Plan Review Details - Permit 19010903
Plan Review Stops For Permit 19010903
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-03-06 Cont ID  
Sent By tklarge Date 2019-03-06 Time 06:24 Rev Time 0.00
Received By tklarge Date 2019-03-06 Time 05:57 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-02-19 Cont ID  
Sent By tklarge Date 2019-02-19 Time 04:47 Rev Time 0.00
Received By tklarge Date 2019-02-19 Time 03:27 Sent To I
Notes
2019-02-19 04:47:451) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THE PERMIT
 APPLICATION FOLDER SHOWING TWO DIFFERENT TOTAL BTU
 LOADS FOR THE GAS SYSTEM. ONE GAS DRAWING SHOWS A TOTAL
 BTU LOAD OF 215,000 BTU'S AND THE OTHER DRAWING SHOWS A
 TOTAL BTU LOAD OF 245,000 BTU'S. CLARIFY. REMOVE OLD
 DRAWINGS FROM THE PERMIT APPLICATION PACKAGE.WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) IF THE TOTAL BTU LOAD IS 245,000 THEN THE 1 INCH
 LINE FROM THE METER IS UNDERSIZED PER SIZING TABLE
 402.4 (2). CLARIFY .
 3) THE 1/2 INCH LINE TO THE STOVE IS UNDERSIZED. THE
 LINE SHALL BE A MINIMUM OF 3/4 INCH PER TABLE 402.4 (2)
 BASED ON THE LENGTH OF 80 FEET.
 4) GAS PIPING INSTALLED ACROSS ROOF SURFACES SHALL BE
 ELEVATED NO LESS THAN 3 1/2 INCHES ABOVE THE ROOF
 SURFACE. 2017 FBC-FUEL GAS SEC.404.9. PLACE A NOTE ON
 THE PLANS REFERENCING THIS CODE SECTION.
 5) THE MINIMUM SIZE PIPE TO THE TANKLESS WATER HEATER
 SHALL BE 1 INCH PER TABLE 402.4(2). A 3/4 INCH METALLIC
 PIPE CAN ONLY CARRY 117,000 BTU'S UNDER THE 80 FEET ROW
 IN THE GAS TABLE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By tklarge Date 2019-01-29 Time 11:14 Rev Time 0.00
Received By tklarge Date 2019-01-29 Time 10:32 Sent To I
Notes
2019-01-29 11:14:431) SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 4) SHOW THE SIZE OF THE GAS LINE AT THE OUTLET OF THE
 GAS METER.
 5) BASED ON THE DISTANCE FROM THE METER TO THE FURTHEST
 OUTLET AND THE SIZING TABBLE USED, THE 1 INCH LINE MAY
 BE UNDERSIZED.
 ) A SEPARATE ELECTRIC PERMIT WILL BE REQUIRED.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-06 Cont ID  
Sent By tklarge Date 2019-03-06 Time 06:23 Rev Time 0.00
Received By tklarge Date 2019-03-01 Time 11:32 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-19 Cont ID  
Sent By tklarge Date 2019-02-19 Time 04:48 Rev Time 0.00
Received By tklarge Date 2019-02-08 Time 13:48 Sent To  
Notes
2019-02-11 13:49:09RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2019-01-22 Time 13:12 Sent To  
Notes
2019-01-23 13:12:45PLUMB <5K

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-29 Cont ID  
Sent By tklarge Date 2019-01-29 Time 10:32 Rev Time 0.00
Received By tklarge Date 2019-01-29 Time 06:30 Sent To  
Notes
***NONE***