Plan Review Details - Permit 19011312
Plan Review Stops For Permit 19011312
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-17 Cont ID  
Sent By pvalenti Date 2019-06-17 Time 11:19 Rev Time 0.00
Received By pvalenti Date 2019-06-17 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-16 Cont ID  
Sent By pvalenti Date 2019-04-16 Time 10:33 Rev Time 0.00
Received By pvalenti Date 2019-04-16 Time 07:57 Sent To  
Notes
2019-04-16 08:19:20***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 WPB A = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE
  
 2ND REVIEW DENIED:
  
 THE ITEMS FROM THE FIRST REVIEW HAVE BEEN ADDRESSED,
 HOWEVER DURING THE 2ND REVIEW THE FOLLOWING (2) ITEMS
 HAVE BEEN FOUND THAT NEED TO BE ADDRERSSED:
  
 1. FBC B 1612.4; THE PLANS NEED TO BE REVISED TO
 INCLUDE (COASTAL A) FLOOD DESIGN CRITERIA.
  
 2. FBC B 107.3.4/WPB A 107.3.4; THE PLANS NEED TO BE
 PREPARED AND APPROVED BY THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE OF PROJECT (THE (1) STRUCTURAL
 ENGINEER OF RECORD). IN ADDITION TO THE SIGNING AND
 SEALING OF PLANS, THE STRUCTURAL ENGINEER OF RECORD
 NEEDS TO REVIEW (STAMP) AND SIGN
 ALL DELEGATED STRUCTURAL WORK AS WELL.
  
 NOTE: AS PER PRIOR COMMUNICATIONS WITH CHIEF PLANS
 EXAMINER (SAMANTHA HILL) FEEL FREE TO RESPOND BY EMAIL:
 [email protected] AND [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-11 Cont ID  
Sent By jwitmer Date 2019-02-11 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2019-02-11 Time 14:06 Sent To  
Notes
2019-02-11 15:24:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011312
 ADD: 201 N FLAGLER DR.
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: 561-204-4323
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. FEB. 11/2019
 ACTION: DENIED
  
 DESCRIPTION OF WORK FOR THIS PERMIT: PLEASE NOTE THIS
 PERMIT IS FOR STRUCTURAL FOUNDATION & ELECTRICAL
 SERVICE FEEDS FOR LIGHTING.
  
 1A) SHEET S0.0 UNDER THE HEADING OF GENERAL NOTES
 INDICATES THESE PLANS WERE DESIGNED UNDER THE 2014 FBC.
 PLEASE NOTE THE 6TH EDITION OR THE 2017 FBC-B WAS
 ADOPTED STATEWIDE ON DEC. 30/ 2017. PLEASE UPDATE THE
 PLANS. PLEASE NOTE THE 6TH EDITION OR THE 2017 FBC-B
 WAS ADOPTED STATEWIDE ON DEC. 30/ 2017. PLEASE UPDATE
 THE PLANS.
  
 1B) THE WPB.LO.1 (1OF 4 SHEETS) ALSO INDICATES THE
 PLANS WERE DESIGNED UNDER THE 2014 FBC.
  
 2) SHEET S0.0 UNDER THE HEADING FOUNDATIONS INDICATES
 THERE IS A SOILS REPORT BY ARDAMAN & ASSOCIATES DATED
 10/05/17. PLEASE SUBMIT EITHER AN ORIGINAL PAPER SIGNED
 AND SEALED REPORT, OR IN THE NEXT ELECTRONIC UPLOAD AN
 ELECTRONIC VERSION OF THE SOILS REPORT WITH ELECTRONIC
 SIGNATURE.
  
  
 3) THERE IS A DISCREPANCY IN THE WIND DESIGN VALUES
 GIVEN, SHEET S0.0 INDICATES THE WIND DESIGN VALUE OF
 170 VULT AND EXPOSURE D WHEREAS THE WPB PANELS WELDED
 (4) SHEETS INDICATE REV. 1 SHEET THE WIND DESIGN SPEED
 OF 180 MPH, EXPOSURE C, I= 1.00 THERE IS A DISCREPANCY
 IN THE BASIC WIND DESIGN? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) CLARIFICATION NEEDED FOR WHAT WORK IS TO BE PART OF
 THE FOUNDATION PERMIT. SHEET S1.0 DETAIL # 2 SHOWS A
 MAT FOUNDATION AND PILLAR, THIS PERMIT INDICATES IT IS
 FOR A STRUCTURAL FOUNDATION ONLY, WHEREAS IN THE SAME
 DETAIL THE STATEMENT, ART PANEL CONNECTION BY DELEGATE
 ENGINEER HAS BEEN DESIGNED FOR THE FOLLOWING ULT BASE
 REACTIONS. ARE THE VARIOUS ART PANELS PART OF THIS
 PERMIT? UNDER THE SCOPE OF WORK ON THE PERMIT
 APPLICATION IT DOES NOT APPEAR SO?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 11:34 Rev Time 0.00
Received By jleahy Date 2019-02-20 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-17 Cont ID  
Sent By pvalenti Date 2019-06-17 Time 11:20 Rev Time 0.00
Received By pvalenti Date 2019-06-12 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-16 Cont ID  
Sent By pvalenti Date 2019-04-16 Time 10:34 Rev Time 0.00
Received By pvalenti Date 2019-03-12 Time 13:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 11:36 Rev Time 0.00
Received By jleahy Date 2019-01-30 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-06-17 Cont ID  
Sent By pvalenti Date 2019-06-17 Time 11:20 Rev Time 0.00
Received By pvalenti Date 2019-06-17 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By pvalenti Date 2019-04-16 Time 10:34 Rev Time 0.00
Received By pvalenti Date 2019-04-16 Time 10:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 11:36 Rev Time 0.00
Received By jleahy Date 2019-02-20 Time 11:36 Sent To  
Notes
2019-02-20 11:36:43PLANS NOT DIGITALLY SIGNED JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-04 Cont ID  
Sent By aaponte Date 2019-04-04 Time 11:45 Rev Time 0.00
Received By aaponte Date 2019-04-04 Time 11:45 Sent To  
Notes
2019-04-04 11:45:54LANDSCAPE NOT INCLUDED INTHIS PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-02-15 Cont ID  
Sent By aaponte Date 2019-02-15 Time 16:40 Rev Time 0.00
Received By aaponte Date 2019-02-15 Time 16:40 Sent To  
Notes
2019-02-15 16:42:53PLEASE INCLUDE THE SIDEWALK DIMENSIONS TO CONFIRM
 COMPLIANCE WITH MINIMUM 8 FOOT WIDE SIDEWALK CLEARANCE.
 PLEASE DIMENSION FROM THE BACK OF CURB TO THE FIRST
 PLANTING BED, AND FROM PLANTING BED TO TREE GRATE FOR
 NARROWEST SIDEWALK PORTION.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.