Plan Review Details - Permit 18120645
Plan Review Stops For Permit 18120645
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-18 Cont ID  
Sent By cthroop Date 2019-03-18 Time 08:48 Rev Time 0.00
Received By cthroop Date 2019-03-14 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-22 Cont ID  
Sent By cthroop Date 2019-02-22 Time 08:09 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 10:00 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 17:10 Sent To  
Notes
2019-02-05 10:07:40BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING - PROVIDE PRODUCT APPROVALS FOR PROPOSED
 ROOFING SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 2. INTERIOR WALL ON PROPOSED FLOOR PLAN APPEARS TO
 TERMINATE IN AN EXISTING WINDOW. PLEASE CLARIFY.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. FACIA/OVERHANG DETAIL IS MISSING ON DETAIL 1, PLAN
 PAGE S02.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PROVIDE ROOF FRAMING PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. PROVIDE ENERGY CALCULATIONS. CANNOT VERIFY R-19
 CEILING INSULATION IS ADEQUATE.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 6. IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-03-18 Cont ID  
Sent By cthroop Date 2019-03-18 Time 08:48 Rev Time 0.00
Received By cthroop Date 2019-03-14 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-22 Cont ID  
Sent By cthroop Date 2019-02-22 Time 08:09 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-02-01 Cont ID  
Sent By jleahy Date 2019-02-01 Time 10:05 Rev Time 0.00
Received By jleahy Date 2019-02-01 Time 10:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-18 Cont ID  
Sent By cthroop Date 2019-03-18 Time 08:48 Rev Time 0.00
Received By cthroop Date 2019-03-13 Time 11:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-22 Cont ID  
Sent By cthroop Date 2019-02-22 Time 08:10 Rev Time 0.00
Received By cthroop Date 2019-02-13 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-12 Cont ID  
Sent By mcruz Date 2019-02-12 Time 10:26 Rev Time 0.00
Received By mcruz Date 2019-01-11 Time 10:35 Sent To PC
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By lmarchan Date 2019-02-26 Time 11:08 Rev Time 0.00
Received By lmarchan Date 2019-02-25 Time 09:24 Sent To  
Notes
2019-02-26 11:08:41RECEIPT MU-2019-005773-0000 - $0.00 PAID
2019-02-25 09:25:152/25/19 SENT TO IMPACT FEE REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 10:07 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 17:11 Sent To  
Notes
2019-02-05 10:08:16IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-18 Cont ID  
Sent By cthroop Date 2019-03-18 Time 08:48 Rev Time 0.00
Received By cthroop Date 2019-03-14 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-02-22 Cont ID  
Sent By cthroop Date 2019-02-22 Time 08:14 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 08:30 Sent To  
Notes
2019-02-22 08:21:14MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MECHANICAL PLAN.
 2. DEMONSTRATE HOW THE NEW HABITABLE SPACE SHALL BE
 HEATED PER FBC R303.10.
  
 R303.10 REQUIRED HEATING.
  
 DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES -
 WINTER
  
 FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION
 R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
 NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR
 DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE
 COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??.
  
 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS,
 SECTION 1101.1 SCOPE. ?AN ADDITION TO A BUILDING OR
 STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE
 AS ADOPTED FOR NEW CONSTRUCTION??
  
 SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM
 REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR
 STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, ENERGY.
  
 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS,
 SECTION R502 ADDITIONS, ?ADDITIONS TO AN EXISTING
 BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL
 CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE
 PROVISIONS RELATE TO NEW CONSTRUCTION??.
 SECTION R502.1.1.2 HEATING AND COOLING SYSTEMS. NEW
 HEATING, COOLING AND DUCT SYSTEMS THAT ARE PART OF THE
 ADDITION SHALL COMPLY WITH SECTIONS R403.1, R403.2,
 R403.3, R403.5 AND R403.6.
  
 FBC PLUMBING, APPENDIX D, DEGREE DAY AND DESIGN
 TEMPERATURES, TABLE D101, DESIGN TEMPERATURE, WINTER,
 97 ?% = 45 DEGREES DESIGN TEMP.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 10:08 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 17:11 Sent To  
Notes
2019-02-05 10:11:06MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE MECHANICAL PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE ENERGY CALCULATIONS.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES. ENERGY
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2019-01-26 Cont ID  
Sent By gjohnson Date 2019-01-26 Time 10:58 Rev Time 0.00
Received By gjohnson Date 2019-01-26 Time 10:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2019-02-22 Cont ID  
Sent By cthroop Date 2019-02-22 Time 08:09 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 08:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 10:13 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 08:53 Sent To  
Notes
2019-02-05 10:15:43ROOFING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR NEW ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-03-18 Cont ID  
Sent By cthroop Date 2019-03-18 Time 08:48 Rev Time 0.00
Received By cthroop Date 2019-03-14 Time 14:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-22 Cont ID  
Sent By cthroop Date 2019-02-22 Time 08:09 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 10:11 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 17:11 Sent To  
Notes
2019-02-05 10:13:41BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-02-19 Cont ID  
Sent By mcruz Date 2019-02-19 Time 13:53 Rev Time 0.00
Received By mcruz Date 2019-02-19 Time 13:53 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-02-12 Cont ID  
Sent By mcurz Date 2019-02-12 Time 10:26 Rev Time 0.00
Received By mcruz Date 2019-02-12 Time 10:00 Sent To PC
Notes
***NONE***