Plan Review Details - Permit 18120878
Plan Review Stops For Permit 18120878
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-29 Cont ID  
Sent By jpearson Date 2019-01-29 Time 15:24 Rev Time 0.00
Received By jpearson Date 2019-01-29 Time 15:24 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By jpearson Date 2019-01-15 Time 08:20 Rev Time 0.00
Received By jpearson Date 2019-01-15 Time 08:20 Sent To I
Notes
2019-01-15 08:20:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE AND PANEL A,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30;
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-01-29 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-25 Time 13:29 Sent To  
Notes
2019-01-28 13:30:09RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-01-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-11 Time 14:08 Sent To  
Notes
2019-01-14 14:08:12RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-01-02 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-26 Time 12:57 Sent To  
Notes
2018-12-27 12:57:14REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2019-01-29 Cont ID  
Sent By ccole Date 2019-01-14 Time 15:22 Rev Time 0.00
Received By jpearson Date 2019-01-14 Time 15:23 Sent To  
Notes
2019-01-29 15:24:13PLAN ALREADY APPROVED BY CHRIS COLE ON 1-14-19, BUT
 STOP COULD NOT BE DELETED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By ccole Date 2019-01-14 Time 16:17 Rev Time 0.00
Received By ccole Date 2019-01-14 Time 16:17 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By ccole Date 2019-01-02 Time 11:28 Rev Time 0.00
Received By ccole Date 2019-01-02 Time 11:20 Sent To I
Notes
2019-01-02 12:00:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120878
 1/2/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $3000.00 VALUE LISTED ON THE APPLICATION IS LOW
 FOR THE INSTALLATION OF A NEW 5-TON AC SYSTEM AND
 DUCTWORK. PERMIT VALUE IS BASED ON LABOR, MATERIALS,
 EQUIPMENT, SITE WORK, DESIGN FEES, AND OVER HEAD AND
 PROFIT PER SECTION 109.3 WPB. PLEASE PROVIDE A CONTRACT
 AND INVOICES TO VERIFY ACCURATE JOB VALUE.
  
 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY AIR
 SYSTEM OF THE NEW 5-TON AC SYSTEM PER SECTION 606.2.1
 FBC M.. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF
 THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 3) THE 500 CFMS OF AIR IN OFFICE 3 DOES NOT APPEAR TO
 BE CONSISTENT WITH THE AC CALULATIONS WHICH SHOWS THE
 COOLING LOADS TO BE THE SAME AS OFFICE 2. OFFICE 2 HAS
 ONLY 150 CFMS OF AIR PROVIDED.
  
 4) ENGINEERED WIND LOAD CALCULATIONS ARE REQUIRED FOR
 INSTALLATION OF THE ROOFTOP CONDENSER AND STAND-
 SECTION 301.15 FBC M. IN ADDITION PLEASE SUBMIT A FL.
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE CONDENSER
 STAND.
  
 5) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.2
 FBC M.
  
 6) PROVIDE AN ELECTRICAL PLAN AND AN ELECTRIC
 SUB-PERMIT- SECTION 107 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  