Plan Review Details - Permit 19011073
Plan Review Stops For Permit 19011073
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-04 Cont ID  
Sent By shill Date 2019-02-04 Time 08:47 Rev Time 0.00
Received By shill Date 2019-02-04 Time 08:47 Sent To  
Notes
2019-02-04 08:47:38INTERIOR ONLY (REDLINED)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-26 Cont ID  
Sent By shill Date 2019-01-26 Time 11:22 Rev Time 0.00
Received By shill Date 2019-01-26 Time 11:22 Sent To  
Notes
2019-01-26 11:24:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE PLAN PROPOSES TO REMOVE DOORS AND WINDOWS.
 COMPONENTS & CLADDING CANNOT BE REMOVED AS A PART OF AN
 INTERIOR DEMO PERMIT, FBC 107. REMOVE FROM SCOPE (CAN
 BE CROSSED OFF OR CONTACT ME VIA EMAIL TO REQUEST A
 REDLINE).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-06 Cont ID  
Sent By jpearson Date 2019-02-06 Time 06:48 Rev Time 0.00
Received By jpearson Date 2019-02-06 Time 06:48 Sent To I
Notes
2019-02-06 06:48:16SUB-PERMIT APPLICATION RECEIVED BY EMAIL. ORIGINAL
 REQUIRED AT TIME OF PICK UP.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By jpearson Date 2019-01-29 Time 13:17 Rev Time 0.00
Received By jpearson Date 2019-01-29 Time 13:17 Sent To FIRE
Notes
2019-01-29 13:16:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FOR DEMO PERMITS, ELECTRICAL PLAN REVIEW NEEDS AN
 ELECTRICAL PERMIT APPLICATION FROM AN ELECTRICAL
 CONTRACTOR FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected] AND CC
 [email protected] AND [email protected] SO WE RECEIVE IT
 ALSO. WHEN THIS EMAIL IS RECEIVED ONE OF THE REVIEWERS
 WILL APPROVE THE PLAN REVIEW. THE ORIGINAL PERMIT
 APPLICATION MUST BE SUBMITTED WHEN THE PERMIT IS PICKED
 UP. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-02-01 Cont ID  
Sent By sathomas Date 2019-02-01 Time 00:00 Rev Time 0.00
Received By sathomas Date 2019-02-01 Time 00:00 Sent To I
Notes
2019-02-01 14:07:00PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-01 Cont ID  
Sent By sholder Date 2019-02-01 Time 15:44 Rev Time 0.00
Received By cpuell Date 2019-01-24 Time 14:31 Sent To  
Notes
2019-01-26 11:26:341/26 TO GJ DESK
  
  
2019-01-25 14:31:53SHILL

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-26 Cont ID  
Sent By gjohnson Date 2019-01-26 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2019-01-26 Time 11:47 Sent To E
Notes
***NONE***