Plan Review Details - Permit 18120892
Plan Review Stops For Permit 18120892
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-06-12 Cont ID  
Sent By jgomez Date 2019-06-12 Time 10:59 Rev Time 0.00
Received By jgomez Date 2019-06-12 Time 09:58 Sent To  
Notes
2019-06-12 10:49:21PROVISO (PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTIONS):
 1-PROVIDE PRODUCT APPROVAL (APPROVED BY THE ENGINEER OF
 RECORD) FOR:
 (A)EXTERIOR WINDOWS.
 (B)EXTERIOR DOORS.
 (C)ROOFING PRODUCT FOR SPECIFIC ASSEMBLY TO BE
 INSTALLED.
  
 2- WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-23 Cont ID  
Sent By jgomez Date 2019-05-23 Time 10:37 Rev Time 0.00
Received By jgomez Date 2019-05-22 Time 19:01 Sent To  
Notes
2019-05-22 19:01:48PROVISO (PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSPECTIONS):
 1-PROVIDE PRODUCT APPROVAL (APPROVED BY THE ENGINEER OF
 RECORD) FOR:
 (A)EXTERIOR WINDOWS.
 (B)EXTERIOR DOORS.
 (C)ROOFING PRODUCT FOR SPECIFIC ASSEMBLY TO BE
 INSTALLED.
  
 2- WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By jgomez Date 2019-04-19 Time 15:01 Rev Time 0.00
Received By jgomez Date 2019-04-19 Time 13:34 Sent To  
Notes
2019-04-19 15:01:502017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120892
 ADD: 4375 EASLEY DR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-835-7406
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 28/2019
 ACTION: DENIED
  
 1) OK.
  
 2) OK.
  
 ORIGINAL COMMENT:
 3) THE SHEET 023-S-2 UNDER THE HEADING OF FOUNDATIONS
 NOTE # 1 INDICATES THERE IS A SOILS REPORT PREPARED BY
 FEDERAL ENGINEERING AND TESTING, DATED AUGUST 24, 2018.
 PLEASE SUBMIT A PAPER ORIGINAL SIGNATURE AND SEALED OR
 SUBMIT ELECTRONICALLY WITH AN ELECTRONIC SIGNATURE.
  
 RESPONSE:
 SOIL TEST REPORT SUBMITTED DOESN'T HAVE A DIGITAL
 SIGNATURE. UPLOAD REPORT WITH ENGINEER'S DIGITAL
 SIGNATURE OR SUBMIT HARD COPIES WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
  
 4A) OK.
  
 4B) OK.
  
 5) PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVICE IF SUBMITTING PRODUCT
 APPROVALS AS DEFERRED SUBMITTAL. PROVIDE COMPLETE
 INFORMATION PRIOR TO INSTALLATION TO AVOID
 CONFLICTS/DELAYS. ALL PRODUCT APPROVALS NEED TO BE
 APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL)
  
 (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE AND OR INSULATION,
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) OK. NOTED ON DRAWINGS.
 THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE THE
 ADDITION IS TO HAVE A BAR JOIST AND METAL DECK ROOF
 SYSTEM. PLEASE HAVE A 3RD PARTY ENGINEER REVIEW ALL
 WELDED JOINTS AND BOLTED JOINTS AND SUPPLY A SIGNED AND
 SEALED LETTER OF THE INSPECTIONS AT THE TIME OF THE
 WINDOW BUCK INSPECTION AND BEFORE THE INTERIOR FRAMING
 INSPECTION. IF THERE IS ANY QUESTIONS IN REGARDS TO
 BUILDING INSPECTIONS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666.
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 10) NEW COMMENTS ON ENERGY CALCULATIONS:
 A) NEED ARCHITECT'S NAME AND LICENSE NUMBER ON THE
 ENERGY CALCULATIONS. SEE FOOTNOTE ON CERTIFICATIONS
 PAGE. ALSO. SEE SEC. C103.1.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B) NEED THE OWNER'S OR OWNER'S AUTHORIZED AGENT TO
 CERTIFY THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 C103.1.1.2 FBC-ENERGY CONSERVATION
  
  
 11) OK.
  
  
 12) OK.
  
