Plan Review Details - Permit 19020044
Plan Review Stops For Permit 19020044
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-03-02 Cont ID  
Sent By fgiaquin Date 2020-03-02 Time 07:24 Rev Time 0.00
Received By fgiaquin Date 2020-03-02 Time 06:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-01-30 Cont ID  
Sent By fgiaquin Date 2020-01-30 Time 08:21 Rev Time 0.00
Received By fgiaquin Date 2020-01-29 Time 06:44 Sent To I
Notes
2020-01-30 08:21:11MUST PASS ZONING FIRST

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By fgiaquin Date 2019-06-20 Time 07:02 Rev Time 0.00
Received By fgiaquin Date 2019-06-20 Time 05:58 Sent To I
Notes
2019-06-20 06:53:22APPROVED WITH PROVISIONS:
  
 BEFORE FINAL INSPECTION,
  
 PROVIDE LOAD CALCULATION.
  
 INFORMATIONAL NOTE: L.E.D. LIGHTING LOADS ARE
 CALCULATED BY AMPERAGE, NOT WATTAGE. NEC 220.18B

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-02 Cont ID  
Sent By fgiaquin Date 2019-03-02 Time 10:03 Rev Time 0.00
Received By fgiaquin Date 2019-03-02 Time 09:10 Sent To Z
Notes
2019-03-02 09:55:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL DESIGNS OVER $125,000 MUST BE DESIGNED
 AND SIGNED/SEALED BY A DESIGN PROFESSIONAL. (ELECTRIAL
 PLAN) FS 471.003(2)(H)(1)
  
 2 DOCUMENTS PREPARED BY A DESIGN PROFESSIONAL MUST BE
 SIGNED/SEALED. (WIND LOAD CALCULATION DOCUMENT). PLEASE
 SEE REQUIREMENTS BELOW FOR SIGNATURE/SEALS:
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 3. VALUE LOW FOR SIZE OF PROJECT. RAISE VALUE. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-03-02 Cont ID  
Sent By fgiaquin Date 2020-03-02 Time 07:24 Rev Time 0.00
Received By fgiaquin Date 2020-02-20 Time 13:57 Sent To  
Notes
2020-02-21 13:57:26RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-31 Cont ID  
Sent By ccarvaja Date 2020-01-31 Time 08:45 Rev Time 0.00
Received By ccarvaja Date 2020-01-24 Time 13:54 Sent To  
Notes
2020-01-27 13:54:24RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-20 Cont ID  
Sent By fgiaquin Date 2019-06-20 Time 07:02 Rev Time 0.00
Received By fgiaquin Date 2019-05-23 Time 13:45 Sent To  
Notes
2019-05-24 13:45:43RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-18 Cont ID  
Sent By cpuell Date 2019-03-18 Time 16:27 Rev Time 0.00
Received By cpuell Date 2019-02-01 Time 15:33 Sent To  
Notes
2019-02-01 15:33:19ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 4 Status P Date 2020-02-25 Cont ID  
Sent By eschneid Date 2020-02-25 Time 10:20 Rev Time 0.50
Received By eschneid Date 2020-02-25 Time 09:55 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2020-01-28 Cont ID  
Sent By eschneid Date 2020-01-28 Time 11:01 Rev Time 0.50
Received By eschneid Date 2020-01-28 Time 10:00 Sent To E
Notes
2020-01-28 11:01:56FAILED
  
 1) REPEAT COMMENT: DRAWING E1.0 DOES NOT MATCH THE SITE
 LAYOUT SHOWN ON THE SURVEY OR ON DRAWING E1.1. ALL
 PLANS MUST SHOW THE SAME CONDITION.
  
 2) UPDATED COMMENT: THE PLANS STATE THAT THE POLES WILL
 BE LOCATED FIVE (5) FEET FROM THE PROPERTY LINES.
  
 A. THE POLES ALONG OKEECHOBEE BOULEVARD ARE SHOWN
 WITHIN THE FIVE (5) FOOT WIDE LANDSCAPE BUFFER;
 THEREFORE, THESE POLES ARE NOT LOCATED FIVE FEET FROM
 THE PROPERTY LINE. THE PLANS MUST CLEARLY SHOW THE
 POLES OUTSIDE OF THE FIVE (5) FOOT SETBACK. IF THE
 POLES ARE NOT ACCURATELY DEPICTED WITH A FIVE (5) FOOT
 SETBACK THEY WILL BE INSTALLED IN THE WRONG LOCATION.
 THE NOTE ON THE PLANS IS NOT SUFFICIENT.
  
 B. THE POLES ALONG THE ALLEY CONTINUE TO BE SHOWN IN
 THE ALLEY. THE PROPERTY LINE IS THE EDGE OF PAVEMENT AT
 THE FENCE. THE POLES NEED TO BE CLEARLY SHOWN FIVE (5)
 FEET INSIDE THE PROPERTY LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-06-19 Cont ID  
Sent By eschneid Date 2019-06-19 Time 13:31 Rev Time 0.25
Received By eschneid Date 2019-06-19 Time 13:31 Sent To E
Notes
2019-06-19 13:47:11FAILED
  
 1) THANK YOU FOR PROVIDING THE SURVEY. THE SITE PLAN -
 ELECTRICAL DOES NOT MATCH THE SITE LAYOUT SHOWN ON THE
 SURVEY. THE SITE PLAN BASE MUST MATCH THE SURVEY AND
 THEN THE LIGHTS NEED TO BE PLACED TO AVOID THE TREES.
  
 2) REPEAT COMMENT: THE PLANS STATE THAT THE POLES WILL
 BE REMOVED AND REPLACED. ALL NEW POLES ARE REQUIRED TO
 MEET THE FIVE (5) FOOT SETBACK REQUIRED IN THE GENERAL
 COMMERCIAL ZONING DISTRICT. PROVIDE THE SETBACK
 DIMENSIONS FOR ALL THE PERIMETER POLES ON THE SITE PLAN
 SHOWING COMPLIANCE WITH THE FIVE (5) FOOT SETBACK
 REQUIREMENT.
  
 3) THE SITE PLAN SHOWS THE NORTHERNMOST POLE TYPE E
 ALONG CONGRESS AVENUE IN CONFLICT WITH AN EXISTING
 TREE, WHEN COMPARED TO THE SURVEY.
  
 4) THE SITE PLAN SHOWS ALL OF THE POLES ALONG THE
 NORTHERN PROPERTY LINE IN THE ALLEY, WHEN COMPARED TO
 THE SURVEY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-03-18 Cont ID  
Sent By eschneid Date 2019-03-18 Time 12:50 Rev Time 0.25
Received By eschneid Date 2019-03-18 Time 12:50 Sent To PC
Notes
2019-03-18 12:56:36FAILED
  
 1) PROVIDE 2 COPIES OF A RECENT SURVEY, LESS THAN ONE
 YEAR OLD. THE SURVEY MUST SHOW THE LOCATION OF TREES
 AND PALMS.
  
 2) THE PLANS STATE THAT THE POLES WILL BE REMOVED AND
 REPLACED. ALL NEW POLES ARE REQUIRED TO MEET THE FIVE
 (5) FOOT SETBACK REQUIRED IN THE GENERAL COMMERCIAL
 ZONING DISTRICT. PROVIDE THE SETBACK DIMENSIONS FOR ALL
 THE PERIMETER POLES ON THE SITE PLAN SHOWING COMPLIANCE
 WITH THE FIVE (5) FOOT SETBACK REQUIREMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]