|
 |
 |
 |
 |
 |
Plan Review Details - Permit 19010126
Plan Review Stops For Permit 19010126 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2019-01-23 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-01-23 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-01-23 |
Time |
10:32 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2019-01-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-01-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-01-08 |
Time |
14:10 |
Sent To |
I |
|
Notes |
2019-01-08 14:19:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | PIPING. THE EXISTING SYSTEM APPEARS TO BE TYPICAL ARM | | OVER. | | | | FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN | | THE DESIGNED ARM OVER SYSTEM. | | | | THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT | | SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER | | FLOW. | | | | PLEASE PROVIDE CALCULATIONS DETAILS OR USE THE SAME | | TYPE OF ARM OVER THAT MATCHES THE EXISTING SYSTEM OR | | PROVIDE A JUSTIFICATION NARRATIVE WITH SPECIFIC | | DETAILS. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-01-23 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-01-23 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2019-01-18 |
Time |
14:19 |
Sent To |
|
|
Notes |
2019-01-22 14:19:22 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-01-08 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-01-08 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2019-01-04 |
Time |
12:41 |
Sent To |
|
|
Notes |
2019-01-07 12:41:44 | ROUTED TO FIRE INBOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |