Plan Review Details - Permit 19020031
Plan Review Stops For Permit 19020031
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-25 Cont ID  
Sent By pvalenti Date 2019-05-25 Time 09:45 Rev Time 0.00
Received By pvalenti Date 2019-05-25 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-20 Cont ID  
Sent By pvalenti Date 2019-04-20 Time 11:00 Rev Time 0.00
Received By pvalenti Date 2019-04-19 Time 13:32 Sent To  
Notes
2019-04-20 13:36:51***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND REVIEW DENIED:
  
 1. WORK COMPLETED WITHOUT THE BENEFIT OF PERMITS. THE
 SHEET A100 SHOWS THE FRONT ENTRY SET OF DOORS AS A PAIR
 OF INSWING DOORS. THE CHANGE OF OCCUPANCY PERMIT
 10070543 SHOWS THESE DOORS AS OUTSWING DOORS. THERE WAS
 ALSO A MISC. PERMIT FILED UNDER THE ADDRESS OF 339
 WESTMINSTER PL. PERMIT NUMBER 08040046, NOA 07?0522.05
 HARMAN WINDOWS AND DOORS FOR OUTSWING GLAZED WOOD
 FRENCH DOORS, L. M. IMPACT TESTED. PLEASE PROVIDE THE
 PRODUCT TESTING FOR THESE DOORS FOR INSWING USE.
 FAIL: (AS PER N.O.A. # 07-0522.05, THE ENTRY DOORS MUST
 BE SHOWN ON THE PLANS WITH AN OUTSWING)
  
 2. OK (2017 FBC B TYPE VB ACKNOWLEDGED BY DESIGN
 PROFESSIONAL)
 3. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL)
 4. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL)
 5.A. OK (LEVEL III IDENTIFIED ON PLANS/ACKNOWLEDGED BY
 DESIGN PROFESSIONAL)
 5.B. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL)
 6.A., B., & C.
 FAIL: (ALL PRODUCT APPROVALS FOR GLAZING, WINDOWS,
 DOORS, MULLIONS, WALL LOUVERS, ROOFING PRODUCTS &
 ASSEMBLIES NEED TO BE REVIEW STAMPED/SIGNED BY DESIGN
 PROFESSIONAL & SUBMITTED TO THE CITY FOR APPROVAL)
  
 6.D. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL)
 7. SHEET A?101 THE FLOOR PLAN AND SHEET A?500 THE DOOR
 SCHEDULE WILL NEED TO MEET THE REQUIREMENT OF THE 2017
 FBC?B SECTION 1010.1.1 SIZE OF DOORS. THE REQUIRED
 CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR
 THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM
 CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES. THE DOORS IDENTIFIED AS 102, 108 & 110 DO NOT
 MEET THIS REQUIREMENT.
 FAIL: (IT APPEARS THAT THE SIZE OF DOOR 102 HAS NOT
 BEEN ADJUSTED ON THE DOOR SCHEDULE)
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-19 Cont ID  
Sent By jwitmer Date 2019-02-19 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2019-02-13 Time 09:19 Sent To  
Notes
2019-02-19 11:22:092017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020031
 ADD: 3020 S DIXIE/ AKA: 339 WESTMINSTER PL.
 CONT: TIM GIVENS BUILDING & REMODELING
 TEL: 561-533-5828
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 19/ 2019
 ACTION: DENIED
  
 1) WORK COMPLETED WITHOUT THE BENEFIT OF PERMITS. THE
 SHEET A100 SHOWS THE FRONT ENTRY SET OF DOORS AS A PAIR
 OF INSWING DOORS. THE CHANGE OF OCCUPANCY PERMIT
 10070543 SHOWS THESE DOORS AS OUTSWING DOORS. THERE WAS
 ALSO A MISC. PERMIT FILED UNDER THE ADDRESS OF 339
 WESTMINSTER PL. PERMIT NUMBER 08040046, NOA 07-0522.05
 HARMAN WINDOWS AND DOORS FOR OUTSWING GLAZED WOOD
 FRENCH DOORS, L. M. IMPACT TESTED. PLEASE PROVIDE THE
 PRODUCT TESTING FOR THESE DOORS FOR INSWING USE.
  
 2017 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, OR MEANS OF EGRESS.
  
 2) THE LIFE SAFETY SHEET LS100 UNDER THE HEADING OF
 CONSTRUCTION TYPE LIST THE CONSTRUCTION TYPE AS TYPE 5
 UNSPRINKLERED. PLEASE IDENTIFY IF THE TERM TYPE V
 CONSTRUCTION IS THE TERM USED BEFORE AND IN THE 2001
 FBC WHERE WE HAD TYPE VI CONSTRUCTION OR ARE YOU USING
 THE TERM SINCE IN THE 2004 FBC WHERE THE STRUCTURE IS
 LISTED V-A 1 HOUR PROTECTED OR V-B UNPROTECTED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) PLEASE NOTE THAT THE LIFE SAFETY PLAN LS100 SHOWS 3
 EXITS FROM THE BUILDING. ONLY ONE MEANS OF EGRESS IS
 REQUIRED, SINCE THE FRONT ENTRY TO THE FURTHEST POINT
 IN THE BUILDING OFFICE 102 OR THE KITCHEN IS UNDER 50
 FEET. IN THE 2017 FBC-B TABLE 1006.2.1 COMMON PATH OF
 TRAVEL FOR A BUSINESS OCCUPANCY/ UNSPRINKLERED/ AND AN
 OCCUPANT LOAD OF <49 THE COMMON PATH OF TRAVEL IS 75
 FEET.
 SIGNAGE WILL BE REQUIRED AT THE EXITS THAT ARE NOT
 ACCESSIBLE TO WHERE THE ACCESSIBLE EXIT IS LOCATED.
  
 2017 FBC-ACCESSIBILITY CODE SECTIONS: 216.4 MEANS OF
 EGRESS. SIGNS FOR MEANS OF EGRESS SHALL COMPLY WITH
 216.4. 216.4.1 EXIT DOORS. DOORS AT EXIT PASSAGEWAYS,
 EXIT DISCHARGE, AND EXIT STAIRWAYS SHALL BE IDENTIFIED
 BY TACTILE SIGNS COMPLYING WITH 703.1, 703.2, AND
 703.5.
 216.6 ENTRANCES.
  
 WHERE NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES
 COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT
 INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING
 WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT
 COMPLY WITH 404.
  
 4) SHEET D100 INDICATES WITH NOTES 13 & 14 THE REMOVAL
 OF THE CHIMNEY, ROOF TILE, PLYWOOD AND ROTTEN WOOD
 TRUSSES, REPLACE AS NECESSARY. PLEASE NOTE COMPLIANCE
 WITH THE 2017 FBC-EXISTING BUILDING CODE SECTION
 706.1.1. NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF
 AREA OR ROOF SECTION OF ANY EXISTING BUILDING OR
 STRUCTURE SHALL BE REPAIRED, REPLACED OR RECOVERED IN
 ANY 12-MONTH PERIOD UNLESS THE ENTIRE EXISTING ROOFING
 SYSTEM OR ROOF SECTION IS REPLACED TO CONFORM TO
 REQUIREMENTS OF THIS CODE.
  
 5A) SHEET D100 INDICATES UNDER THE EXISTING BUILDING
 CODE A LEVEL 2 ALTERATION IS BEING DECLARED. PLEASE
 REVIEW THE CLASSIFICATION OF WORK FOR A LEVEL 3
 ALTERATION, IT WOULD APPEAR THAT YOU HAVE MET THAT
 THRESHOLD. EXISTING BUILDING CODE 505.2 APPLICATION.
 LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTERS 7 AND 8 FOR LEVEL 1 AND 2 ALTERATIONS,
 RESPECTIVELY, AS WELL AS THE PROVISIONS OF CHAPTER 9.
  
