Plan Review Stops For Permit 18120645 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-03-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-18 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-14 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-15 |
Time |
08:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-05 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-01 |
Time |
17:10 |
Sent To |
|
|
Notes |
2019-02-05 10:07:40 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ROOFING - PROVIDE PRODUCT APPROVALS FOR PROPOSED | | ROOFING SYSTEM COMPONENTS. | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | 2. INTERIOR WALL ON PROPOSED FLOOR PLAN APPEARS TO | | TERMINATE IN AN EXISTING WINDOW. PLEASE CLARIFY. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 3. FACIA/OVERHANG DETAIL IS MISSING ON DETAIL 1, PLAN | | PAGE S02. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 4. PROVIDE ROOF FRAMING PLAN. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 5. PROVIDE ENERGY CALCULATIONS. CANNOT VERIFY R-19 | | CEILING INSULATION IS ADEQUATE. | | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 | | STORIES. ENERGY | | | | 6. IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT | | FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY | | CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR | | REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE | | RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE | | OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO | | V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN | | AIRE.PDF | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-03-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-18 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-14 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-15 |
Time |
08:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2019-02-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-02-01 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-02-01 |
Time |
10:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-03-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-18 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-13 |
Time |
11:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-02-22 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-13 |
Time |
16:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-02-12 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2019-02-12 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-01-11 |
Time |
10:35 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2019-02-26 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-02-26 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-02-25 |
Time |
09:24 |
Sent To |
|
|
Notes |
2019-02-26 11:08:41 | RECEIPT MU-2019-005773-0000 - $0.00 PAID | 2019-02-25 09:25:15 | 2/25/19 SENT TO IMPACT FEE REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-05 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-01 |
Time |
17:11 |
Sent To |
|
|
Notes |
2019-02-05 10:08:16 | IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2019-03-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-18 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-14 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2019-02-22 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-15 |
Time |
08:30 |
Sent To |
|
|
Notes |
2019-02-22 08:21:14 | MECHANICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE MECHANICAL PLAN. | | 2. DEMONSTRATE HOW THE NEW HABITABLE SPACE SHALL BE | | HEATED PER FBC R303.10. | | | | R303.10 REQUIRED HEATING. | | | | DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES - | | WINTER | | | | FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION | | R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN | | TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C), | | EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING | | FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF | | NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM) | | ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS | | IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE | | INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS | | SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS | | SECTION. | | | | TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR | | DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE | | COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??. | | | | 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS, | | SECTION 1101.1 SCOPE. ?AN ADDITION TO A BUILDING OR | | STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE | | AS ADOPTED FOR NEW CONSTRUCTION?? | | | | SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM | | REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR | | STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, ENERGY. | | | | 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS, | | SECTION R502 ADDITIONS, ?ADDITIONS TO AN EXISTING | | BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL | | CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE | | PROVISIONS RELATE TO NEW CONSTRUCTION??. | | SECTION R502.1.1.2 HEATING AND COOLING SYSTEMS. NEW | | HEATING, COOLING AND DUCT SYSTEMS THAT ARE PART OF THE | | ADDITION SHALL COMPLY WITH SECTIONS R403.1, R403.2, | | R403.3, R403.5 AND R403.6. | | | | FBC PLUMBING, APPENDIX D, DEGREE DAY AND DESIGN | | TEMPERATURES, TABLE D101, DESIGN TEMPERATURE, WINTER, | | 97 ?% = 45 DEGREES DESIGN TEMP. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-05 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-01 |
Time |
17:11 |
Sent To |
|
|
Notes |
2019-02-05 10:11:06 | MECHANICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE MECHANICAL PLAN. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. PROVIDE ENERGY CALCULATIONS. | | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 | | STORIES. ENERGY | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2019-01-26 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-26 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-26 |
Time |
10:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-15 |
Time |
08:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-05 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-05 |
Time |
08:53 |
Sent To |
|
|
Notes |
2019-02-05 10:15:43 | ROOFING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM | | COMPONENTS. | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2019-03-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-18 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-14 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-02-22 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-15 |
Time |
08:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-05 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-01 |
Time |
17:11 |
Sent To |
|
|
Notes |
2019-02-05 10:13:41 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-02-19 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2019-02-19 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-02-19 |
Time |
13:53 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2019-02-12 |
|
|
Cont ID |
|
Sent By |
mcurz |
Date |
2019-02-12 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-02-12 |
Time |
10:00 |
Sent To |
PC |
|
Notes |
|
|