Plan Review Details - Permit 19011155
Plan Review Stops For Permit 19011155
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2019-08-26 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-26 Cont ID  
Sent By jwitmer Date 2019-02-26 Time 12:42 Rev Time 0.00
Received By jwitmer Date 2019-02-26 Time 08:11 Sent To  
Notes
2019-02-26 12:42:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011155
 ADD: 250 S AUSTRALIAN AVE. 17TH & 18TH FLOORS
 CONT: TURNER CONSTRUCTION
 TEL: 786-9000
 E-MAIL: [email protected] NUNEZ DARA
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 26TH/ 2019
 ACTION: DENIED
  
 1) SHEET 003_A102 PARTITION TYPES. WALL TYPE 1/ TYPE R
 IS INDICATED AS A ONE HOUR FR WALL. IF THIS WALL TYPE
 IS A ONE HOUR FIRE PARTITION PLEASE PROVIDE COMPLIANCE
 WITH 2017 FBC-B 708.3 FIRE-RESISTANCE RATING, PLEASE
 PROVIDE AN ASSEMBLY NUMBER (UL OR GYPSUM ASSOCIATION)
 SHOWING THE COMPONENTS OF THE WALL, SPACING OF STUDS
 AND THE HEIGHT LIMITATIONS.
  
 2) SHEET 003_A102 PARTITION TYPES. WALL TYPES 1 & 2
 INDICATE THE BOTTOM PLATE IS TO BE SHOOT INTO THE SLAB
 USING HILTI PINS, HOW LONG ARE THE PINS AND WHAT TYPE
 OF FLOOR SLAB DOES THIS BUILDING HAVE, POST TENSION
 TENDONS? WALL TYPE DETAILS 3 & 4 ALSO INDICATE THE USE
 OF POWER ACTIVATED PINS ? INCH DIA. X 1 ? INCHES LONG.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET 003_A102 PARTITION TYPES 3 & 4 BOTH SHOW 6
 INCH CONCRETE STEEL TUBES BEING CORED INTO THE FLOOR
 SLAB. THERE IS AGAIN NO NOTATION AS TO CAUTION OF THE
 TYPE OF FLOOR SLAB, IF TENDONS COULD BE CUT, THE WIDTH
 OF THE WHOLE, THE DEPTH OF THE HOLE, NOR HOW THICK THE
 SLAB REALLY IS. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) SHEET 003_A102 THE TOP OF THE PARTITIONS THERE IS NO
 MENTION AS TO HOW TO SECURE THE WALL SYSTEMS WITH
 EXCEPTION TO WALL TYPE 3 THAT SHOWS WHAT MIGHT BE A
 LINEAR DIFFUSER BEING ANCHORED IN TO THE FLOOR ABOVE
 NOTE INDICATES APPROVED METAL INSERT OR ANCHOR, PLEASE
 PROVIDE THE TYPE OF ANCHOR.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) SHEET 005_A200.1 CONSTRUCTION PLANS. THIS FLOOR PLAN
 DOES NOT INDICATE WHAT WALLS ARE NEW AND WHAT WALLS
 REMAINED. THERE ARE VERY FEW MEASUREMENTS TO EVEN
 REVIEW FOR CODE COMPLIANCE, THE STAIRWAY WALLS,
 ELEVATOR WALLS ARE NOT EVEN IN THE WALL TYPE LEGEND
 FOUND ON THIS PAGE. PLEASE NOTE THE DOORS THAT MAKE UP
 THE ELEVATOR LOBBY ARE ON WALLS BUILT OUT FROM THE 2
 HOUR SHAFT ENCLOSURES FOR THE ELEVATORS BUT THERE IS NO
 MENTION OF THE WALL TYPE, PLEASE NOTE THE ELEVATOR
 LOBBY WALLS ONLY NEED TO BE A 1 HOUR SEE FBC-B TABLE
 716.5 FOR WALL TYPES AND RATINGS AS WELL AS OPENING
 PROTECTIVES.
  
 6) SHEET 005_A200.1 CONSTRUCTION PLANS & 006_A200.2.
 BOTH SHEETS INDICATE A COMMUNICATING STAIR BETWEEN 2
 STORIES WITH NO ENCLOSURE, IS THIS A NEW OPENING, DOES
 THIS STAIR GO FURTHER THAN THE 2 STORIES WHERE WORK IS
 TO OCCUR? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 SHOW HOW COMPLIANCE WITH THE 2017 FBC-B SECTION 1019.3.
  
