Plan Review Details - Permit 18120854
Plan Review Stops For Permit 18120854
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By rmcdouga Date 2019-02-07 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2019-02-07 Time 13:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-14 Cont ID  
Sent By rmcdouga Date 2019-01-14 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2019-01-14 Time 16:42 Sent To  
Notes
2019-01-14 18:57:421ST REVIEW FBC-2017 BUILDING
 PERMIT #18120854
 1/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COVER SHEET CONTAINS GENERAL NOTES AND PROJECT
 DATA THAT ARE ESSENTIAL TO THE PLANS AND IS PART OF THE
 CONSTRUCTION DOCUMENTS. THIS SHEET IS REQUIRED TO HAVE
 A TITLE BLOCK AND TO BE SIGNED AND SEALED BY THE
 DESIGNER OF RECORD. FBC 107.1 AND CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 2) THE DOOR TO SUITE 3 IS REQUIRED TO HAVE 18" PARALLEL
 TO THE DOORWAY BEYOND THE LATCH SIDE OF THE OPENING ON
 THE PULL SIDE OF THE DOOR FOR A FRONT APPROACH. FBC
 ACCESSIBILITY 404.2.4.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-14 Cont ID  
Sent By jpearson Date 2019-02-14 Time 07:31 Rev Time 0.00
Received By jpearson Date 2019-02-14 Time 06:59 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-01-09 Cont ID  
Sent By jpearson Date 2019-01-09 Time 07:53 Rev Time 0.00
Received By jpearson Date 2019-01-09 Time 07:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-31 Cont ID  
Sent By pleduc Date 2019-01-31 Time   Rev Time 0.00
Received By pleduc Date 2019-01-31 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-02 Cont ID  
Sent By pleduc Date 2019-01-02 Time   Rev Time 0.00
Received By pleduc Date 2019-01-02 Time 13:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-02-14 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-28 Time 15:01 Sent To  
Notes
2019-01-29 15:01:17B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-17 Cont ID  
Sent By jesmith Date 2019-01-17 Time 12:18 Rev Time 0.00
Received By jesmith Date 2019-01-17 Time 12:18 Sent To  
Notes
2018-12-27 13:04:37B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-01-14 Cont ID  
Sent By rmcdouga Date 2019-01-14 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2019-01-14 Time 16:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-02-13 Cont ID  
Sent By ccole Date 2019-02-13 Time 16:16 Rev Time 0.00
Received By ccole Date 2019-02-13 Time 14:56 Sent To E
Notes
2019-02-13 16:24:07MECHANICAL PROVISO:
  
 PROVIDE A REVISED MECHANICAL PLAN THAT INCLUDES:
  
 1) AIR BALANCE CALCULATION.
  
 2) AUTOMATIC OPERATION OF THE EXHAUST SYSTEMS WHEN THE
 SPACES ROOMS OR SPACES ARE IN USE.
  
 3) WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 ROOFTOP EXHAUST VENTILATORS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-10 Cont ID  
Sent By ccole Date 2019-01-10 Time 17:23 Rev Time 0.00
Received By ccole Date 2019-01-10 Time 17:23 Sent To  
Notes
2019-01-10 17:44:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120854
 1/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BEAUTY SALONS SHALL HAVE EXHAUST VENTILATION SYSTEMS
 SIZED AT A RATE OF 0.6 CFMS PER SF. PER TABLE 403.3.1.1
 FBC M. PLEASE REVISE THE PLANS TO MEET COMPLIANCE.
  
 2) SHEET M-2: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S PER SECTION
 606.2.1 FBC M. PLEASE PROVIDE SYMBOLS ON THE PLAN TO
 SHOW THE LOCATIONS.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE RTU'S AND CURBS- SECTION 301.15 FBC M.
  
 4) M-2: DRYER EXHAUST DUCTS SHALL BE EQUIPPED WITH
 BACKDRAFT DAMPERS, NOT MOTORIZED DAMPERS AS INDICATED
 IN NOTE #3- SECTION 504.4 FBC M.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS-
 SECTION 504.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By jesmith Date 2019-01-31 Time 10:14 Rev Time 0.00
Received By jesmith Date 2019-01-31 Time 10:08 Sent To  
Notes
2019-01-31 10:08:58APPROVED
 PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. T & P RELIEF LINE SHALL DISCHARGE TO THE HUB DRAIN
 THROUGH AN AIR GAP PER FBC PL 504.6(2)(10)

