Plan Review Details - Permit 19011061
Plan Review Stops For Permit 19011061
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-07-17 Cont ID  
Sent By rgathrig Date 2019-07-17 Time 15:36 Rev Time 0.00
Received By rgathrig Date 2019-07-17 Time 15:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 09:21 Rev Time 0.00
Received By pvalenti Date 2019-07-03 Time 09:17 Sent To  
Notes
2019-07-03 09:19:48***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING PLAN REVIEW DENIED:
  
 1. ***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 2ND BUILDING PLAN REVIEW DENIED:
  
 (THE COMMENTS FROM ITEM #1 OF THE 1ST REVIEW, NOTED
 BELOW, STILL HAVE NOT BEEN CORRECTED. PROVIDE
 SIGNED/SEALED BY DESIGNER, FULL SIZE PLANS.)
 1. THE SUBMITTED SHEET A.1 DOES NOT INDICATE WHO THE
 DESIGNER OF THE PLAN IS.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TOBE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 (THE COMMENTS FROM ITEM #2 OF THE 1ST REVIEW, NOTED
 BELOW, STILL HAVE NOT BEEN CORRECTED. PROVIDE THE PLANS
 IN FULL ACCEPTABLE SIZE. )
 2. THE SUBMITTED SHEET A.1 DOES NOT COMPLY WITH RECORD
 RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 (THE COMMENTS FROM ITEM #3 OF THE 1ST REVIEW, NOTED
 BELOW, ONLY HAVE CORRECTIONS IN ONE DETAILED SECTION OF
 SHEET A?1. THE OTHER DETAILED SECTIONS OF SHEET A?1
 NEED TO BE CORRECTED. PROVIDE THE CORRECTED PLANS IN
 FULL ACCEPTABLE SIZE PER NOTES IN COMMENT #2 )
 3. SHEET A.1 DETAIL # 1 CABINET ELEVATION SHOWS A
 MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE
 AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE
 FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017
 FBC?ACCESSIBILITY CODE SECTIONS: 308 REACH RANGES.
 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-20 Cont ID  
Sent By pvalenti Date 2019-05-20 Time 13:27 Rev Time 0.00
Received By pvalenti Date 2019-05-20 Time 13:24 Sent To  
Notes
2019-05-20 14:07:38***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING PLAN REVIEW DENIED:
  
 (THE COMMENTS FROM ITEM #1 OF THE 1ST REVIEW, NOTED
 BELOW, STILL HAVE NOT BEEN CORRECTED.)
 1. THE SUBMITTED SHEET A?1 DOES NOT INDICATE WHO THE
 DESIGNER OF THE PLAN IS?
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 (THE COMMENTS FROM ITEM #2 OF THE 1ST REVIEW, NOTED
 BELOW, STILL HAVE NOT BEEN CORRECTED.)
 2. THE SUBMITTED SHEET A?1 DOES NOT COMPLY WITH RECORD
 RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 (THE COMMENTS FROM ITEM #3 OF THE 1ST REVIEW, NOTED
 BELOW, ONLY HAVE CORRECTIONS IN ONE DETAILED SECTION OF
 SHEET A-1. THE OTHER DETAILED SECTIONS OF SHEET A-1
 NEED TO BE CORRECTED.)
 3. SHEET A?1 DETAIL # 1 CABINET ELEVATION SHOWS A
 MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE
 AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE
 FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017
 FBC?ACCESSIBILITY CODE SECTIONS: 308 REACH RANGES.
 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By jwitmer Date 2019-02-05 Time 08:40 Rev Time 0.00
Received By jwitmer Date 2019-02-05 Time 08:25 Sent To  
Notes
2019-02-05 08:40:472017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011061
 ADD: 501 FERN ST. SUITE: 101
 CONT: MOSS & ASSOCIATES
 TEL: 561-719-5517
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 05/2019
 ACTION: DENIED
  
 1) THE SUBMITTED SHEET A-1 DOES NOT INDICATE WHO THE
 DESIGNER OF THE PLAN IS?
  
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) THE SUBMITTED SHEET A-1 DOES NOT COMPLY WITH RECORD
 RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 3) SHEET A-1 DETAIL # 1 CABINET ELEVATION SHOWS A
 MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE
 AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE
 FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTIONS:
  
 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-06-25 Cont ID  
Sent By jpearson Date 2019-06-25 Time 12:43 Rev Time 0.00
Received By jpearson Date 2019-06-25 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-20 Cont ID  
Sent By jpearson Date 2019-05-20 Time 15:51 Rev Time 0.00
Received By jpearson Date 2019-05-20 Time 15:51 Sent To I
Notes
2019-05-20 15:11:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jpearson Date 2019-02-21 Time 09:23 Rev Time 0.00
Received By jpearson Date 2019-02-21 Time 09:23 Sent To I
Notes
2019-02-21 09:23:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-03 Cont ID  
Sent By pvalenti Date 2019-07-03 Time 09:42 Rev Time 0.00
Received By pvalenti Date 2019-05-28 Time 10:13 Sent To  
Notes
2019-05-30 10:13:33B05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-05-20 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-13 Time 11:43 Sent To  
Notes
2019-05-14 11:43:24B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-21 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-24 Time 14:48 Sent To  
Notes
2019-01-28 14:49:59B02

