Plan Review Details - Permit 19010757
Plan Review Stops For Permit 19010757
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By jgomez Date 2019-02-25 Time 09:18 Rev Time 0.00
Received By jgomez Date 2019-02-22 Time 18:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By jgomez Date 2019-02-05 Time 11:47 Rev Time 0.00
Received By jgomez Date 2019-02-05 Time 08:40 Sent To  
Notes
2019-02-05 11:51:31RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PLANS NEED ARCHITECT'S ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 481 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: COPY OF DIGITAL SIGNATURE IS NOT ALLOWED.
  
 2- ARCHITECT TO SPECIFY THE DESIGN PRESSURES FOR DOORS
 TO BE REPLACED. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) DOOR PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By jpearson Date 2019-02-26 Time 08:38 Rev Time 0.00
Received By jpearson Date 2019-02-26 Time 08:38 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By jpearson Date 2019-02-05 Time 08:39 Rev Time 0.00
Received By jpearson Date 2019-02-05 Time 07:43 Sent To  
Notes
2019-02-05 08:38:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. A DIGITAL SIGNATURE ON A PAPER PLAN IS NOT
 ACCEPTABLE. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 4. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. IF NO LOADS ARE BEING ADDED, STATE ON
 PLAN. NEC 215.2, 220, 408.30; FBC RE E3602.2
 5. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 7. PROVIDE GFCI PROTECTED RECEPTACLE OUTLETS ON THE
 KITCHEN ISLAND TO CODE. NEC 210.8, 210.52(C)(2); FBC RE
 E3901.4.2
 8. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-02-01 Cont ID  
Sent By fmittner Date 2019-02-01 Time 16:25 Rev Time 0.00
Received By fmittner Date 2019-02-01 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-02-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-14 Time 10:02 Sent To  
Notes
2019-02-22 18:57:26R04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-05 Cont ID  
Sent By jgomez Date 2019-02-05 Time 11:55 Rev Time 0.00
Received By jgomez Date 2019-01-18 Time 15:49 Sent To I
Notes
2019-01-24 15:49:51R18

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By jgomez Date 2019-02-25 Time 09:19 Rev Time 0.00
Received By jgomez Date 2019-02-25 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-29 Cont ID  
Sent By gjohnson Date 2019-01-29 Time 15:29 Rev Time 0.00
Received By gjohnson Date 2019-01-29 Time 08:32 Sent To  
Notes
***NONE***