 13) OK.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-28 Cont ID  
Sent By jwitmer Date 2019-01-28 Time 10:06 Rev Time 0.00
Received By jwitmer Date 2019-01-24 Time 09:59 Sent To  
Notes
2019-01-28 10:06:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120892
 ADD: 4375 EASLEY DR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-835-7406
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 28/2019
 ACTION: DENIED
  
 1) IN REVIEWING THE COVERSHEET THE LIFE SAFETY SHEET
 005-A-020 THE PLANS INDICATE THE BUILDING AND ADDITION
 IS TO BE FIRE SPRINKLERED. PLEASE SUBMIT FIRE SPRINKLER
 PLANS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING.
 107.3.51.1. (5.) FIRE SUPPRESSION SYSTEMS SHALL
 INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 PRE-ENGINEERED SYSTEMS CAN BE SHOP DRAWINGS UNDER A
 SEPARATE PERMIT.
  
 FIRE SPRINKLERS 61G15-32.004 DESIGN OF WATER BASED FIRE
 PROTECTION SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE: (A-M).
  
 2) THE COVERSHEET LIST THE TOTAL UNDER ROOF SQUARE FEET
 OF THE BUILDING AS 7,675 SQ. FT. THE NEW LAB IN ITSELF
 IS OVER THE 10% OF THE BUILDING. THE EXISTING LAB WOULD
 APPEAR TO BE AROUND 600 SQ. FT. OR A TOTAL AREA OF
 1,949 SQ. FT. WHICH HAS OR COULD HAVE HAZARDOUS
 CHEMICALS. PLEASE PROVIDE THE CHEMICALS TO BE USED IN
 THE LAB AND MSDS SHEETS, AMOUNT OF CHEMICALS THAT ARE
 TO BE USED IN EACH OF THE LAB AREAS, IF THE CHEMICALS
 ARE TO BE STORED IN 1 HOUR RATED FIRE CABINETS. THE
 PLANS FAIL TO SHOW A FIRE SEPARATION (FIRE BARRIERS)
 FOR CONTROL AREAS FROM THE REMAINDER OF THE BUILDING.
  
 2017 FBC-B 307.1 HIGH-HAZARD GROUP H OCCUPANCY
 INCLUDES, AMONG OTHERS, THE USE OF A BUILDING OR
 STRUCTURE, OR A PORTION THEREOF, THAT A PHYSICAL OR
 HEALTH HAZARD IN QUANTITIES IN EXCESS OF THOSE ALLOWED
 IN CONTROL AREAS COMPLYING WITH SECTION 414, BASED ON
 THE MAXIMUM ALLOWABLE QUANTITY LIMITS FOR CONTROL AREAS
 SET FORTH IN TABLES 307.1(1) AND 307.1(2).
 PLEASE SEE SECTION 414.2 OF THE 2017 FBC-B FOR CONTROL
 AREAS.
  
 3) THE SHEET 023-S-2 UNDER THE HEADING OF FOUNDATIONS
 NOTE # 1 INDICATES THERE IS A SOILS REPORT PREPARED BY
 FEDERAL ENGINEERING AND TESTING, DATED AUGUST 24, 2018.
 PLEASE SUBMIT A PAPER ORIGINAL SIGNATURE AND SEALED OR
 SUBMIT ELECTRONICALLY WITH AN ELECTRONIC SIGNATURE.
  
 4A) PLEASE REVIEW SHEET 023-S-2 THE NEGATIVE VALUES
 (PRESSURES) FOR VULT AND VASD ARE THE SAME THE VASD
 VALUES SHOULD BE MULTIPLIED BY THE 0.6 TO BECOME VASD.
 2017 FBC-B 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 THE WALL NEGATIVE PRESSURES ALSO APPEAR FOR THE WALL
 ALSO APPEAR 3.5 LBS. LOW PRESSURES ARE TAKEN AT 15 FEET
 ABOVE GRADE, THAT IS THE LAST PRESSURE GIVEN IN THE
 TABLES IN 1609 AND IN ASCE 7-10.
  
 4B) PRESSURES (NEGATIVE) GIVEN ON SHEET 012-A-200 FOR
 THE WALL ALSO APPEAR 3.5 LBS. LOW PRESSURES ARE TAKEN
 AT 15 FEET ABOVE GRADE THAT IS THE LAST PRESSURE GIVEN
 IN THE TABLES IN 1609 AND IN ASCE 7-10.
  
 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE AND OR INSULATION,
  
 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE THE
 ADDITION IS TO HAVE A BAR JOIST AND METAL DECK ROOF
 SYSTEM. PLEASE HAVE A 3RD PARTY ENGINEER REVIEW ALL
 WELDED JOINTS AND BOLTED JOINTS AND SUPPLY A SIGNED AND
 SEALED LETTER OF THE INSPECTIONS AT THE TIME OF THE
 WINDOW BUCK INSPECTION AND BEFORE THE INTERIOR FRAMING
 INSPECTION. IF THERE IS ANY QUESTIONS IN REGARDS TO
 BUILDING INSPECTIONS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666.
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 10) ENERGY CODE. THE APPLICANT HAS SUBMITTED THE ENERGY
 GAUGE SUMMIT ASHRAE 90.1 ENERGY COST BUDGET OPTION OF
 CODE COMPLIANCE FOR ENERGY. THE QUESTION THAT I HAVE IS
 ON THE INPUT DATA REPORT PAGE 2 FOR THE EXTERIOR WALLS
 THE REPORT SHOWS WIDTH AND HEIGHT (EFFECTIVE) OF THE
 WALLS. THE QUESTION IS THE HEIGHT OF THE WALL IS GIVEN
 AT 9 FEET AND ON SHEET A-220 ALL OF THE DETAILS SHOW
 THE EXTERIOR WALL INSULATION GOING UP TO 9 FEET THE
 HEIGHT OF THE DROPPED CEILING, WHEREAS THE ROOF TOP
 INSULATION IS GIVEN AT A HEIGHT OF 12 FOOT 3 INCHES.
 PLEASE PROVIDE WHY THE EXTERIOR WALL INSULATION OR THE
 EXTERIOR SOFFIT AND FACIA WOULD NEED TO COMPLETE THE
 INSULATION TO THE ROOF LINE, TO MAKE A COMPLETE
 ENVELOPE?
  
 2017 FBC-ENERGY CODE C304.3.2.2 APPLICANT-DETERMINED
 ASSEMBLY U-FACTORS, C-FACTORS, F-FACTORS OR HEAT
 CAPACITIES. IF THE BUILDING OFFICIAL DETERMINES THAT
 THE PROPOSED CONSTRUCTION ASSEMBLY IS NOT ADEQUATELY
 REPRESENTED IN THE APPROPRIATE TABLE OF ASHRAE 90.1
 NORMATIVE APPENDIX A, THE APPLICANT SHALL DETERMINE
 APPROPRIATE VALUES FOR THE ASSEMBLY USING THE
 ASSUMPTIONS IN ASHRAE 90.1 NORMATIVE APPENDIX A.
  
 11A) THE ROOF PLAN, SHEETS 011-A-110, 039-P1.2 AND
 013-A-220 ALL REPRESENT THE ROOF PLAN. THE SHEET P1.2
 DOES GIVE THE ROOF AREA AND PARAPET TO BE DRAINED AND
 THE SIZE OF THE VERTICAL LEADERS. WHAT IS MISSING IS
 THE ANNUAL RAIN FALL. SEE 1503.4 ROOF DRAINAGE OF THE
 2017 FBC-B. UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF
 EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE SYSTEMS
 SHALL COMPLY WITH SECTION 1503 AND THE FLORIDA BUILDING
 CODE, PLUMBING, CHAPTER 11.
  
 11B) PLEASE REVIEW SHEET 011-A-110 THE ROOF PLAN.
 DETAIL 3 INDICATES THE NEW ROOF LINE IS IN AT A HIGHER
 ELEVATION THAN THE OLD ROOF. WHEN VIEWING THE EXISTING
 ROOF LINE IN DETAIL 1 IN THE END VIEW OF THE ROOF IT
 APPEARS THAT THERE IS 2 EMERGENCY OVERFLOW SCUPPERS
 THAT WILL BE NO LONGER EFFECTIVE SINCE THE NEW ROOF
 LINE IS HIGHER? HOW OR WHERE WILL THE EMERGENCY
 OVERFLOWS BE LOCATED IN THE EXISTING ROOF?
  
 2017 FBC-B 1503.4.1 SECONDARY (EMERGENCY OVERFLOW)
 DRAINS OR SCUPPERS. WHERE ROOF DRAINS ARE REQUIRED,
 SECONDARY (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS
 SHALL BE PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION
 EXTENDS ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL
 BE ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR
 ANY REASON. THE INSTALLATION AND SIZING OF SECONDARY
 EMERGENCY OVERFLOW DRAINS, LEADERS AND CONDUCTORS SHALL
 COMPLY WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF
 THE FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11.
  
 12) SHEET 015-A-401 DETAILS 3 AND 6 .
 12A) DETAIL 3 SHOWS EITHER POWER DRIVEN FASTENER OR
 EXPANSION ANCHOR BEING INSTALLED INTO THE BOTTOM OF AN
 EXISTING PRE-CAST ROOF JOIST. PLEASE GET THE STRUCTURAL
 ENGINEER TO SIGN OFF ON THIS APPLICATION SINCE THE
 BOTTOM REINFORCING MAYBE ENDANGERED OR CONCRETE MAYBE
 CHIPPED OR CRACKED EXPOSING THE BOTTOM CHORD OF
 INFORCEMENT. 107.2.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, STRESS
 DIAGRAMS, AND OTHER DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE BASIS OF
 CALCULATIONS. ALL DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA REQUIRED BY THE BUILDING OFFICIAL TO
 BE PREPARED BY AN ARCHITECT OR ENGINEER SHALL BE
 AFFIXED WITH THEIR OFFICIAL SEAL, SIGNATURE AND DATE AS
 STATE LAW REQUIRES.
  
 12B) PLEASE REVIEW DETAIL 6 OF THE SAME SHEET. HIGH HAT
 IS TO BE APPLIED TO THE CORNER OF AN EXISTING BEAM, THE
 PLANS SHOW ONE PIECE OF HIGH-HAT FLANGE AT THE CORNER
 OF THE BEAM THERE IS NO MENTION OF HOW TO ANCHOR THE
 HIGH HAT AND WHAT DISTANCE TO STAY AWAY FROM THE CORNER
 TO KEEP FROM THE CONCRETE FROM SPAWLING. . 107.2.1.2
 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY REQUIRE
 DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 AND THE BASIS OF CALCULATIONS. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA REQUIRED BY THE
 BUILDING OFFICIAL TO BE PREPARED BY AN ARCHITECT OR
 ENGINEER SHALL BE AFFIXED WITH THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE AS STATE LAW REQUIRES.
  
 13) THE VALUE OF THE PROJECT WAS REDUCED FROM
 $1,686,678.00 TO $300,000.00 IN VALUE. PLEASE PROVIDE
 AN ITEMIZED LIST TO SEE WHAT WAS REMOVED FROM THE
 PROJECT VALUE, INCLUDE THE LINE ITEM VALUE FOR EACH
 ITEM REMOVED.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-17 Cont ID  
Sent By jpearson Date 2019-04-17 Time 14:42 Rev Time 0.00
Received By jpearson Date 2019-04-17 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By jpearson Date 2019-01-29 Time 10:21 Rev Time 0.00
Received By jpearson Date 2019-01-29 Time 10:21 Sent To  
Notes
2019-01-29 10:20:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTION FOR RECEPTACLE OUTLETS
 LOCATED IN BATHROOM. NEC 210.8
 2. PROVIDE DISCONNECTING MEANS FOR NEW 45KVA
 TRANSFORMER PER NEC 450.14.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-09 Cont ID  
Sent By pleduc Date 2019-05-09 Time   Rev Time 0.00
Received By pleduc Date 2019-05-09 Time 11:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-08 Cont ID  
Sent By pleduc Date 2019-04-08 Time   Rev Time 0.00
Received By pleduc Date 2019-03-29 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-09 Cont ID  
Sent By pleduc Date 2019-01-09 Time   Rev Time 0.00
Received By pleduc Date 2019-01-09 Time 11:02 Sent To  
Notes
2019-01-09 15:48:48THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE IS AN INCORRECT(2014 5TH ED.) TO THE CURRENT
 FLORIDA FIRE PREVENTION CODE. THE CURRENT CODE
 REFERENCE IS 2017 6TH ED.
  
 PLEASE REVIEW AND ENSURE COMPLAINCE.
  
 PLEAS UPDATE YOUR RECORDS FOR FUTURE SUBMITTALS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 12:07 Rev Time 0.00
Received By shill Date 2019-07-09 Time 13:32 Sent To  
Notes
2019-07-19 08:24:041. IRRIGATION AND LANDSCAPE PLANS NOT DIGITALLY SIGNED
 IT SHALL BE DIGITALLY SIGNED OR ONE COPY SUBMITTED AND
 REVIEWED AT THE BUILDING DEPARTMENT. PER FAC
 61G1-16.005
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-06-12 Cont ID  
Sent By jgomez Date 2019-06-12 Time 11:00 Rev Time 0.00
Received By jgomez Date 2019-05-23 Time 08:31 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-23 Cont ID  
Sent By lmarchan Date 2019-05-23 Time 15:02 Rev Time 0.00
Received By lmarchan Date 2019-05-03 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-23 Cont ID  
Sent By cpuell Date 2019-04-23 Time 14:16 Rev Time 0.00
Received By cpuell Date 2019-03-28 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-01-29 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-07 Time 15:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-01-28 Cont ID  
Sent By jwitmer Date 2019-01-28 Time 10:07 Rev Time 0.00
Received By jwitmer Date 2019-01-24 Time 09:59 Sent To  
Notes
2019-01-28 10:07:21NOT REQUIRED A GOVERNMENTAL PROJECT. NO IMPACT FEES.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-13 Cont ID  
Sent By ccole Date 2019-05-13 Time 17:06 Rev Time 0.00
Received By ccole Date 2019-05-13 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-15 Cont ID  
Sent By ccole Date 2019-04-15 Time 16:09 Rev Time 0.00
Received By ccole Date 2019-04-15 Time 16:09 Sent To  
Notes
2019-04-15 17:17:142ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18120892
 4/15/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A2.0 & M1.1: MISSING FIRE DAMPERS FOR THE 8/8
 TRANSFER DUCT AND THE 22/14 O/A DUCT PENETRATING THE
 FIRE-RATED CHEM STORAGE ROOM WALLS- SECTION 607.5.2 FBC
 M.
  
 2) A2.0 & M1.1: THE 6/6 EXHAUST DUCT FROM THE CHEM
 STORAGE ROOM MUST BE ENCLOSED IN FIRE-RESISTANT
 CONSTRUCTION FROM THE POINT OF THE FIRE-RATED WALL
 PENETRATION TO THE OUTLET TERMINAL- SECTION 510.7.3 FBC
 M.
  
 3) A100, A603, & M1.1: AS PREVIOUSLY NOTED, IT APPEARS
 THAT AIR IS BEING RECIRCULATED VIA TRANSFER GRILLS FROM
 THE SOLID ROOM INTO THE HALLWAY WHICH IS PROHIBITED-
 SEE TABLE 403.3.1.1 FOOTNOTE G- RECIRCULATION OF AIR
 FROM THE LAB ROOMS IS PROHIBITED WITH THE EXCEPTION OF
 10% OF THE AIRSTREAM FROM THE SPACES IS PERMITTED TO BE
 RECIRCULATED. THE ROOM IS NOT LABELED "LAB" HOWEVER
 THERE IS A FUME HOOD IN THE ROOM AND OTHER PROCESSING
 EQUIPMENT AND OVENS.
  
 4) A100, A603, & M1.1: SHOW THE EXHAUST DUCT RUN AND
 TERMINATION LOCATION FOR THE EXHAUST HOOD IN THE
 MICROBIOLOGY ROOM- SECTION 510.6.7 FBC M.
  
 5) A100, A603, & M1.1: PLEASE PROVIDE A NARRATIVE THAT
 DESCRIBES THE PROCESSES THAT OCCUR UNDER THE HOODS IN
 THE LAB, SOLIDS, AND MICROBIOLOGY ROOMS. A) PROVIDE A
 SEQUENCE OF OPERATION THAT INCLUDES HOW MAKE UP AIR
 WILL BE AUTOMATICALLY PROVIDED- SECTION 510.6.5 FBC M
 B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE HOODS, FANS, AND
 EXHAUST DUCTWORK- SECTIONS 304.1 & 510.6.3 FBC M.
  
 6) M1.100: VERIFY ALL EXHAUST OUTLET CLEARANCES ARE IN
 COMPLIANCE WITH SECTION 501.3.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By ccole Date 2019-01-22 Time 16:51 Rev Time 0.00
Received By ccole Date 2019-01-22 Time 16:51 Sent To  
Notes
2019-01-22 17:47:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120892
 1/22/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M1.1 & M2.1: EXHAUST VENTILATION AT A RATE OF
 1.0 CFMS PER SF. IS REQUIRED FOR THE LAB ROOMS- TABLE
 403.3.1.1 FBC M. PLEASE PROVIDE THE CALCULATIONS AND
 THE REQUIRED EXHAUST SYSTEMS. THE ROOMS REQUIRING
 EXHAUST VENTILATION ARE THE EXISTING LAB, THE SOLID
 ROOM, AND THE MICROBIOLOGY ROOM. THE CURRENT PLAN SHOWS
 EXHAUST DUCTS IN THE LAB AND THE SOLID ROOM BUT NO
 CALCULATIONS OR FAN INFORMATION TO VERIFY COMPLIANCE.
 PLEASE NOTE THAT CHEMICAL FUME HOODS REQUIRE LOCAL
 EXHAUST, BUT THE 1.0 CFM RATE IS REQUIRED FOR THE
 ENTIRE ROOM. IF CHEMICAL FUME HOODS ARE TO BE INSTALLED
 PLEASE PROVIDE EQUIPMENT SCHEDULES AND SHOW THE
 LOCATIONS OF THE HOODS.
  