  
 7) SHEET 005_A200.1 CONSTRUCTION PLANS & 006_A200.2.
 PLEASE SHOW ON BOTH FLOOR PLAN COMMON PATH OF TRAVEL
 AND THE TRAVEL DISTANCES EXCEEDS THE VALUES LISTED IN
 TABLE 1006.2.1 OR WHERE THE DESIGN OCCUPANT LOAD
 EXCEEDS THAT FOUND IN TABLE 1006.2.12.
  
 8) SHEET 005_A200.1 CONSTRUCTION PLANS & 006_A200.2.
 BOTH SHEETS INDICATE THE USE OF MICROWAVES INSTALLED IN
 THE UPPER CABINETS, PLEASE SHOW HOW COMPLIANCE WITH THE
 2017 FBC-ACCESSIBILITY CODE WILL OCCUR:
 8A) 308 REACH RANGES. 308.2 FORWARD REACH / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 8B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 9) SHEET 013_A500 THE RESTROOM ELEVATIONS 4 & 5 DO NOT
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTIONS:
 604.5 GRAB BARS.
 9A) 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR SHALL BE
 42 INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE
 REAR WALL.
  
 9B) 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE
 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE
 OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 9C) PLEASE ALSO SEE DETAILS 4 & 5 AS TO WHERE YOU
 MEASURE FOR HEIGHT, TO THE TOP OF THE GRIPPING SURFACE
 NOT CENTER-LINE. SEE RESTROOM NOTE # 2.
 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By jleahy Date 2019-08-14 Time 11:45 Rev Time 0.00
Received By jleahy Date 2019-08-14 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By jleahy Date 2019-03-05 Time 11:15 Rev Time 0.00
Received By jleahy Date 2019-03-05 Time 10:57 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2019-08-14 Cont ID  
Sent By jleahy Date 2019-08-14 Time 11:45 Rev Time 0.00
Received By jleahy Date 2019-08-14 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2019-03-05 Cont ID  
Sent By jleahy Date 2019-03-05 Time 11:21 Rev Time 0.00
Received By jleahy Date 2019-03-05 Time 11:21 Sent To  
Notes
2019-03-05 11:21:44LOW VOLTAGE FOR DATA AND PHONE ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-06 Cont ID  
Sent By pleduc Date 2019-08-06 Time   Rev Time 0.00
Received By pleduc Date 2019-08-06 Time 10:31 Sent To  
Notes
2019-08-06 12:44:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-01 Cont ID  
Sent By pleduc Date 2019-02-01 Time   Rev Time 0.00
Received By pleduc Date 2019-01-31 Time 12:27 Sent To  
Notes
2019-02-01 16:01:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS.
  
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2019-09-12 Cont ID  
Sent By gjohnson Date 2019-09-12 Time 10:37 Rev Time 0.00
Received By gjohnson Date 2019-09-05 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-28 Cont ID  
Sent By gjohnson Date 2019-08-28 Time 12:06 Rev Time 0.00
Received By gjohnson Date 2019-07-30 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-13 Cont ID  
Sent By gjohnson Date 2019-03-13 Time 07:44 Rev Time 0.00
Received By gjohnson Date 2019-01-29 Time 09:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-02-26 Cont ID  
Sent By jwitmer Date 2019-02-26 Time 12:42 Rev Time 0.00
Received By jwitmer Date 2019-02-26 Time 08:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-03-11 Cont ID  
Sent By ccole Date 2019-03-11 Time 16:27 Rev Time 0.00
Received By ccole Date 2019-03-11 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-12 Cont ID  
Sent By gjohnson Date 2019-09-12 Time 10:34 Rev Time 0.00
Received By gjohnson Date 2019-09-11 Time 17:19 Sent To  
Notes
2019-09-12 10:36:21PLUMBING PROVISO : 19011155
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE TOILET.
 PER FBC ACC 604.3.1 AND WPB AMEND TO FBC 107.2.1
 ADDITIONAL INFORMATION REQUIRED
  
 2.SHOW COMPLIANCE WITH FBC ACC 604.4 SEATS. THE SEAT
 HEIGHT OF A WATER CLOSET ABOVE THE FINISH FLOOR SHALL
 BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM)
 MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS SHALL
 NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. WPB AMEND
 TO FBC 107.2.1 ADDITIONAL INFORMATION REQUIRED
  
 3. SHOW COMPLIANCE WITH FBC ACC 605.2 HEIGHT AND DEPTH.
 URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE
 WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP MINIMUM
 MEASURED FROM THE OUTER FACE OF THE URINAL RIM TO THE
 BACK OF THE FIXTURE. WPB AMEND TO FBC 107.2.1
 ADDITIONAL INFORMATION REQUIRED
  
