Plan Review Details - Permit 19011061
Plan Review Stops For Permit 19011061 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2019-07-17 |
|
|
Cont ID |
|
Sent By |
rgathrig |
Date |
2019-07-17 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
rgathrig |
Date |
2019-07-17 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2019-07-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-07-03 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-07-03 |
Time |
09:17 |
Sent To |
|
|
Notes |
2019-07-03 09:19:48 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 3RD BUILDING PLAN REVIEW DENIED: | | | | 1. ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561?805?6673 | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | 2ND BUILDING PLAN REVIEW DENIED: | | | | (THE COMMENTS FROM ITEM #1 OF THE 1ST REVIEW, NOTED | | BELOW, STILL HAVE NOT BEEN CORRECTED. PROVIDE | | SIGNED/SEALED BY DESIGNER, FULL SIZE PLANS.) | | 1. THE SUBMITTED SHEET A.1 DOES NOT INDICATE WHO THE | | DESIGNER OF THE PLAN IS. | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TOBE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | (THE COMMENTS FROM ITEM #2 OF THE 1ST REVIEW, NOTED | | BELOW, STILL HAVE NOT BEEN CORRECTED. PROVIDE THE PLANS | | IN FULL ACCEPTABLE SIZE. ) | | 2. THE SUBMITTED SHEET A.1 DOES NOT COMPLY WITH RECORD | | RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF | | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A | | MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE | | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY | | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, | | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. | | | | (THE COMMENTS FROM ITEM #3 OF THE 1ST REVIEW, NOTED | | BELOW, ONLY HAVE CORRECTIONS IN ONE DETAILED SECTION OF | | SHEET A?1. THE OTHER DETAILED SECTIONS OF SHEET A?1 | | NEED TO BE CORRECTED. PROVIDE THE CORRECTED PLANS IN | | FULL ACCEPTABLE SIZE PER NOTES IN COMMENT #2 ) | | 3. SHEET A.1 DETAIL # 1 CABINET ELEVATION SHOWS A | | MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE | | AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE | | FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017 | | FBC?ACCESSIBILITY CODE SECTIONS: 308 REACH RANGES. | | 308.2 FORWARD REACH./ 308.2.1 | | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. | | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 | | OBSTRUCTED HIGH REACH. | | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL | | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES | | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL | | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT | | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE | | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS | | MAXIMUM. | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-05-20 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-20 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-20 |
Time |
13:24 |
Sent To |
|
|
Notes |
2019-05-20 14:07:38 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 2ND BUILDING PLAN REVIEW DENIED: | | | | (THE COMMENTS FROM ITEM #1 OF THE 1ST REVIEW, NOTED | | BELOW, STILL HAVE NOT BEEN CORRECTED.) | | 1. THE SUBMITTED SHEET A?1 DOES NOT INDICATE WHO THE | | DESIGNER OF THE PLAN IS? | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | (THE COMMENTS FROM ITEM #2 OF THE 1ST REVIEW, NOTED | | BELOW, STILL HAVE NOT BEEN CORRECTED.) | | 2. THE SUBMITTED SHEET A?1 DOES NOT COMPLY WITH RECORD | | RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF | | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A | | MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE | | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY | | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, | | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. | | | | (THE COMMENTS FROM ITEM #3 OF THE 1ST REVIEW, NOTED | | BELOW, ONLY HAVE CORRECTIONS IN ONE DETAILED SECTION OF | | SHEET A-1. THE OTHER DETAILED SECTIONS OF SHEET A-1 | | NEED TO BE CORRECTED.) | | 3. SHEET A?1 DETAIL # 1 CABINET ELEVATION SHOWS A | | MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE | | AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE | | FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017 | | FBC?ACCESSIBILITY CODE SECTIONS: 308 REACH RANGES. | | 308.2 FORWARD REACH./ 308.2.1 | | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. | | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 | | OBSTRUCTED HIGH REACH. | | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL | | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES | | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL | | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT | | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE | | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS | | MAXIMUM. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2019-02-05 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2019-02-05 |
Time |
08:25 |
Sent To |
|
|
Notes |
2019-02-05 08:40:47 | 2017 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 19011061 | | ADD: 501 FERN ST. SUITE: 101 | | CONT: MOSS & ASSOCIATES | | TEL: 561-719-5517 | | E-MAIL: [email protected] | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: TUES. FEB. 05/2019 | | ACTION: DENIED | | | | 1) THE SUBMITTED SHEET A-1 DOES NOT INDICATE WHO THE | | DESIGNER OF THE PLAN IS? | | | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE | | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR | | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE | | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD | | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND | | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER | | ONE SHEET. | | | | 2) THE SUBMITTED SHEET A-1 DOES NOT COMPLY WITH RECORD | | RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF | | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A | | MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE | | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY | | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, | | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. | | | | 3) SHEET A-1 DETAIL # 1 CABINET ELEVATION SHOWS A | | MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE | | AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE | | FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017 | | FBC-ACCESSIBILITY CODE SECTIONS: | | | | 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 | | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. | | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 | | OBSTRUCTED HIGH REACH. | | | | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL | | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES | | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL | | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT | | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE | | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS | | MAXIMUM. | | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | JAMES A. WITMER BN, PX, SFP, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | TEL: 561-805-6717 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-06-25 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-06-25 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-06-25 |
Time |
12:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-05-20 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-05-20 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-05-20 |
Time |
15:51 |
Sent To |
I |
|
Notes |
2019-05-20 15:11:40 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | 109.3 (NOT PROVIDED.) | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-02-21 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-02-21 |
Time |
09:23 |
Sent To |
I |
|
Notes |
2019-02-21 09:23:31 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY | | THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | 471.025; WPB FBC 107.2.1, 107.3.5 | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-07-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-07-03 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-28 |
Time |
10:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-05-20 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-05-13 |
Time |
11:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-02-21 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-01-24 |
Time |
14:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2019-07-17 |
|
|
Cont ID |
|
Sent By |
rgathrig |
Date |
2019-07-17 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
rgathrig |
Date |
2019-07-17 |
Time |
15:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2019-06-12 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-06-12 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-06-12 |
Time |
10:04 |
Sent To |
|
|
Notes |
2019-06-12 10:05:03 | PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH | | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | 1) VALUE STILL APPEARS TOO LOW. PROVIDE ACTUAL SIGNED | | CONTRACTS NOT EMAILS OF EST. THE PLUMBING FIXTURES, ADA | | LIFT AND DESIGN COST HAVE NOT BEEN INCLUDED IN YOUR | | VALUATION SUBMITTAL. WPB AMEND 109.3 | | | | 2) PLANS SUBMITTED ARE NOT SIGNED AND SEALED BY DESIGN | | PROFESSIONAL. THE EXISTING FLOOR PLAN LAY OUT HAS BEEN | | REMOVED.F.S 471, 481 | | | | 3) TANKLESS WATER HEATER INSTALLATION MANUAL CALLS OUT | | ONLY A 10F HEAT RISE PRODUCING A MAX 90F OF HOT WATER @ | | 2GPM. PER FBC-P 607.1 HOT WATER SHALL BE REQUIRED. HOT | | WATER IS DEFINED AS 110F OR GREATER. SUBMIT A TANKLESS | | WATER HEATER WITH A MIN OF 30F HEAT RISE @ 2GPM. FBC-P | | 604.3. PLEASE NOTE BY CHANGING THE KW OF THE HWH THE | | ELC DEMAND AND WIRE SIZE WILL INCREASE. PLEASE BE SURE | | TO REVISE THE ELC LOAD AND PLAN ACCORDINGLY. | | | | 4) PROVIDE CLEAR FLOOR SPACE, TUNING SPACE, AND | | ACCESSIBLE ROUTE OF AND TO THE BREAK ROOM SINK. ALL | | ELEMENTS SHALL MEET FLORIDA ACCESSIBILITY. 606.2, 305, | | 402, 403 | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2019-05-16 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-05-16 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-05-16 |
Time |
07:28 |
Sent To |
|
|
Notes |
2019-05-16 08:13:10 | PLUMBING 2ND REVIEW**DENIED** | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | 1) THE VALUE SEEMS LOW. THIS WAS ADDRESSED BY THE | | ELECTRICAL PLANS REVIEWER ON THE 1ST REVIEW BUT NO | | DOCUMENTATION WAS SUBMITTED TO ADDRESS THIS COMMENT. | | 2ND REQUEST:PROVIDE A SIGNED BONA FIDE CONTRACT TO | | INCLUDE THE ENTIRE SCOPE OF WORK FOR THIS PROJECT. FL | | ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF DESIGN | | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS | | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE | | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT | | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE | | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION | | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, | | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, | | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, | | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS | | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF | | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO | | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED | | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT | | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS | | REVIEW. | | | | 2) PROVIDE THE LOCATION OF DISCHARGE THAT THE LIFT | | STATION SHALL PUMP TO. PROVIDE CHECK VALVE AND MATERIAL | | TO BE USED. FBC 107.2. | | | | 3) PROVIDE THE INSTALLATION MANUAL FOR THE LIFT | | STATION. FBC 107.2.1 | | | | 4) PROVIDE THE INSTALLATION MANUAL FOR THE TANKLESS | | WATER HEATER TO INCLUDE THE HEAT RISE CHART SHOWING THE | | HEATER IS CAPABLE OF PRODUCING HOT WATER MIN 110F TO | | THE FIXTURE AS REQUIRED FBC P 607.1. | | | | 5) YOU ISOMETRIC APPEARS TO SHOW THE USE OF AAV'S. A | | VENT SHALL BE REQUIRED AS TO NOT ALLOW THE LIFT PUMP TO | | BECOME AIR BOUND AND AS A SEPARATE BUILDING DRAIN VENT | | SHALL EXTENT TO THE OUT DOORS. FBC 901.2.1, 904.1 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-02-01 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-02-01 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-02-01 |
Time |
11:21 |
Sent To |
|
|
Notes |
2019-02-01 11:21:59 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. PROVIDE PLUMBING FLOOR PLAN AND SANITARY ,WATER | | ISOMETRIC. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | 2. ALL INFORMATION, DRAWINGS,SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. PER WPB AMEND TO | | FBC 107.2.1 | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
|