 2) M1.1: REFER TO TABLE 403.3.1.1 FOOTNOTE G-
 RECIRCULATION OF AIR FROM THE LAB ROOMS IS PROHIBITED
 WITH THE EXCEPTION OF 10% OF THE AIRSTREAM FROM THE
 SPACES IS PERMITTED TO BE RECIRCULATED. THE CURRENT
 PLAN SHOWS RECIRCULATED AIR FROM THE LABS INTO THE
 ADJACENT OFFICES AND HALLWAY.
  
 3) M1.1: CLARIFY HOW O/A IS BEING PROVIDED TO THE
 SPACES. THERE ARE TWO 22X14" DUCTS RETURNING AIR TO THE
 AIR HANDLERS VIA TWO 42X24" RETURN GRILLES THAT ARE
 SHOWN OUTSIDE THE PERIMETER OF THE SPACES. ARE THESE
 GRILLES MISLABELED?
  
 4) REFER TO SECTION 510.2 FBC M AND VERIFY COMPLIANCE:
 510.2 WHERE REQUIRED.
  
 A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER
 OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF
 HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST
 SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE
 POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS:
  
 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT
 IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER
 FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED
 ROOM TEMPERATURE.
  
 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 4 IS PRESENT IN ANY CONCENTRATION.
  
 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS
 EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION
 OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY.
  
 EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1,
 EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE
 EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A
 HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN
 CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL
 CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION
 TOXICITY.
  
 5) REFER TO SECTION 414.1.3 FBC B.AND PROVIDE THE
 MAXIMUM QUANTITIES OF HAZARDOUS MATERIALS TO BE STORED,
 AND USED IN OPEN OR CLOSED SYSTEMS ETC. PLEASE SUBMIT
 MSDS SHEETS FOR EACH MATERIAL.
  
 6) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE AC CONDENSERS- SECTION 301.15.
  
 7) PROVIDE A LAB EQUIPMENT LAYOUT PLAN AND EQUIPMENT
 SCHEDULE- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2019-04-11 Cont ID  
Sent By gjohnson Date 2019-04-11 Time 11:56 Rev Time 0.00
Received By gjohnson Date 2019-04-11 Time 11:56 Sent To  
Notes
2019-04-11 11:59:46MED GAS PROFISO:
  
  
 . A SEPARATE PERMIT IS REQUIRED FOR MED GAS, ALONG WITH
 THE APPLICATION PROOF OF MED GAS CERTIFICATION FOR THE
 CONTRACTOR AND INSTALLER IS REQUIRED. PER FAC
 61G4-15.031(1)(4)(A)(B)

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-06-05 Cont ID  
Sent By gjohnson Date 2019-06-05 Time 12:46 Rev Time 0.00
Received By gjohnson Date 2019-06-05 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-05-23 Cont ID  
Sent By tklarge Date 2019-05-23 Time 13:56 Rev Time 0.00
Received By tklarge Date 2019-05-23 Time 13:29 Sent To  
Notes
2019-05-23 13:57:07SIGNATURE COULD NOT BE VERIFIEDON THE IRRRIGATION
 PLANS.
2019-05-23 10:13:06IRRIGATION PLANS SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-11 Cont ID  
Sent By gjohnson Date 2019-04-11 Time 11:55 Rev Time 0.00
Received By gjohnson Date 2019-04-11 Time 11:55 Sent To  
Notes
2019-04-11 11:55:45PLUMBING PROVISO:
  
 SHALL COMPLY PRIOR TO FINAL INSPECTION.
  
 1. PROVIDE ISOMETRIC DRAWING FOR STORM DRAIN AND
 OVERFLOW ROOF DRAINS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-28 Cont ID  
Sent By gjohnson Date 2019-01-28 Time 12:10 Rev Time 0.00
Received By gjohnson Date 2019-01-28 Time 12:10 Sent To  
Notes
2019-01-28 12:21:401ST REVIEW: 18120892
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.7 TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 604.2 THE WATER
 CLOSET SHALL BE POSITIONED WITH A WALL OR PARTITION TO
 THE REAR AND TO ONE SIDE. THE CENTERLINE OF THE WATER
 CLOSET SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM
 FROM THE SIDE WALL OR PARTITION.
  
 3. A OVERFLOW ROOF DRAIN OR SCUPPER IS REQUIRED. PER
 FBC PL 1108.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 2 Status P Date 2019-07-19 Cont ID  
Sent By gjohnson Date 2019-07-19 Time 08:24 Rev Time 0.00
Received By gjohnson Date 2019-07-19 Time 08:24 Sent To  
Notes
***NONE***

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By gjohnson Date 2019-06-05 Time 12:47 Rev Time 0.00
Received By gjohnson Date 2019-06-05 Time 12:47 Sent To  
Notes
2019-06-05 12:51:331ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. IRRIGATION PLAN NOT DITGITALLY SIGNED IT SHALL BE
 DIGITALLY SIGNED. PER FAC 61G1-16.005
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2019-07-19 Cont ID  
Sent By shill Date 2019-07-19 Time 12:06 Rev Time 0.00
Received By shill Date 2019-07-19 Time 12:06 Sent To  
Notes
2019-07-19 12:07:13PROVISO: SUBMIT A PAPER ORIIGNAL FOR SHEET IR1
  
 DISCUSSED W/ALBERTO BARBOZA (ARCHITECT'S OFFICE)
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2019-07-19 Cont ID  
Sent By gjohnson Date 2019-07-19 Time 08:21 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2019-06-12 Cont ID  
Sent By jgomez Date 2019-06-12 Time 10:59 Rev Time 0.00
Received By jgomez Date 2019-06-12 Time 10:59 Sent To  
Notes
2019-06-12 11:00:31SHEET A-040 NEED THE DIGITAL SIGNATURE.
2019-06-05 12:53:571. IRRIGATION PLAN NOT DITGITALLY SIGNED IT SHALL BE
 DIGITALLY SIGNED. PER FAC 61G1-16.005 /GPJ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-05-28 Cont ID  
Sent By shill Date 2019-05-28 Time 08:07 Rev Time 0.00
Received By shill Date 2019-05-28 Time 08:07 Sent To  
Notes
2019-05-28 08:08:14PAPER ORIGINALS RECEIVED FOR SOILS TEST & ENERGY CALCS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-05-23 Cont ID  
Sent By jgomez Date 2019-05-23 Time 10:41 Rev Time 0.00
Received By tklarge Date 2019-05-23 Time 10:18 Sent To  
Notes
2019-05-23 14:07:46SIGNATURE FOR THE IRRIGATION PLANS COULD NOT BE
 VERIFIED. T.LARGE
2019-05-02 12:54:145/1/19 HARD COPIES OF SOIL TEST AND ENERGY CALCS
 LOCATED IN LIBRARY. LEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-22 Cont ID  
Sent By jgomez Date 2019-04-22 Time 15:01 Rev Time 0.00
Received By jgomez Date 2019-04-22 Time 15:01 Sent To  
Notes
2019-04-22 15:01:45ALL SHEETS FOR THIS SUBMISSION WERE GOOD FOR SIGNATURE.
 ANY NEW SHEETS SUBMITTED FOR NEXT REVIEW WILL NEED TO
 BE CHECKED. WPB FBC 107.1
  
 SOIL TEST REPORT SUBMITTED DOESN'T HAVE A DIGITAL
 SIGNATURE. UPLOAD REPORT WITH ENGINEER'S DIGITAL
 SIGNATURE OR SUBMIT HARD COPIES WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
  
2019-04-17 14:24:58ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-01-29 Cont ID  
Sent By jpearson Date 2019-01-29 Time 08:59 Rev Time 0.00
Received By jpearson Date 2019-01-29 Time 08:59 Sent To  
Notes
2019-01-29 08:59:50ALL SHEETS FOR THIS SUBMISSION WERE GOOD FOR SIGNATURE.
 ANY NEW SHEETS SUBMITTED FOR NEXT REVIEW WILL NEED TO
 BE CHECKED. WPB FBC 107.1

