2019-01-29 11:14:43 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| 4) SHOW THE SIZE OF THE GAS LINE AT THE OUTLET OF THE |
| GAS METER. |
| 5) BASED ON THE DISTANCE FROM THE METER TO THE FURTHEST |
| OUTLET AND THE SIZING TABBLE USED, THE 1 INCH LINE MAY |
| BE UNDERSIZED. |
| ) A SEPARATE ELECTRIC PERMIT WILL BE REQUIRED. |
| |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |