-805-6666
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-29 Cont ID  
Sent By jduprey Date 2019-03-29 Time 09:31 Rev Time 0.00
Received By jduprey Date 2019-03-29 Time 09:30 Sent To  
Notes
2019-03-29 09:37:40BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CORRECTED
  
 PREVIOUS COMMENTS:
  
 1A. THE REPAIR DETAILS MUST BE SIGNED BY THE ENGINEER.
 FBC 107 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL
 SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN.
 CODE RULE 61G15-23.001
 WHEN AN ENGINEER MUST SEAL, SIGN AND DATE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS UNDER THE PROVISIONS OF
 SECTION 471.025, F.S., AND SUBSECTION (1) OF THIS RULE,
 AN INDEX SHEET FOR ENGINEERING SPECIFICATIONS AND
 CALCULATIONS MAY BE USED. THE INDEX SHEET MUST BE
 SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS, WITH SUFFICIENT
 INFORMATION ON INDEX SHEET SO THAT THE USER WILL BE
 AWARE OF EACH PORTION OF THE SPECIFICATIONS OR
 CALCULATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS
 RESPONSIBLE.
  
 2. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE. ONLY TWO COPIES WERE PROVIDED
 AND ONLY ONE COPY HAVE THE CONTRACTOR INFORMATION AND
 SIGNATURE.
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
 3. CORRECTED
  
 4. CORRECTED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jduprey Date 2019-02-21 Time 13:52 Rev Time 0.00
Received By jduprey Date 2019-02-21 Time 13:46 Sent To  
Notes
2019-02-21 13:51:40BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ONLY ONE COPY OF THE PROJECT MANUAL WAS SUBMITTED.
 ALL DOCUMENTS MUST BE SUBMITTED DUPLICATED. FBC 107
 1A. THE REPAIR DETAILS MUST BE SIGNED BY THE ENGINEER.
 FBC 107 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL
 SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN.
 CODE RULE 61G15-23.001
  
 2. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
 3. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
 4. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-29 Cont ID  
Sent By jduprey Date 2019-04-29 Time 12:01 Rev Time 0.00
Received By jduprey Date 2019-04-29 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-29 Cont ID  
Sent By jduprey Date 2019-03-29 Time 09:38 Rev Time 0.00
Received By jduprey Date 2019-03-27 Time 14:56 Sent To  
Notes
2019-03-28 14:56:48RESUB ROUTED TO JDUPREY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-21 Cont ID  
Sent By jduprey Date 2019-02-21 Time 13:52 Rev Time 0.00
Received By jduprey Date 2019-02-04 Time 13:03 Sent To  
Notes
2019-02-05 13:03:58BLDG MISC 1

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2019-04-29 Cont ID  
Sent By jduprey Date 2019-04-29 Time 11:48 Rev Time 0.00
Received By jduprey Date 2019-04-29 Time 11:48 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2019-03-29 Cont ID  
Sent By jduprey Date 2019-03-29 Time 09:37 Rev Time 0.00
Received By jduprey Date 2019-03-29 Time 09:37 Sent To  
Notes
2019-03-29 09:38:03BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CORRECTED
  
 PREVIOUS COMMENTS:
  
 1A. THE REPAIR DETAILS MUST BE SIGNED BY THE ENGINEER.
 FBC 107 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL
 SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN.
 CODE RULE 61G15-23.001
 WHEN AN ENGINEER MUST SEAL, SIGN AND DATE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS UNDER THE PROVISIONS OF
 SECTION 471.025, F.S., AND SUBSECTION (1) OF THIS RULE,
 AN INDEX SHEET FOR ENGINEERING SPECIFICATIONS AND
 CALCULATIONS MAY BE USED. THE INDEX SHEET MUST BE
 SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS, WITH SUFFICIENT
 INFORMATION ON INDEX SHEET SO THAT THE USER WILL BE
 AWARE OF EACH PORTION OF THE SPECIFICATIONS OR
 CALCULATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS
 RESPONSIBLE.
  
 2. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE. ONLY TWO COPIES WERE PROVIDED
 AND ONLY ONE COPY HAVE THE CONTRACTOR INFORMATION AND
 SIGNATURE.
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
 3. CORRECTED
  
 4. CORRECTED
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jduprey Date 2019-02-21 Time 13:52 Rev Time 0.00
Received By jduprey Date 2019-02-21 Time 13:51 Sent To  
Notes
2019-02-21 13:52:02BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ONLY ONE COPY OF THE PROJECT MANUAL WAS SUBMITTED.
 ALL DOCUMENTS MUST BE SUBMITTED DUPLICATED. FBC 107
 1A. THE REPAIR DETAILS MUST BE SIGNED BY THE ENGINEER.
 FBC 107 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL
 SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN.
 CODE RULE 61G15-23.001
  
 2. SPECIAL INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE.
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
 3. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
 4. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 CHAPTER 1, SECTION 110.8 OF THE CITY OF WEST PALM
 BEACH, CHAPTER 1 AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 553.79 OF FLORIDA STATUTES; AND CHAPTER
 468, PART XII
  
  