Plan Review Details - Permit 19010781
Plan Review Stops For Permit 19010781
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-24 Cont ID  
Sent By tklarge Date 2019-01-24 Time 08:22 Rev Time 0.00
Received By tklarge Date 2019-01-18 Time 13:59 Sent To  
Notes
2019-01-22 13:59:44ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-24 Cont ID  
Sent By tklarge Date 2019-01-24 Time 08:22 Rev Time  
Received By tklarge Date   Time   Sent To I
Notes
2019-01-24 06:44:091) SUBMIT A CODE COMPLIANT SANITARY RISER DIAGRAM FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.3.
 2) SHOW ALL PIPE SIZES ON THE REQUESTED SANITARY
 RISER.WPB AMEND. TO FBC SEC. 107.2.1.
 3) WHAT IS DISCHARGING INTO THE OUTSIDE DRAIN?
 RAINWATER CANNOT DISCHARGE TO THE SANITARY SYSTEM PER
 CITY ORDINANCE.
 4) SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS ON CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR FINAL INSPECTION.
 5) A CLEANOUT BROUGHT TO GRADE SHALL BE INSTALLED AT
 THE CONNECTION AT THE CITY LATERAL.
  
 A COMPREHENSIVE REVIEW COULD NOT BE PERFORMED DUE TO
 THE LACK OF REQUIRED INFORMATION ON THE PLAN.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved