Plan Review Stops For Permit 19010015 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2019-01-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-01-09 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-01-09 |
Time |
14:52 |
Sent To |
|
|
Notes |
2019-01-09 15:38:28 | PER CONVERSATIONS WITH ARCHITECT, OWNER, AND ROBERT | | BROWN, BUILDING OFFICIAL: | | EGRESS THROUGH THE BREWING AREA WILL BE ALLOWED FOR | | THIS PERMIT FOR THE FOLLOWING REASONS: | | THE ASSEMBLY AREA IS IN THE SAME ROOM AS THE BREWING | | EQUIPMENT | | THE VESSELS WHICH ARE HEATED ARE NOT ADJACENT TO THE | | EGRESS PATH | | THE NEW EGRESS PATH IS APPROXIMATELY 14' WIDE (MORE | | THAN SUFFICIENT FOR OCCUPANT LOAD) | | | | SAMANTHA HILL | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2019-01-04 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2019-01-04 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2019-01-04 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-01-18 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-18 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-16 |
Time |
08:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-01-15 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-01-02 |
Time |
10:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2019-01-18 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-01-18 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-01-18 |
Time |
12:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2019-01-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-01-15 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-01-15 |
Time |
13:27 |
Sent To |
|
|
Notes |
2019-01-15 13:52:38 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19010015 | | 1/15/19 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) MANUFACTURER'S SPECIFCATIONS FOR THE BREWHOUSE WERE | | NOT SUBMITTED. PLEASE SUBMIT THE SPECS WITH DIAGRAMS | | AND PRODUCT DATA INDICATING THE DESIGN AND OPERATING | | PRESSURE AND TEMPERATURE OF THE BREWHOUSE, AND LISTING | | AND LABELING. | | | | 2) PLEASE SUBMIT SPECS FOR THE BREWHOUSE VENT PIPE AND | | ROOF CAP, AND PROVIDE A DIAGRAM THAT SHOWS THE TOTAL | | RUN LENGTH OF THE VENT FROM THE TANK TO TERMINATION | | ABOVE THE ROOF- SEE TABLE 504.2(1) FBC FG. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-01-18 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-18 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-18 |
Time |
13:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-01-09 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-09 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-09 |
Time |
17:09 |
Sent To |
|
|
Notes |
2019-01-09 17:38:17 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | PROVIDE REVISED PLUMBING FLOOR PLAN AND ISOMETRIC | | DRAWINGS. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-01-18 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-18 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2019-01-18 13:21:39 | MECH SIGNATURES OK |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-01-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-01-14 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-01-14 |
Time |
11:19 |
Sent To |
|
|
Notes |
2019-01-14 11:20:01 | DIGITAL SIGNATURES OK | | NEW PAGES SUBMITTED 2ND REVIEW REQUIRE VERIFICATION | | | | S. HILL | | 561-805-6724 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2019-01-10 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2019-01-10 |
Time |
|
Rev Time |
|
Received By |
awooten |
Date |
2019-01-10 |
Time |
|
Sent To |
|
|
Notes |
2019-01-10 16:41:09 | APPROVED PER ZBA CASE 3360 | | | | ALANA WOOTEN | | PLANNING DIVISION | | 561-822-1449 | | [email protected] |
|
|