|
 |
 |
 |
 |
 |
Plan Review Details - Permit 19010781
Plan Review Stops For Permit 19010781 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-01-24 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-01-24 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-01-18 |
Time |
13:59 |
Sent To |
|
|
Notes |
2019-01-22 13:59:44 | ROUTED TO PLUMBING INBOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-01-24 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-01-24 |
Time |
08:22 |
Rev Time |
|
Received By |
tklarge |
Date |
|
Time |
|
Sent To |
I |
|
Notes |
2019-01-24 06:44:09 | 1) SUBMIT A CODE COMPLIANT SANITARY RISER DIAGRAM FOR | | REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.3. | | 2) SHOW ALL PIPE SIZES ON THE REQUESTED SANITARY | | RISER.WPB AMEND. TO FBC SEC. 107.2.1. | | 3) WHAT IS DISCHARGING INTO THE OUTSIDE DRAIN? | | RAINWATER CANNOT DISCHARGE TO THE SANITARY SYSTEM PER | | CITY ORDINANCE. | | 4) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE | | WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE | | CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. | | SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM | | EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING | | OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO INCLUDE | | TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR | | BARRIER OVER THE SOIL. A COPY OF THE TERMITE | | CERTIFICATE SHALL BE ONSITE FOR FINAL INSPECTION. | | 5) A CLEANOUT BROUGHT TO GRADE SHALL BE INSTALLED AT | | THE CONNECTION AT THE CITY LATERAL. | | | | A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED DUE TO | | THE LACK OF REQUIRED INFORMATION ON THE PLAN. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |