Plan Review Details - Permit 18120893
Plan Review Stops For Permit 18120893
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-14 Cont ID  
Sent By jduprey Date 2019-02-14 Time 16:35 Rev Time 0.00
Received By jduprey Date 2019-02-14 Time 16:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-28 Cont ID  
Sent By jduprey Date 2019-01-28 Time 15:24 Rev Time 0.00
Received By jduprey Date 2019-01-28 Time 14:44 Sent To  
Notes
2019-01-28 15:24:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE DRAWING SHEET "SITE" NOTE #4 INDICATES THE
 CONSTRUCTION DOCUMENTS HAVE BEEN PREPARED IN ACCORDANDE
 WITH FBC 2014. THE CURRENT CODE IS THE FBC 2017. PLEASE
 REVISED THE DOCUMENTS PREPARED UNDER FBC 2014 MEET THE
 FBC 2017 REQUIREMENTS.
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 2. DOORS & WINDOWS:
 2A. FOR THE EAST ELEVATION AND NORTH ELEVATION DOORS IS
 NOT CLEAR WICH PRODUCT IS GOING TO BE USED. PLEASE
 INDICATE OR PROVIDE THE PRODUCT APPROVAL FOR THIS DOOR.
 FBC 107
 2B. PLEASE PROVIDE THE FOLLOWING INFORMATION:
  
 WINDOWS WITH DIMENSIONS OF ROUGH OPENINGS. IF NO
 CHANGES ARE TO BE MADE TO THE ROUGH OPENINGS, PROVIDE
 STATEMENT THAT WINDOWS WILL BE LIKE FOR LIKE. IF
 OPENINGS ARE ALTERED, PROVIDE FRAMING PLAN PER FBCR
 CHAPTER 6.
  
 IDENTIFY THE EGRESS WINDOW AND PROVIDE DIMENSION FROM
 THE FINISH FLOOR TO THE WINDOWS SILL. FBC 107; FBC 1030
  
 3. THE FOUNDATION PLAN INDICATES NEW FOOTINGS WITH
 AUGER CAST PILES DESIGN THAT WILL BE PART OF THE NEW
 STRUCTURAL SYSTEM. PLEASE PROVIDE THE CALCULATIONS,
 GEOTECHNICAL REPORT RECOMENDATION FOR THE FOUNDATIONS
 AND/OR MORE SPECIFIC DETAILS IN REGARDS THE AUGER CAST
 PILE FOUNDATIONS OF THIS NEW STRUCTURAL SYSTEM. WILL BE
 HELPFUL IF AN EXISTING FOUNDATION PLAN CAN BE PROVIDED.
 FBC 107
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-14 Cont ID  
Sent By jpearson Date 2019-02-14 Time 15:57 Rev Time 0.00
Received By jpearson Date 2019-02-14 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-10 Cont ID  
Sent By jpearson Date 2019-01-10 Time 11:06 Rev Time 0.00
Received By jpearson Date 2019-01-09 Time 17:01 Sent To  
Notes
2019-01-10 11:06:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A DISCONNECT NEXT TO METER, A
 MAIN PANEL, AND A SUB-PANEL. ON THE FLOOR PLAN, THERE
 IS ONLY A METER CAN AND SUB-PANEL SHOWN. WHERE IS THE
 MAIN PANEL LOCATED? PANEL SCHEDULE FOR MAIN PANEL SAYS
 THAT IT IS 200 AMP, BUT RISER DIAGRAM SHOWS IT AS 150
 AMP. PROVIDE CLARIFICATION AND/OR CORRECTIONS TO
 CLEARLY SHOW LOCATIONS OF ALL PANELS AND A CORRECT
 RISER DIAGRAM. NEC 215.5, 230, 250.50, 250.94, 408.30;
 FBC RE E3706.1, E3608.1, E3609.3; WPB FBC 107.2.1
 2. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 4. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 5. AT LEAST ONE RECEPTACLE OUTLET MUST BE INSTALLED IN
 GARAGE FOR EACH MOTOR VEHICLE SPACE. PROVIDE
 CORRECTION. FBC RE E3901.9
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 7. SMOKE ALARM REQUIRED IN LIVING ROOM AS IT IS A ROOM
 THAT CAN BE USED FOR SLEEPING PURPOSES. PROVIDE
 CORRECTION. FBC RE R314.3
 8. FOR DOWNSTAIRS BATH, A GFCI PROTECTED RECEPTACLE
 OUTLET ON A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF
 BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D);
 FBC RE E3703.4, E3901.6
 9. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 10. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION FOR GYM DOOR. NEC
 210.70(A)(2)(B), FBC RE E3903.3
 11. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE
 OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING
 UNIT. NEC 210.52(E)(3); FBC RE E3901.7
 12. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status N Date 2019-02-15 Cont ID  
Sent By dharvey Date 2019-02-15 Time 15:25 Rev Time 0.00
Received By dharvey Date 2019-02-15 Time 15:25 Sent To  
Notes
2019-02-15 15:25:40PREVIOUSLY PASSED

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-01-04 Cont ID  
Sent By fmittner Date 2019-01-04 Time 10:55 Rev Time 0.00
Received By fmittner Date 2019-01-04 Time 10:55 Sent To  
Notes
2019-01-04 10:56:13- SECOND FLOOR WINDOWS TO HAVE MULL BAR AND SILLS TO
 MATCH ORIGINAL
 - GARAGE DOOR TO BE IN ORIGINAL LOCATION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-15 Cont ID  
Sent By dharvey Date 2019-02-15 Time 15:25 Rev Time 0.00
Received By dharvey Date 2019-02-11 Time 11:28 Sent To  
Notes
2019-02-12 11:28:13R27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-29 Cont ID  
Sent By hmoser Date 2019-01-29 Time 10:47 Rev Time 0.00
Received By hmoser Date 2018-12-27 Time 10:58 Sent To  
Notes
2018-12-28 10:58:31R06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By hmoser Date 2019-02-15 Time 09:00 Rev Time 0.00
Received By hmoser Date 2019-02-15 Time 08:57 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By hmoser Date 2019-01-29 Time 10:47 Rev Time 0.00
Received By hmoser Date 2019-01-29 Time 10:35 Sent To  
Notes
2019-01-29 10:47:03MECHANICAL PLAN REVIEW
  
 APPROVAL IS PENDING:
  
 1. FBC R M1401.3 PROVIDE ENERGY CALCULATIONS.
 2. CITY OF WPB LOCAL AMENDMENTS 107 PROVIDE EQUIPMENT
 SCHEDULE ON MECHANICAL PAGE OF PLANS.
 3. CITY OF WPB LOCAL AMENDMENTS 107 PROVIDE
 CLARIFICATION OF DUCT SIZE. PLANS INDICATE 7" AND 6" ON
 THE SAME SECTION OF DUCTWORK FOR THE KITCHEN DROP.
 4. FBC R M1307.2 PROVIDE ENGINEERING FOR EXTERIOR
 CONDENSING UNIT TIE-DOWN ATTACHMENTS.

Review Stop P PLUMBING
Rev No 2 Status N Date 2019-02-15 Cont ID  
Sent By dharvey Date 2019-02-15 Time 15:26 Rev Time 0.00
Received By dharvey Date 2019-02-15 Time 15:26 Sent To  
Notes
2019-02-15 15:26:10PREVIOUSLY PASSED

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-22 Cont ID  
Sent By gjohnson Date 2019-01-22 Time 14:47 Rev Time 0.00
Received By gjohnson Date 2019-01-22 Time 11:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-01-04 Cont ID  
Sent By fmittner Date 2019-01-04 Time 10:56 Rev Time 0.00
Received By fmittner Date 2019-01-04 Time 10:56 Sent To  
Notes
***NONE***