 5B) PLEASE SHOW COMPLIANCE WITH THE EXISTING BUILDING
 CODE SECTION 907.4.2 SUBSTANTIAL STRUCTURAL ALTERATION.
 WHERE MORE THAN 30 PERCENT OF THE TOTAL FLOOR AND ROOF
 AREAS OF THE BUILDING OR STRUCTURE HAVE BEEN OR ARE
 PROPOSED TO BE INVOLVED IN STRUCTURAL ALTERATION WITHIN
 A 5-YEAR PERIOD, THE EVALUATION AND ANALYSIS SHALL
 DEMONSTRATE THAT THE LATERAL LOAD-RESISTING SYSTEM OF
 THE ALTERED BUILDING OR STRUCTURE COMPLIES WITH THE
 FLORIDA BUILDING CODE, BUILDING FOR WIND LOADING.
  
 6A) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS.
 (C) WALL LOUVERS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES.
  
 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 6C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6D) THRESHOLDS. 2017 ACCESS. CODE 404.2.5. THRESHOLDS,
 IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 7) SHEET A-101 THE FLOOR PLAN AND SHEET A-500 THE DOOR
 SCHEDULE WILL NEED TO MEET THE REQUIREMENT OF THE 2017
 FBC-B SECTION 1010.1.1 SIZE OF DOORS. THE REQUIRED
 CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR
 THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM
 CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS
 WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE
 OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES. THE DOORS IDENTIFIED AS 102, 108 & 110 DO NOT
 MEET THIS REQUIREMENT.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By jleahy Date 2019-05-28 Time 08:17 Rev Time 0.00
Received By jleahy Date 2019-05-28 Time 08:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-02 Cont ID  
Sent By jleahy Date 2019-04-02 Time 16:57 Rev Time 0.00
Received By jleahy Date 2019-04-02 Time 16:57 Sent To  
Notes
2019-04-02 16:58:57PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
  
 NOTHING IN A COMMERCIAL CALCULATION HAS 10,000 AT 100%
 AND REMAINDER AT 40% THAT IS A RESIDENTIAL CALCULATION

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jleahy Date 2019-02-21 Time 15:11 Rev Time 0.00
Received By jleahy Date 2019-02-21 Time 15:11 Sent To  
Notes
2019-02-21 15:12:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 LOAD CALCULATION IS FOR A RESIDENCE?
  
 COMMERCIAL LOAD CALC REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-14 Cont ID  
Sent By pleduc Date 2019-05-14 Time   Rev Time 0.00
Received By pleduc Date 2019-05-14 Time 15:40 Sent To  
Notes
2019-05-14 15:40:46THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS NO INDICATIONS OF EXISTING/NEW HADNRAIL
 DETAIL.
  
 HANDRAILS SHALL COMPLY WITH NFPA 101, CH 7, -
  
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT
 THE SIDES OF
 STAIRS BY 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS
 SHALL APPLY:
 (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN
 30 IN. (760
 MM) OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (2) FOR EXISTING STAIRS, HANDRAILS SHALL MEET THE
 FOLLOWING CRITERIA:
 (A) THEY SHALL BE PROVIDED WITHIN 44 IN. (1120 MM) OF
 ALL
 PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (B) SUCH STAIRS SHALL NOT HAVE THEIR EGRESS CAPACITY
 ADJUSTED
 TO A HIGHER OCCUPANT LOAD THAN PERMITTED BY THE
 CAPACITY
 FACTOR IN TABLE 7.3.3.1 IF THE STAIR?S CLEAR WIDTH
 BETWEEN
 HANDRAILS EXCEEDS 60 IN. (1525 MM).
  
 PLEASE REVIEW AND ENSURE COMPLIANCE. FIRE INSPECTOR
 WILL COMFIRM ON FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-19 Cont ID  
Sent By pleduc Date 2019-03-19 Time   Rev Time 0.00
Received By pleduc Date 2019-03-19 Time 10:24 Sent To  
Notes
2019-03-19 10:26:18THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS NO INDICATIONS OF EXISTING/NEW HADNRAIL
 DETAIL.
  
