Plan Review Details - Permit 19010989
Plan Review Stops For Permit 19010989
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-05 Cont ID  
Sent By jpearson Date 2019-02-05 Time 08:02 Rev Time 0.00
Received By jpearson Date 2019-02-05 Time 08:02 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By jpearson Date 2019-01-25 Time 15:44 Rev Time 0.00
Received By jpearson Date 2019-01-25 Time 15:44 Sent To I
Notes
2019-01-25 15:44:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 3. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 4. PROVIDE DISTANCE OF LIGHT FIXTRES TO POOL WATER TO
 CONFIRM CODE COMPLIANCE. ALSO PROVIDE SPEC SHEETS FOR
 LIGHT FIXTURE WHICH INCLUDE TYPE OF FIXTURE AND
 VOLTAGE. WPB FBC 107.2.1; NEC 680.22
 5. ALL EXTERIOR RECEPTACLES REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.3
 6. WHAT SIZE BREAKER WILL 6-3 ROMEX BE ATTACHED TO?
 THIS SIZE ROMEX IS GOOD FOR 50 AMPS. NEC 334.80; FBC RE
 E3705.4.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-02-05 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-30 Time 13:39 Sent To  
Notes
2019-01-31 13:39:39RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-01-25 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-23 Time 16:03 Sent To  
Notes
2019-01-24 16:03:41REVISION ROUTED TO JPEARSON