Plan Review Details - Permit 18120902
Plan Review Stops For Permit 18120902
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-30 Cont ID  
Sent By hmoser Date 2019-01-30 Time 06:26 Rev Time 0.00
Received By hmoser Date 2019-01-23 Time 16:29 Sent To I
Notes
2019-01-24 16:29:38RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-10 Cont ID  
Sent By hmoser Date 2019-01-10 Time 14:19 Rev Time 0.00
Received By hmoser Date 2019-01-08 Time 15:22 Sent To  
Notes
2019-01-08 15:22:42RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-31 Cont ID  
Sent By hmoser Date 2018-12-31 Time 14:18 Rev Time 0.00
Received By hmoser Date 2018-12-27 Time 10:31 Sent To  
Notes
2018-12-28 10:32:05ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-30 Cont ID  
Sent By hmoser Date 2019-01-29 Time 14:28 Rev Time 0.00
Received By hmoser Date 2019-01-29 Time 14:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-01-10 Cont ID  
Sent By hmoser Date 2019-01-10 Time 14:06 Rev Time 0.00
Received By hmoser Date 2019-01-10 Time 14:06 Sent To I
Notes
2019-01-10 14:19:06PLAN DENIED
 1) CAN NOT EXCEPT COPIES OF ENGINEER PLANS
 NEED ORIGINAL PLAN.
 2) VALUE ON JOB IS TO LOW FOR COOLER. COOLER MUST BE
 ADDED
 IN THE VALUE OF THE JOB WITH LABOR.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-31 Cont ID  
Sent By hmoser Date 2018-12-31 Time 14:17 Rev Time 0.00
Received By hmoser Date 2018-12-31 Time 13:45 Sent To I
Notes
2018-12-31 14:17:36PLAN DENIED
 1) PROVIDE PRODUCT APPROVALS ON COOLER/FREEZER
 SECTION 107 FBC 2017
 2) COOLER/FREEZER IS OUTSIDE, PROVIDE WIND
 CALCULATIONS.
 PER SECTION 301.15 WIND RESISTANCE. 2017 MECHANICAL
 CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-8058-6676
  
  