 HANDRAILS SHALL COMPLY WITH NFPA 101, CH 7, -
  
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT
 THE SIDES OF
 STAIRS BY 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS
 SHALL APPLY:
 (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN
 30 IN. (760
 MM) OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (2) FOR EXISTING STAIRS, HANDRAILS SHALL MEET THE
 FOLLOWING CRITERIA:
 (A) THEY SHALL BE PROVIDED WITHIN 44 IN. (1120 MM) OF
 ALL
 PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (B) SUCH STAIRS SHALL NOT HAVE THEIR EGRESS CAPACITY
 ADJUSTED
 TO A HIGHER OCCUPANT LOAD THAN PERMITTED BY THE
 CAPACITY
 FACTOR IN TABLE 7.3.3.1 IF THE STAIR?S CLEAR WIDTH
 BETWEEN
 HANDRAILS EXCEEDS 60 IN. (1525 MM).
  
 PLEASE REVIEW AND ENSURE COMPLIANCE. FIRE INSPECTOR
 WILL COMFIRM ON FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By pleduc Date 2019-02-05 Time   Rev Time 0.00
Received By pleduc Date 2019-02-05 Time 11:44 Sent To  
Notes
2019-02-05 12:17:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A000 - THERE IS AN INDICATION OF BUSINESS
 OCCUPANCY FROM THE FLORIDA BUILDING CODE. WHAT IS THE
 OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE
 PREVENTION CODE, 6TH ED.
  
 PLEASE PROVIDE WHAT THIS OCCUPANCY FUNCTIONS AS, WHAT
 TYPE OF BUSINESS AND ACTIVITIES OCCUR WITHIN THE
 OCCUPANCY, HOURS OF OPERATION, WILL IT BE A MIXED OR
 SEPARATED OCCUPANCY?
  
 CHAPTER 6 CLASSIFICATION OF OCCUPANCY AND HAZARD OF
 CONTENTS
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR
 STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL
 BE CLASSIFIED IN
 ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY
 CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A
 QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL
 CASE.
  
 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY. AN OCCUPANCY
 (1) USED
 FOR A GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION,
 WORSHIP,
 ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING
 TRANSPORTATION, OR
 SIMILAR USES; OR (2) USED AS A SPECIAL AMUSEMENT
 BUILDING, REGARDLESS OF
 OCCUPANT LOAD.
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6
  
  
  
 PLEASE BE SPECIFIC AS POSSIBLE AND INCLUDE SEPCIFIC
 CODE REFERENCES.
  
  
  
 2) SHEET LS100 - A BILLARD ROOM, LOUNGE AND BAR AREAS
 ARE INDICATED ON THE FLOOR PLAN. THESE AREAS ARE
 ASSEMBLY AREAS THAT APPEAR TO BE MORE THAN INCIDENTAL
 USE FOR THE BUSINESS OFFICE OCCUPANCY AS INDICATED PER
 # 1 ABOVE.
  
 IT APPEARS THA THE BUSINESS OFFICE IS INCIDENTAL TO THE
 ASSEMBLY USE.
  