Review Stop Z ZONING
Rev No 6 Status P Date 2019-08-29 Cont ID  
Sent By jroach Date 2019-08-29 Time 09:06 Rev Time 0.00
Received By jroach Date 2019-08-29 Time 09:06 Sent To  
Notes
2019-08-29 09:07:03PROVISOS:
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR
 THE PROPERTY...
 A. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN
 IN COMPLIANCE WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR) ARTICLE XIV, SHALL BE SUBMITTED TO
 THE BUILDING DIVISION FOR REVIEW.
 B. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION (502).
 C. THE IRRIGATION SHALL BE INSTALLED IN ACCORDANCE WITH
 THE APPROVED IRRIGATION PERMIT AND PASS A PLUMBING
 FINAL INSPECTION (703).
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 5 Status F Date 2019-07-16 Cont ID  
Sent By jroach Date 2019-07-16 Time 16:07 Rev Time 0.00
Received By jroach Date 2019-07-16 Time 16:07 Sent To  
Notes
2019-07-16 16:07:31AWAITING SIGNED/NOTARIZED CONDITIONAL PERMIT FORM FROM
 OWNER/CONTRACTOR. UPON RECEIPT OF SUCH FORM, THE ZONING
 STATUS WILL BE CHANGED TO PASSED, WITH THE FOLLOWING
 PROVISOS:
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR
 THE PROPERTY...
 A. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN
 IN COMPLIANCE WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR) ARTICLE XIV, SHALL BE SUBMITTED TO
 THE BUILDING DIVISION FOR REVIEW.
 B. AN IRRIGATION PERMIT SHALL BE SUBMITTED TO THE
 BUILDING DIVISION FOR REVIEW.
 C. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION (502).
 D. THE IRRIGATION SHALL BE INSTALLED IN ACCORDANCE WITH
 THE APPROVED IRRIGATION PERMIT AND PASS A PLUMBING
 FINAL INSPECTION (703).
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 4 Status F Date 2019-06-04 Cont ID  
Sent By jroach Date 2019-06-04 Time 14:13 Rev Time 0.00
Received By jroach Date 2019-06-04 Time 14:12 Sent To  
Notes
2019-06-04 14:15:16AWAITING SIGNED/NOTARIZED CONDITIONAL PERMIT FORM FROM
 OWNER/CONTRACTOR. UPON RECEIPT OF SUCH FORM, THE ZONING
 STATUS WILL BE CHANGED TO PASSED, WITH THE FOLLOWING
 PROVISOS:
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR
 THE PROPERTY...
 A. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN
 IN COMPLIANCE WITH THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR) ARTICLE XIV, SHALL BE SUBMITTED TO
 THE BUILDING DIVISION FOR REVIEW.
 B. AN IRRIGATION PERMIT SHALL BE SUBMITTED TO THE
 BUILDING DIVISION FOR REVIEW.
 C. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION (502).
 D. THE IRRIGATION SHALL BE INSTALLED IN ACCORDANCE WITH
 THE APPROVED IRRIGATION PERMIT AND PASS A PLUMBING
 FINAL INSPECTION (703).
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 3 Status F Date 2019-05-21 Cont ID  
Sent By jroach Date 2019-05-21 Time 11:32 Rev Time 0.00
Received By jroach Date 2019-05-21 Time 11:32 Sent To  
Notes
2019-05-21 11:34:25ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.21.2019
 PERMIT NO.: 18120892
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLANS DON?T MATCH THE SCOPE WORK THAT WAS SHOWN AND
 APPROVED WITH THE SITE PLAN APPROVAL. THE BUILDING
 PERMIT PLANS NEED TO MATCH WHAT WAS APPROVED.
 ADDITIONALLY, A SEPARATE LANDSCAPE PERMIT APPLICATION
 WILL NEED TO BE SUBMITTED TO THE BUILDING DEPARTMENT
 FOR INSTALLATION OF THE LANDSCAPE MATERIAL.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-04-23 Cont ID  
Sent By jroach Date 2019-04-23 Time 13:58 Rev Time 0.00
Received By jroach Date 2019-04-23 Time 13:58 Sent To  
Notes
2019-04-23 13:58:29ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.23.2019
 PERMIT NO.: 18120892
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SEC. 94-35(D) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS, ALL ADDITIONS EXCEEDING
 1,000 SQUARE FEET SHALL BE REVIEWED AND APPROVED
 THROUGH THE CITY'S SITE PLAN REVIEW PROCESS PRIOR TO
 THE ISSUANCE OF ANY BUILDING PERMITS. A COMPLETE
 DEVELOPMENT APPLICATION SHALL BE SUBMITTED TO THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-23 Cont ID  
Sent By jroach Date 2019-01-23 Time 11:39 Rev Time 0.00
Received By jroach Date 2019-01-23 Time 11:39 Sent To  
Notes
2019-01-23 11:40:09ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.23.2019
 PERMIT NO.: 18120892
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SEC. 94-35(D) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS, ALL ADDITIONS EXCEEDING
 1,000 SQUARE FEET SHALL BE REVIEWED AND APPROVED
 THROUGH THE CITY'S SITE PLAN REVIEW PROCESS PRIOR TO
 THE ISSUANCE OF ANY BUILDING PERMITS. A COMPLETE
 DEVELOPMENT APPLICATION SHALL BE SUBMITTED TO THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH