Plan Review Details - Permit 18120672
Plan Review Stops For Permit 18120672
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-11 Cont ID  
Sent By jgomez Date 2019-01-16 Time 18:48 Rev Time 0.00
Received By jgomez Date 2019-01-15 Time 11:28 Sent To  
Notes
2019-01-11 18:54:27ALTERATION, BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- UNDER THE 2017 FBC-EXISTING BUILDING CODE, THE
 DESIGNER OF RECORD HAS NOT LISTED WHICH METHOD THE
 PLANS WERE CREATED. 2017 FBC-EXISTING BUILDING CODE
 SECTION 301.1. THE ALTERATION, CHANGE OF OCCUPANCY,
 ADDITION OR RELOCATION OF ALL EXISTING BUILDINGS SHALL
 COMPLY WITH ONE OF THE METHODS LISTED IN SECTIONS
 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
  
 2- A) BASED ON FLOOR PLANS SUBMITTED, THERE IS ONLY ONE
 COMPLAINT EXIT FROM THIS STORY. SPIRAL STAIRS ARE NO
 CONSIDERED A COMPLAINT EXIT. BASED ON THE EGRESS TRAVEL
 DISTANCE, THIS OCCUPANCY IS REQUIRED TO HAVE 2 EXITS.
 SEE SEC. 801.3 FBC-EXISTING BUILDING AND SEC. 1006.3.1
 FBC. REVISE PLANS AS REQUIRED.
  
 NOTE: ARCHITECT MAY CONTACT ME IF THERE ARE ANY
 QUESTIONS REGARDING THIS ISSUE.
  
 B)PROVIDE LIFE SAFETY PLAN SHOWING THE EXIT ACCESS
 TRAVEL DISTANCE. SEE SEC. 1017.3 FBC.
  
 3- PROJECT DATA ON SHEET AO DOESN'T SPECIFY IF THIS
 BUILDING IS SPRINKLERED OR NOT. SEC. 107.3.5.1 CITY
 AMENDMENTS.
  
 4- THERE ARE MANY BUILDINGS IN THIS PROPERTY. PROVIDE
 PLOT PLAN SHOWING LOCATION OF BUILDING WHERE WORK IS
 TAKEN PLACE. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- REVISE OCCUPANCY LOADS INFORMATION ON SHEET A0:
 A) THIS BUILDING DOESN'T SEEM TO BE U-GROUP U (UTILITY
 AND MISCELLANEOUS) OCCUPANCY. SEE SEC. 312 FBC AND
 REVISE AS REQUIRED. THERE ARE NOT OFFICES IN UTILITY
 GROUPS. CLEARLY SPECIFY THE OCCUPANCY FOR THE FIRST AND
 SECOND FLOOR. CLARIFY IF THERE IS ANY MIXED
 OCCUPANCIES.
  
 B) REVISE OCCUPANT LOAD CALCULATIONS. SEE TABLE
 1004.1.2 FBC. TYPICALLY, CONFERENCE AREAS ARE
 CONSIDERED AS ASSEMBLY GROUP WITH UNCONCENTRATED TABLES
 AND CHAIRS AND SQUARE FOOTAGE OF 15 NET IS CONSIDERED
 FOR THE OCCUPANT LOAD.
  
 6- IT LOOKS LIKE NEW CONFERENCE AREA ARE BLOCKING THE
 CONTINUITY OF THE MEANS OF EGRESS PATH. REVISE AS
 REQUIRED. SEC. 1005.4 FBC.
  
 7- SPECIFY DIMENSION BETWEEN NEW OFFICES AND EXISTING
 STAIR "04" TO VERIFY COMPLIANCE WITH MANEUVERING AT
 DOORS SEC. FIGURE 404.2.4.1 FLORIDA ACCESSIBILITY CODE.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION SEEMS
 TO BE LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON
 PLANS. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE AS REQUIRED OR PROVIDE COPIES OF
 SIGNED CONTRACTS FOR BUILDING OFFICIAL APPROVAL.
  
 9-WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By jpearson Date 2019-01-02 Time 13:47 Rev Time 0.00
Received By jpearson Date 2019-01-02 Time 11:11 Sent To  
Notes
2019-01-02 13:47:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 2. PROVIDE LOAD CALCULATION FOR PANELS, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By pleduc Date 2018-12-20 Time   Rev Time 0.00
Received By pleduc Date 2018-12-20 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-16 Cont ID  
Sent By jgomez Date 2019-01-16 Time 16:57 Rev Time 0.00
Received By jgomez Date 2018-12-18 Time 14:34 Sent To I
Notes
2018-12-19 14:34:42B26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-01-10 Cont ID  
Sent By jgomez Date 2019-01-10 Time 12:37 Rev Time 0.00
Received By jgomez Date 2019-01-10 Time 12:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-07 Cont ID  
Sent By hmoser Date 2019-01-07 Time 10:53 Rev Time 0.00
Received By hmoser Date 2019-01-07 Time 10:07 Sent To  
Notes
2019-01-07 10:53:12PLAN DENIED
 1) PLEASE SHOW DUCT WORK ON AIR CONDITIONING PLAN
 SHOWING DUCT SIZE AND OUTSIDE AIR DUCT AND SIZE.
 2) NEW CONFERENCE ROOM SHOWS THREE SUPPLY DROPS
 AND ONE RETURN. REFER TO SECTION 601.6 BALANCED RETURN
 AIR
 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By jesmith Date 2019-01-15 Time 11:19 Rev Time 0.00
Received By jesmith Date 2019-01-15 Time 11:18 Sent To  
Notes
2019-01-15 11:19:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET A0; UPON REVIEW OF FBC SECTION 312,
 THE GROUP U (UTILITY AND MISCELLANEOUS) OCCUPANCY
 APPEARS TO BE INCORRECTLY APPLIED. PLEASE PROVIDE AN
 OCCUPANCY THAT ALLOWS REVIEW OF MINIMUM PLUMBING
 FACILITIES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC
 PL CHAPTER 4 PER WPB FBC 107.2.1.
 2. RE: NEW RESTROOM; PLAN SHEET D1.0 INDICATES TWO (2)
 EXISTING WATER CLOSETS. SCOPE OF WORK ADDRESSES REMOVAL
 AND REPLACEMENT OF ONE (1) EACH WATER CLOSET AND
 LAVATORY. IT APPEARS THAT THIS IS BASICALLY A
 REPLACEMENT OF EXISTING FIXTURES WITH MINOR
 MODIFICATION OF THE EXISTING LAVBATORY FIXTURE DRAIN,
 BUT THE DEMO DRAWING CLOUDS THE ACTUAL INTENT.PLEASE
 CLARIFY PER WPB FBC 107.2.1.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715