 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY,
 AREAS USED AS
 FOLLOWS SHALL BE PERMITTED TO BE CONSIDERED PART OF THE
 PREDOMINANT
 OCCUPANCY AND SHALL BE SUBJECT TO THE PROVISIONS OF THE
 CODE THAT APPLY
 TO THE PREDOMINANT OCCUPANCY:
 (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE
 (2) *NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER
 THAN THAT
 ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY THRESHOLD
 (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR
 FOR CUSTOMARY
 NON-HAZARDOUS USES NECESSARY FOR TRANSACTING THE
 PRINCIPAL
 BUSINESS IN STORAGE AND INDUSTRIAL OCCUPANCIES NEED NOT
 BE
 SEPARATED FROM THE PRINCIPAL USE.
 (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING
 LOW HAZARD
 PRODUCTS IN ACCORDANCE WITH SUBDIVISION 6.2.2 NEED NOT
 BE
 SEPARATED BY FIRE-RESISTANT CONSTRUCTION FROM THE
 OCCUPANCIES TO
 WHICH THEY ARE ACCESSORY.
 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS
 REQUIRED BY TABLE
 508.2.5 OF THE FLORIDA BUILDING CODE WHERE TABLE
 508.2.5 PERMITS AN
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE
 BARRIER, THE INCIDENTAL
 USE AREA SHALL BE SEPARATED BY CONSTRUCTION CAPABLE OF
 RESISTING THE
 PASSAGE OF SMOKE.
 6.1.14.1.4 THE FOLLOWING ACCESSORY OCCUPANCIES SHALL
 NOT BE REQUIRED TO
 BE SEPARATED FROM THE PRIMARY OCCUPANCY AS REQUIRED IN
 6.1.14.4:
 (1) A KITCHEN IN AN ASSEMBLY OCCUPANCY DOES NOT
 CONSTITUTE A MIXED
 OCCUPANCY.
 (2) ACCESSORY USES IN INDUSTRIAL AND STORAGE
 OCCUPANCIES AS OTHERWISE
 PROVIDED IN 6.1.14.1.3(1)
 (3) ROOMS OR SPACES USED FOR CUSTOMARY STORAGE OF
 NON-HAZARDOUS
 MATERIALS IN ASSEMBLY, BUSINESS, EDUCATIONAL,
 INDUSTRIAL,
 MERCANTILE, HOTEL AND DORMITORY, AND APARTMENT
 OCCUPANCIES WHICH
 IN AGGREGATE DO NOT EXCEED 10% OF THE MAJOR FLOOR AREA
 IN WHICH
 THEY ARE LOCATED. PROTECTION FROM HAZARDS SHALL BE AS
 OTHERWISE
 PROVIDED IN THE SPECIFIC OCCUPANCY CHAPTER.
  
 BASED ON WHAT IS RECEIVED ON # 1 ABOVE, NEITHER
 ASSEMBLEY NOR BUSINESS APPLY.
  
 PLEASE ADDRESS # 1 ABOVE AND CORRECT THE OCCUPANCY
 CLASSIFICATION AS APPICABLE PER THE FLORIDA FIRE
 PREVENTION CODE, 6TH ED.
  
  
  
 3) ALL SHEETS A - BASED ON # 1 ABOVE THERE MAY BE
 REVISIONS NECESSARY TO COMPLY WITH APPLICABLE CODES.
  
 I.E. DOOR HARDWARE, LOCKS (PER THE APPLICABLE
 OCCUPANCY), FIRE SPRINKLER AND FIRE ALARM (PER THE
 APPLICABLE OCCUPANCY), FLOOR AND CEILING FINISHES, ETC.
  
  
  
 4) A SHEETS - THERE ARE NO INDICATIONS OF COMPLAINCE
 WITH THE STAIRS AND/OR RAILINGS INDICATED.
  
 THE STAIRS AND RAILINGS SHALL COMPLY WITH NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 7.1 GENERAL.
 7.1.1* APPLICATION. MEANS OF EGRESS FOR BOTH NEW AND
 EXISTING
 BUILDINGS SHALL COMPLY WITH THIS CHAPTER. (SEE ALSO
 4.5.3.)
  
 7.2 MEANS OF EGRESS COMPONENTS.
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE
 SPECIAL REQUIREMENTS OF 7.2.2, UNLESS OTHERWISE
 SPECIFIED IN
 7.2.2.1.2.
  
 PLEASE PROVIDE THE APPLICABLE DETAILS IN COMPLIANCE.
  
  
  
  
 5) SHEET LS100 - IS DOES NOT APPEAR THAT THE REAR EXIT
 LEADS TO A PUBLIC WAY.
  
