Plan Review Details - Permit 19010039
Plan Review Stops For Permit 19010039
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By pvalenti Date 2019-04-25 Time 16:52 Rev Time 0.00
Received By pvalenti Date 2019-04-25 Time 16:52 Sent To  
Notes
2019-04-25 16:54:07***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 RECEIVED FLOORING UNDERLAYMENT SPECIFICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-01-30 Cont ID  
Sent By jwitmer Date 2019-01-30 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2019-01-30 Time 07:17 Sent To  
Notes
2019-01-30 10:11:092017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010039
 ADD: 4850 RYNA GREENBAUM DR.
 CONT: IBIS BUILDING CORP.
 TEL: 561-568-2570
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 30/2019
 ACTION: BUILDING PROVISO
  
 1) SHEET H1-01 INDICATES WITH NOTE 3 THE REMOVAL OF
 CARPET, PAD AND ADHESIVE. NOTE 9 INDICATES THE REMOVAL
 OF WOOD FLOORING, TO BE DETERMINED IN THE FIELD. NO
 INFORMATION WAS SUBMITTED ABOUT THE NEW FLOOR FINISHES
 TO BE INSTALLED A SEPARATE PERMIT OR REVISION WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH:
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-25 Cont ID  
Sent By jpearson Date 2019-04-25 Time 09:54 Rev Time 0.00
Received By jpearson Date 2019-04-25 Time 08:44 Sent To  
Notes
2019-04-25 09:54:15PASSED WITH PROVISO ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-07 Cont ID  
Sent By jpearson Date 2019-02-07 Time 15:53 Rev Time 0.00
Received By jpearson Date 2019-02-07 Time 11:23 Sent To I
Notes
2019-02-07 15:53:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONE PERSON SHOULD TAKE RESPONSIBILITY FOR ELECTRICAL
 PLAN. THERE ARE 2 IDENTICAL SHEETS, ONE SIGNED/SEALED
 BY THE AOR, AND ONE SIGNED BY THE ELECTRICAL
 CONTRACTOR. DECIDE WHICH PLAN WILL BE SUBMITTED FOR
 REVIEW AND REMOVE OTHER SHEET. WPB FBC 107.1
 2. PLANS SHOW ITEMS ON DEMOLITION PLAN AS BEING
 REMOVED, AND THEN SHOW THE SAME ITEMS ON FLOOR PLAN AS
 EXISTING. ARE THESE ITEMS BEING DEMOLISHED OR NOT? PLAN
 NEEDS TO REFLECT THE WORK PROPOSED. PROVIDE SCOPE OF
 WORK DESCRIPTION AND PLAN TO MATCH. WPB FBC 107.2.1
 3. PROVIDE A MORE CLEAR REPRESENTATION OF THE LOCATION
 OF ELECTRICAL PANELS. OVERCURRENT PROTECTIVE DEVI ES
 ARE NOT PERMIITED IN CLOTHES CLOSETS AND IT IS NOT
 POSSIBLE TO DETERMINE THE LOCATION OF THE PANELS FROM
 THIS DRAWING. WPB FBC 107.2.1; NEC 240.24(D)
 4. THERE ARE KEYNOTES LISTED THAT DO NOT APPEAR ON
 PLAN, SUCH AS KEYNOTE 7. THERE ARE KEYNOTES LISTED THAT
 DO NOT PERTAIN TO ELECTRICAL ITEMS AND SHOULD BE
 REMOVED FROM ELECTRICAL PLAN, SUCH AS KEYNOTE 9.
 PROVIDE CLARIFICATIONS AND/OR CORRECTIONS. WPB FBC
 107.2.1
 5. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC EX 607.1.1
 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1)
 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-09 Cont ID  
Sent By scaldero Date 2019-04-09 Time 11:14 Rev Time 0.00
Received By scaldero Date 2019-04-09 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-10 Cont ID  
Sent By scaldero Date 2019-01-10 Time 11:21 Rev Time 0.00
Received By scaldero Date 2019-01-10 Time 11:15 Sent To  
Notes
2019-01-10 11:20:57PERMIT # 19010039
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-25 Cont ID  
Sent By pvalenti Date 2019-04-25 Time 16:54 Rev Time 0.00
Received By pvalenti Date 2019-04-01 Time 09:23 Sent To  
Notes
2019-04-03 09:23:15B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-02-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-02 Time 10:23 Sent To  
Notes
2019-01-04 10:23:44B12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-01-30 Cont ID  
Sent By jwitmer Date 2019-01-30 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2019-01-30 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-04-25 Cont ID  
Sent By ccole Date 2019-04-25 Time 11:45 Rev Time 0.00
Received By ccole Date 2019-04-25 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By ccole Date 2019-02-05 Time 13:15 Rev Time 0.00
Received By ccole Date 2019-02-05 Time 13:14 Sent To  
Notes
2019-02-05 13:15:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010039
 2/5/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL/HVAC
 ALTERATIONS WITH CORRESPONDING DRAWINGS AND DETAILS-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 15:35 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-31 Cont ID  
Sent By gjohnson Date 2019-01-31 Time 06:42 Rev Time 0.00
Received By gjohnson Date 2019-01-31 Time 06:42 Sent To  
Notes
2019-01-31 06:43:10 
  
 1ST REVIEW: 19010039
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PLUMBING FLOOR PLAN CLEARLY SHOWING
 SCOPE OF PLUMBING WORK BEING DONE AND LOCATION OF WATER
 HEATER. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE A WATER AND SANITARY ISOMETRIC DRAWING FOR
 RELOCATED WASHING MACHINE.PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]