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-17 Cont ID  
Sent By jesmith Date 2019-01-17 Time 12:09 Rev Time 0.00
Received By jesmith Date 2019-01-17 Time 08:47 Sent To  
Notes
2019-01-17 12:08:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-1; SANITARY RISER. CORRECT ON PLAN
 AS NOTED BELOW PER WPB FBC 107.2.1.
 A.2" HUB DRAIN SERVICING THE WATER HEATER
 1) A P-TRAP REQUIRED PER FBC PL 1002.1.
 2) A SEPERATE VENT IS REQUIRED FOR THE TRAPPED FIXTURE
 DRAIN PER FBC PL 901.2.1 AND SECTION 909. LENGTH OF
 FIXTURE DRAIN SHALL COMPLY WITH FBC PL TABLE 909.1.
 PLEASE NOTE THAT THE PROVISIONS OF FBC PL 911 AND 912
 DO NOT APPLY TO THIS INSTALLATION.
 B. LAUNDRY
 1) FIXTURE BRANCH SERVICING THE TWO (2) CLOTHES WASHER
 FIXTURE DRAINS SHALL BE MINIMUM 3" SIZE PER FBC PL
 406.2.
 2) CLOTHES WASHER FIXTURE DRAINS AND TRAPSD SHALL BE
 MINIMUM 2" SIZE PER FBC PL 406.2 AND TABLE 709.1.
 3) UPSTREAM CLOTHES WASHER FIXTURE DRAIN IS S-TRAPPED
 WHICH IS PROHIBITED PER FBC PL 1002.3 (5). SHOW
 COMPLIANCE WITH FBC PL SECTION 909.
 C. SHAMPOO BACKWASH SINKS
 1) IDENTIFY EACH TRAP ON ISOMETRIC AS THE NOTED
 INTERCEPTOR, ZURN Z1175 PER WPB FBC 107.2.1.
  
 2. RE: PLAN SHEET P-1; WATER RISER ISOMETRIC. CORRECT
 ON PLAN AS NOTED BELOW PER WPB FBC 107.2.1.
 A. EXISTING WATER COLD WATER SERVICE/DISTRIBUTION
 APPEARS TO BE COMMON TO THE ENTIRE BUILDING. PROVIDE
 SIZING OF EXISTING COMMON SERVICE/DISTRIBUTION AND
 CALCULATIONS WHICH INCLUDE THE EXISTING USAGE IN THE
 BUILDING PER WPB FBC 107.2.1.
 B. SHOW THE FULL EXTENT OF THE HOT WATER RETURN LINE ON
 THE RISER DIAGRAM SHOWING COMPLIANCE WITH FBC PL 607.2
 PER WPB FBC 107.2.1.
 C. PROVIDE SHUT OFF VALVE FOR SERVICE INTO THE UNIT PER
 FBC 606.1.
  
 3. WATER HEATER
 A. PROVIDE A SCHEMATIC OF THE SPECIFIED BOTTOM FED
 WATER HEATER WITH RECIRC PUMP, EXPANSION TANK AND
 PIPING SHOWING ALL SIZING, VALVING (INCLUDING CHECK
 VALVES AND VACUUM RELIEF VALVE) AND PIPING
 INTERCONNECTIONS PER WPB FBC 107.2.1.
 B. PROVIDE SIZE OF EXPANSION TANK SHOWING COMPLIANCE
 WITH FBC PL 607.3 PER WPB FBC 107.2.1.
  
 4. PROVIDE A FIXTURE SCHEDULE WITH THE FOLLOWING
 INFORMATION PER WPB FBC 107.2.1.
 A. MANUFACTURER NAME AND MODEL # WITH NOTE "EQUAL TO".
 INCLUDE FAUCET FOR LAVATORY AND MOP SINK.INDICATE TYPE
 OF BACKFLOW PREVENTION TO PROVIDE FOR MOP SINK FAUCET.
 1) IF BY OWNER, THEN NOTE IN SCHEDULE. INDICATE THE
 TYPE OF BACKFLOW PREVENTION TO PROVIDE WHERE APPLICABLE
 IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL SECTION
 608. PLEASE NOTE THAT SUBMITTAL DATA FOR OWNER SUPPLIED
 EQUIPMENT COVERED UNDER THE PLUMBING SCOPE WILL HAVE TO
 BE SUBMITTED TO THE BUILDING DEPARTMENT AND APPROVED
 AND IN PLACE ON THE JOBSITE PRIOR TO FINAL INSPECTION.
 B. WATER USAGE OF FIXTURE
 C. ADA COMPLIANCE FOR THE WATER CLOSET, LAVATORY AND
 ELECTRIC WATER COOLER IN ACCORDANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6.
  
 5. PER WPB FBC 107.2.1, PROVIDE SCHEDULE AND SPEC FOR
 WATER HEATER AND RECIRC PUMP; INCLUDE ELECTRICAL
 CHARACTERISTICS OF THE EQUIPMENT.
  
 6. IS EXISTING TOILET ROOM ADA COMPLIANT? IF SO, THEN
 STATE ON THE PLANS AND SHOW TURNING RADIUS FOR
 WHEELCHAIR PER WPB FBC 107.2.1.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 1 Status P Date 2019-01-07 Cont ID  
Sent By mcruz Date 2019-01-07 Time 16:29 Rev Time 0.00
Received By mcruz Date 2019-01-07 Time 16:26 Sent To PC
Notes
***NONE***