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN
 7.7.1.2 THROUGH 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT
 DISCHARGE SHALL BE OF THE REQUIRED WIDTH AND SIZE TO
 PROVIDE ALL
 OCCUPANTS WITH A SAFE ACCESS TO A PUBLIC WAY.
  
 PLEASE PROVIDE A SITE PLAN SHOWING COMPLAINCE WITH NFPA
 101, CHAPTER 7 MEANS OF EGRESS.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-05-10 Cont ID  
Sent By aborngra Date 2019-05-10 Time 15:04 Rev Time 0.00
Received By aborngra Date 2019-05-10 Time 15:02 Sent To PC
Notes
2019-05-10 15:04:15THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
  
 1. ALL WINDOWS AND DOORS SHALL HAVE CLEAR GLASS OR
 LOW-E GLASS.
 2. ALL WINDOWS LABELED AS SINGLE-HUNG WINDOWS SHALL BE
 DOUBLE-HUNG WINDOWS.
 3. ALL WINDOWS REPLACING AN EXISTING WINDOW SHALL BE
 SIZED TO FIT THE ORIGINAL WINDOW FRAME SIZE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2019-03-25 Cont ID  
Sent By aborngra Date 2019-03-25 Time 08:26 Rev Time 0.00
Received By aborngra Date 2019-03-25 Time 08:26 Sent To PC
Notes
2019-03-25 08:26:39THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. THE CHIMNEY IS A CHARACTER DEFINING FEATURE OF THE
 STRUCTURE. THE PROPOSED PLANS CALL FOR ITS REMOVAL.
 PLEASE REVISE PLANS TO MAINTAIN THE CHIMNEY AS IS.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By aborngra Date 2019-03-13 Time 10:48 Rev Time 0.00
Received By aborngra Date 2019-03-13 Time 10:47 Sent To PC
Notes
2019-03-13 10:48:53THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. THE CHIMNEY IS A CHARACTER DEFINING FEATURE OF THE
 STRUCTURE. THE PROPOSED PLANS CALL FOR ITS REMOVAL.
 PLEASE REVISE PLANS TO MAINTAIN THE CHIMNEY AS IS.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-28 Cont ID  
Sent By hmoser Date 2019-05-28 Time 15:22 Rev Time 0.00
Received By hmoser Date 2019-05-08 Time 11:12 Sent To  
Notes
2019-05-09 11:12:18B29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-20 Cont ID  
Sent By pvalenti Date 2019-04-20 Time 13:05 Rev Time 0.00
Received By pvalenti Date 2019-03-14 Time 11:35 Sent To  
Notes
2019-03-15 11:35:25B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-13 Cont ID  
Sent By cpuell Date 2019-03-13 Time 13:13 Rev Time 0.00
Received By cpuell Date 2019-02-01 Time 14:49 Sent To  
Notes
2019-02-01 14:49:41B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-02-19 Cont ID  
Sent By jwitmer Date 2019-02-19 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2019-02-13 Time 09:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By hmoser Date 2019-05-28 Time 14:25 Rev Time 0.00
Received By hmoser Date 2019-05-28 Time 14:24 Sent To I
Notes
2019-05-28 14:24:47 
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-11 Cont ID  
Sent By ccole Date 2019-04-11 Time 14:57 Rev Time 0.00
Received By ccole Date 2019-04-11 Time 13:10 Sent To  
Notes
2019-04-11 15:00:422ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19020031
 4/11/19
  
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT
 ADDRESSED- NO CORRECTIONS WERE MADE TO THE PLANS AND NO
 RESPONSE NARRATIVE ADDRESSING THE COMMENTS WAS
 SUBMITTED.
  
 PLEASE REVIEW THE COMMENTS LISTED BELOW AND COMPLY.
  
  
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020031
 3/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100: PLEASE PROVIDE A SCOPE OF WORK OUTLINE
 ON THE PLAN- SECTION 107.2.1 WPB.
  
 2) M100: BASED ON THE ARCHITECTURAL PLANS, THE PROPOSED
 PROJECT APPEARS TO BE A CHANGE OF OCCUPANCY, OR A LEVEL
 III ALTERATION AS INDICATED ON LS100. REFER TO SECTION
 809.2 FBC-17 EXISTING BUILDING CODE AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 3) M100: THE PLAN APPEARS TO SHOW A NEW 5-TON AC SYSTEM
 WITH THE AIR HANDLER BEING INSTALLED IN THE ATTIC.
 PLEASE SEE SECTION C403.2.9.6 FBC EC WHICH PROHIBITS
 INSTALLATION OF AIR HANDLERS IN ATTICS.
  
 3) M100: A DUCT SMOKE DETECTORS IS REQUIRED IN THE
 SUPPLY AIR SYSTEMS OF THE NEW 5-TON AC SYSTEM PER
 SECTION 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE
 APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE
 THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS
 OF SUPPLY AIR.
  
 4) M100: PROVIDE THE DIMENSIONS OF THE RETURN GRILLS IN
 THE OFFICES- SECTION 603 FBC M.
  
 5) M100: PROVIDE AIR DEVICE AND AIR DISTRIBUTION
 SCHEDULES THAT INDICATE THE MAKES AND MODELS OF THE
 DIFFUSERS AND GRILLS, AND TYPE OF DUCTWORK TO BE
 INSTALLED- SECTION 603.
  
 6) M100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FLOOR GRILLS IN COMPLIANCE WITH SECTION 603.18.1 FBC M.
 THE SPECS MUST INDICATE THE GRILLS SHALL RESIST
 STRUCTURAL FAILURE AS OUTLINED IN THE SECTION.
  
 7) M100: PROVIDE A BATH AND TOILET ROOM EXHAUST FAN
 SCHEDULE, AND SHOW THE EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS- TABLE 403.3.1.1 FBC M.
  
 8) M100: PROVIDE EQUIPMENT SCHEDULES AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR ANY COOKING
 APPLIANCES TO BE INSTALLED IN THE KITCHEN AND BAR-
 SECTION 917 FBC M. PLEASE IDENTIFY THE LOCATIONS OF THE
 APPLIANCES ON THE PLAN AND PRPOVIDE LOCAL EXHAUST
 SYSTEMS (HOODS) WHERE REQUIRED. PLEASE NOTE THAT
 SEPARATE PERMITS ARE REUIRED FOR GREASE EXHAUST
 SYSTEMS- SECTION 107.2.1 WPB.
  
 9) M100: EXHAUST VENTILATION IS REQUIRED FOR THE
 KITCHEN AT A RATE OF 25 CFMS CONTINUOUSLY OR 100 CFMS
 INTERMITTENTLY IN ACCORDANCE WITH TABLE 403.3.1.1 FBC
 M. PLEASE NOTE FOOTNOTE B PROHIBITS RECIRCULATION OF
 AIR FROM THE KITCHEN TO OTHER OCCUPIED ROOMS AND
 SPACES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-03-01 Cont ID  
Sent By ccole Date 2019-03-01 Time 12:35 Rev Time 0.00
Received By ccole Date 2019-02-28 Time 12:10 Sent To  
Notes
2019-03-01 12:57:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020031
 3/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100: PLEASE PROVIDE A SCOPE OF WORK OUTLINE
 ON THE PLAN- SECTION 107.2.1 WPB.
  
 2) M100: BASED ON THE ARCHITECTURAL PLANS, THE PROPOSED
 PROJECT APPEARS TO BE A CHANGE OF OCCUPANCY, OR A LEVEL
 III ALTERATION AS INDICATED ON LS100. REFER TO SECTION
 809.2 FBC-17 EXISTING BUILDING CODE AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 3) M100: THE PLAN APPEARS TO SHOW A NEW 5-TON AC SYSTEM
 WITH THE AIR HANDLER BEING INSTALLED IN THE ATTIC.
 PLEASE SEE SECTION C403.2.9.6 FBC EC WHICH PROHIBITS
 INSTALLATION OF AIR HANDLERS IN ATTICS.
  
 3) M100: A DUCT SMOKE DETECTORS IS REQUIRED IN THE
 SUPPLY AIR SYSTEMS OF THE NEW 5-TON AC SYSTEM PER
 SECTION 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE
 APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE
 THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS
 OF SUPPLY AIR.
  
 4) M100: PROVIDE THE DIMENSIONS OF THE RETURN GRILLS IN
 THE OFFICES- SECTION 603 FBC M.
  
 5) M100: PROVIDE AIR DEVICE AND AIR DISTRIBUTION
 SCHEDULES THAT INDICATE THE MAKES AND MODELS OF THE
 DIFFUSERS AND GRILLS, AND TYPE OF DUCTWORK TO BE
 INSTALLED- SECTION 603.
  
 6) M100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FLOOR GRILLS IN COMPLIANCE WITH SECTION 603.18.1 FBC M.
 THE SPECS MUST INDICATE THE GRILLS SHALL RESIST
 STRUCTURAL FAILURE AS OUTLINED IN THE SECTION.
  
 7) M100: PROVIDE A BATH AND TOILET ROOM EXHAUST FAN
 SCHEDULE, AND SHOW THE EXHAUST DUCT RUNS AND
 TERMINATION LOCATIONS- TABLE 403.3.1.1 FBC M.
  
 8) M100: PROVIDE EQUIPMENT SCHEDULES AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR ANY COOKING
 APPLIANCES TO BE INSTALLED IN THE KITCHEN AND BAR-
 SECTION 917 FBC M. PLEASE IDENTIFY THE LOCATIONS OF THE
 APPLIANCES ON THE PLAN AND PRPOVIDE LOCAL EXHAUST
 SYSTEMS (HOODS) WHERE REQUIRED. PLEASE NOTE THAT
 SEPARATE PERMITS ARE REUIRED FOR GREASE EXHAUST
 SYSTEMS- SECTION 107.2.1 WPB.
  
 9) M100: EXHAUST VENTILATION IS REQUIRED FOR THE
 KITCHEN AT A RATE OF 25 CFMS CONTINUOUSLY OR 100 CFMS
 INTERMITTENTLY IN ACCORDANCE WITH TABLE 403.3.1.1 FBC
 M. PLEASE NOTE FOOTNOTE B PROHIBITS RECIRCULATION OF
 AIR FROM THE KITCHEN TO OTHER OCCUPIED ROOMS AND
 SPACES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-10 Cont ID  
Sent By gjohnson Date 2019-04-10 Time 09:03 Rev Time 0.00
Received By gjohnson Date 2019-04-10 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-01 Cont ID  
Sent By gjohnson Date 2019-03-01 Time 11:14 Rev Time 0.00
Received By gjohnson Date 2019-03-01 Time 10:51 Sent To  
Notes
2019-03-01 11:14:401ST REVIEW: 19020031
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 2. PROVIDE WATER ISOMETRIC. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. SHOW LOCATION OF WATER HEATER ON PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 4. BAR SINK MISSING FROM SANITARY ISOMETRIC PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 5. PLEASE INDICATE ON PLAN THE KITCHEN SHALL COMPLY
 WITH FBC ACC 804
  
 6. A GREASE TRAP IS REQUIRED ON THE KITCHEN SINK. PER
 FBC PL 1003.3.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-25 Cont ID  
Sent By aborngra Date 2019-03-25 Time 08:26 Rev Time 0.00
Received By aborngra Date 2019-03-25 Time 08:25 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-13 Cont ID  
Sent By aborngra Date 2019-03-13 Time 10:47 Rev Time 0.00
Received By aborngra Date 2019-03-13 Time 10:47 Sent To PC
Notes
***NONE***