Plan Review Details - Permit 18120746
Plan Review Stops For Permit 18120746
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 14:25 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 14:14 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 08:15 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 08:11 Sent To  
Notes
2019-02-01 08:42:52BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229. (PROVIDE SIGNATURE
 OF DESIGNER)
  
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017
 FLORIDA BUILDING CODE, 6TH EDITION.
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 1. PROVIDE PLAN SHOWING EXISTING CONDITIONS. (PROVIDE
 PLAN SHOW EXISTING CONDITIONS)
 2. PROVIDE PLAN SHOWING PROPOSED WORK. (PROVIDE PLAN
 SHOW ALL PROPOSED WORK)
 3. PROVIDE FLOOR PLAN WITH DEMENSIONS. IDENTIFY
 LOCATION OF ALL WORK. (PROVIDE DEMENSIONS ON PLAN)
 4. WORK DESCRIPTION ON APPLICATION STATES NEW DOORS,
 ELECTRICAL AND HVAC. NONE OF THESE ITEMS HAS BEEN
 ADDRESSED ON PLAN SUBMITTED. (PRODUCT APPROVALS AND
 LOCATION OF DOORS - OK/ CANNOT DETERMINE SCOPE OF
 ELECTRICAL WORK/ PLAN SHOWS NEW A/C - PROVIDE
 MECHANICAL PLAN AND MECHANICAL SUB-PERMIT/SCOPE OF WORK
 STATES NO NEW PLUMBING SUPPLY OR SANITARY LINES -
 SUBMITTAL INCLUDES WATER RISER DIAGRAHM AND MULTIPLE
 SANITARY RISER DIAGRAHMS THAT DO NOT MATCH FLOOR PLAN -
 PLEASE CLARIFY/ SPECIFICATIONS PROVIDED FOR TANKLESS
 WATER HEATER WITH LOCATION ON PLAN - PLUMBING
 SUB-PERMIT REQUIRED/ TRENCH DETAIL ON PLANS-WHERE WILL
 THIS BE USED-SHOW ON PLAN)
  
 NEW COMMENT
  
 5. VALUE - SCOPE OF WORK IS NOT CLEAR ENOUGH TO
 DETERMINE VALUE AT THIS TIME.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 ADVISORY
  
 F.S. 553.80 (2) (B)
 (B)?WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 PLEASE FEEL FREE TO CONTACT ME OR COME IN TO DISCUSS
 YOUR PROJECT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 16:11 Rev Time 0.00
Received By cthroop Date 2018-12-26 Time 12:29 Sent To  
Notes
2018-12-26 16:17:02BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE 2017
 FLORIDA BUILDING CODE, 6TH EDITION.
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 1. PROVIDE PLAN SHOWING EXISTING CONDITIONS.
 2. PROVIDE PLAN SHOWING PROPOSED WORK.
 3. PROVIDE FLOOR PLAN WITH DEMENSIONS. IDENTIFY
 LOCATION OF ALL WORK.
 4. WORK DESCRIPTION ON APPLICATION STATES NEW DOORS,
 ELECTRICAL AND HVAC. NONE OF THESE ITEMS HAS BEEN
 ADDRESSED ON PLAN SUBMITTED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 14:25 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 14:15 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 13:30 Sent To  
Notes
2019-02-15 14:18:03ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. OVERCURRENT PROTECTION FOR NEW TANKLESS WATER HEATER
 SHALL BE LIMITED TO 50 AMPS. PANEL SCHEDULE SHOWS 60
 AMP BREAKER.
 2. CANNOT VERIFY OVERCURRENT PROTECTION FOR NEW A/C
 CONDENSOR. PROVIDE MANUF. SPECS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 08:43 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 08:11 Sent To  
Notes
2019-02-01 08:44:13SEE COMMENTS UNDER BLDG. REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 16:17 Rev Time 0.00
Received By cthroop Date 2018-12-26 Time 12:29 Sent To  
Notes
2018-12-26 16:17:59SEE COMMENTS UNDER BLDG. REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 14:25 Rev Time 0.00
Received By cthroop Date 2019-03-04 Time 16:11 Sent To  
Notes
2019-03-05 16:11:54CTHROOP'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 14:20 Rev Time 0.00
Received By cthroop Date 2019-02-14 Time 09:41 Sent To  
Notes
2019-02-15 09:41:53RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 08:45 Rev Time 0.00
Received By cthroop Date 2019-01-28 Time 14:46 Sent To  
Notes
2019-01-29 14:46:34RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 16:18 Rev Time 0.00
Received By cthroop Date 2018-12-19 Time 13:31 Sent To  
Notes
2018-12-20 13:31:51R06

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 14:25 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 14:18 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 13:30 Sent To  
Notes
2019-02-15 14:20:12MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MANUFACTURERS SPECIFICATIONS FOR NEW A/C
 CONDENSOR AND AIR HANDLER. SPECIFY MODEL TO BE
 INSTALLED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 08:44 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 08:11 Sent To  
Notes
2019-02-01 08:44:46SEE COMMENTS UNDER BLDG. REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 16:17 Rev Time 0.00
Received By cthroop Date 2018-12-26 Time 12:29 Sent To  
Notes
2018-12-26 16:17:31SEE COMMENTS UNDER BLDG. REVIEW.

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-03-06 Cont ID  
Sent By cthroop Date 2019-03-06 Time 14:26 Rev Time 0.00
Received By cthroop Date 2019-03-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-02-15 Cont ID  
Sent By cthroop Date 2019-02-15 Time 14:20 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 13:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 08:44 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 08:11 Sent To  
Notes
2019-02-01 08:45:14SEE COMMENTS UNDER BLDG. REVIEW

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 16:18 Rev Time 0.00
Received By cthroop Date 2018-12-26 Time 12:30 Sent To  
Notes
2018-12-26 16:18:28SEE COMMENTS UNDER BLDG. REVIEW.