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-07-17 Cont ID  
Sent By rgathrig Date 2019-07-17 Time 15:37 Rev Time 0.00
Received By rgathrig Date 2019-07-17 Time 15:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-06-12 Cont ID  
Sent By thunt Date 2019-06-12 Time 10:04 Rev Time 0.00
Received By thunt Date 2019-06-12 Time 10:04 Sent To  
Notes
2019-06-12 10:05:03PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) VALUE STILL APPEARS TOO LOW. PROVIDE ACTUAL SIGNED
 CONTRACTS NOT EMAILS OF EST. THE PLUMBING FIXTURES, ADA
 LIFT AND DESIGN COST HAVE NOT BEEN INCLUDED IN YOUR
 VALUATION SUBMITTAL. WPB AMEND 109.3
  
 2) PLANS SUBMITTED ARE NOT SIGNED AND SEALED BY DESIGN
 PROFESSIONAL. THE EXISTING FLOOR PLAN LAY OUT HAS BEEN
 REMOVED.F.S 471, 481
  
 3) TANKLESS WATER HEATER INSTALLATION MANUAL CALLS OUT
 ONLY A 10F HEAT RISE PRODUCING A MAX 90F OF HOT WATER @
 2GPM. PER FBC-P 607.1 HOT WATER SHALL BE REQUIRED. HOT
 WATER IS DEFINED AS 110F OR GREATER. SUBMIT A TANKLESS
 WATER HEATER WITH A MIN OF 30F HEAT RISE @ 2GPM. FBC-P
 604.3. PLEASE NOTE BY CHANGING THE KW OF THE HWH THE
 ELC DEMAND AND WIRE SIZE WILL INCREASE. PLEASE BE SURE
 TO REVISE THE ELC LOAD AND PLAN ACCORDINGLY.
  
 4) PROVIDE CLEAR FLOOR SPACE, TUNING SPACE, AND
 ACCESSIBLE ROUTE OF AND TO THE BREAK ROOM SINK. ALL
 ELEMENTS SHALL MEET FLORIDA ACCESSIBILITY. 606.2, 305,
 402, 403
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-16 Cont ID  
Sent By thunt Date 2019-05-16 Time 08:12 Rev Time 0.00
Received By thunt Date 2019-05-16 Time 07:28 Sent To  
Notes
2019-05-16 08:13:10PLUMBING 2ND REVIEW**DENIED**
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 1) THE VALUE SEEMS LOW. THIS WAS ADDRESSED BY THE
 ELECTRICAL PLANS REVIEWER ON THE 1ST REVIEW BUT NO
 DOCUMENTATION WAS SUBMITTED TO ADDRESS THIS COMMENT.
 2ND REQUEST:PROVIDE A SIGNED BONA FIDE CONTRACT TO
 INCLUDE THE ENTIRE SCOPE OF WORK FOR THIS PROJECT. FL
 ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
 2) PROVIDE THE LOCATION OF DISCHARGE THAT THE LIFT
 STATION SHALL PUMP TO. PROVIDE CHECK VALVE AND MATERIAL
 TO BE USED. FBC 107.2.
  
 3) PROVIDE THE INSTALLATION MANUAL FOR THE LIFT
 STATION. FBC 107.2.1
  
 4) PROVIDE THE INSTALLATION MANUAL FOR THE TANKLESS
 WATER HEATER TO INCLUDE THE HEAT RISE CHART SHOWING THE
 HEATER IS CAPABLE OF PRODUCING HOT WATER MIN 110F TO
 THE FIXTURE AS REQUIRED FBC P 607.1.
  
 5) YOU ISOMETRIC APPEARS TO SHOW THE USE OF AAV'S. A
 VENT SHALL BE REQUIRED AS TO NOT ALLOW THE LIFT PUMP TO
 BECOME AIR BOUND AND AS A SEPARATE BUILDING DRAIN VENT
 SHALL EXTENT TO THE OUT DOORS. FBC 901.2.1, 904.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-02-01 Cont ID  
Sent By gjohnson Date 2019-02-01 Time 11:21 Rev Time 0.00
Received By gjohnson Date 2019-02-01 Time 11:21 Sent To  
Notes
2019-02-01 11:21:591ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE PLUMBING FLOOR PLAN AND SANITARY ,WATER
 ISOMETRIC. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. ALL INFORMATION, DRAWINGS,SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. PER WPB AMEND TO
 FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  