Plan Review Details - Permit 19010126
Plan Review Stops For Permit 19010126
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-23 Cont ID  
Sent By pleduc Date 2019-01-23 Time   Rev Time 0.00
Received By pleduc Date 2019-01-23 Time 10:32 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By pleduc Date 2019-01-08 Time   Rev Time 0.00
Received By pleduc Date 2019-01-08 Time 14:10 Sent To I
Notes
2019-01-08 14:19:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO BE TYPICAL ARM
 OVER.
  
 FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN
 THE DESIGNED ARM OVER SYSTEM.
  
 THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT
 SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER
 FLOW.
  
 PLEASE PROVIDE CALCULATIONS DETAILS OR USE THE SAME
 TYPE OF ARM OVER THAT MATCHES THE EXISTING SYSTEM OR
 PROVIDE A JUSTIFICATION NARRATIVE WITH SPECIFIC
 DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-23 Cont ID  
Sent By cpuell Date 2019-01-23 Time 13:18 Rev Time 0.00
Received By cpuell Date 2019-01-18 Time 14:19 Sent To  
Notes
2019-01-22 14:19:22RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By cpuell Date 2019-01-08 Time 15:47 Rev Time 0.00
Received By cpuell Date 2019-01-04 Time 12:41 Sent To  
Notes
2019-01-07 12:41:44ROUTED TO FIRE INBOX