 4. SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION.THE
 WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,WPB AMEND TO FBC 107.2.1 ADDITIONAL
 INFORMATION REQUIRED
  
 5. ONE OF THE LAVATORY'S OUTSIDE THE TOILET STALL SHALL
 COMPLY WITH FBC ACC 606.2, 606.3
  
 6. SHOW DIMENSIONS ON ALL CLEAR FLOOR SPACE. WPB AMEND
 TO FBC 107.2.1 ADDITIONAL INFORMATION REQUIRED
  
 7. SHT. A-500 DETAILS #4, #5 SHOW ALL ACCESSIBILITY
 DIMENSIONS. WPB AMEND TO FBC 107.2.1 ADDITIONAL
 INFORMATION REQUIRED
  
 8. SHT. A-500 IT SHALL STATE THAT ALL FIXTURES AND
 CLEARANCES SHALL COMPLY WITH FLORIDA BUILDING CODE
 ACCESSIBILITY 2017 6TH EDITION. WPB AMEND TO FBC
 107.2.1 ADDITIONAL INFORMATION REQUIRED
  
 9. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1
 PLEASE SHOW LOCATION OF ACCESSIBLE WATER FOUNTAIN. WPB
 AMEND TO FBC 107.2.1 ADDITIONAL INFORMATION REQUIRED
  
 10. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION
 GUIDE AND SIZING CHART FOR TANKLESS HEATERS. WPB AMEND
 TO FBC 107.2.1 ADDITIONAL INFORMATION REQUIRED
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-28 Cont ID  
Sent By gjohnson Date 2019-08-28 Time 12:04 Rev Time 0.00
Received By gjohnson Date 2019-08-28 Time 12:04 Sent To  
Notes
2019-08-28 12:06:34CONTRACTOR REQUEST FAILED RESULT SO THAT HE COULD UPLOD
 NEW P DRAWINGS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-03-13 Cont ID  
Sent By gjohnson Date 2019-03-13 Time 06:32 Rev Time 0.00
Received By gjohnson Date 2019-03-13 Time 05:51 Sent To  
Notes
2019-03-13 06:32:471ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE LEVEL OF ALTERATION ON THE PLAN. PER FBC EX
 CH. 5
  
 2. PROVIDE EXISTING FLOOR PLAN 17TH + 18TH FLOOR. PER
 WPB AMEND TO FBC 107.2.1
  
 3. IT IS UNCLEAR WHAT PLUMBING WORK IS BEING DONE SHEET
 A-500 IS SHOWING DETAILS FOR THE COMMON BATHROOMS IS
 THERE WORK BEING DONE ON THESE BATHROOMS PLEASE PLACE
 NOTES ON PLANS WITH DETAILED SCOPE OF PLUMBING WORK
 BEING DONE. IF THESE BATHROOMS ARE BEING MODIFIED
 PLEASE SHOW COMPLIANCE WITH THE FOLLOWING:
 A) FBC ACC 602.4 , 602.2 , 602.7 , 604.2 , 604.3.1 ,
 604.4 , 604.5.1 , 604.5.2 , 605.2 , 605.3 , 604.7 ,
 213.3.4
 B) A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1
 FBC ACC 211.2
 C) TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 4. A BACK FLOW IS REQUIRED ON THE ICE MAKER. PER FBC
 608.3
  
 5. PLEASE SHOW THE PLUMBING FIXTURES ON THE FLOOR PLANS
 P-200 AND P-210. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-09-12 Cont ID  
Sent By gjohnson Date 2019-09-12 Time 10:46 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-19 Cont ID  
Sent By shill Date 2019-03-19 Time 10:54 Rev Time 0.00
Received By shill Date 2019-03-19 Time 10:54 Sent To  
Notes
2019-03-19 10:55:24E & P DIGITAL SIGNATURES OK
 NEW SHEETS SUBMITTED NEXT REIVEW CYCLE REQUIRE
 VERIFICATION
 [email protected]
2019-03-11 16:27:48MECH PLANS GOOD.
2019-02-26 12:43:321ST REVIEW. ARCHITECTURAL SHEETS CHECKED FOR ELECTRONIC
 SIGNATURES, OK. J WITMER

Review Stop Z ZONING
Rev No 1 Status P Date 2019-02-13 Cont ID  
Sent By aaponte Date 2019-02-13 Time 14:28 Rev Time 0.00
Received By aaponte Date 2019-02-13 Time 14:28 Sent To  
Notes
2019-02-13 14:28:32INTERIOR TENANT IMPROVEMENT FOR OFFICE USE.