Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By ccole Date 2019-01-02 Time 09:42 Rev Time 0.00
Received By ccole Date 2019-01-02 Time 08:44 Sent To I
Notes
2019-01-02 10:19:331ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120488
 1/2/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A FRONT ELEVATION VIEW OF THE HOOD AND
 COOKING APPLIANCES SHOWING THE REQUIRED CLEARANCES AS
 REQUIRED BY SECTION 507.4.1 FBC M.
  
 2) CLARIFY IF THE COOKING APPLIANCES UNDER THE HOOD ARE
 NEW OR EXISTING. PLEASE NOTE A SEPARATE PERMIT WILL BE
 REQUIRED FOR INSTALLATION OF ALL NEW APPLIANCES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE FACTORY-BUILT GREASE
 DUCT IN ACCORDANCE WITH THE ENGINEER'S RECOMMENDATIONS
 ON SHEET #2- SEE SECTIONS 506.3.1.1 AND 506.3.11.3 FBC
 M. INDICATE THE MINIMUM CLEARANCE ALLOWED FROM THE
 GREASE DUCT TO THE COMBUSTIBLE ROOF MATERIALS.
  
 4) PROVIDE STRUCTURAL DETAILS FOR THE NEW ROOF OPENING
 AND THE GURARD RAIL CONSTRUCTION- "BY OTHERS" IS NOT
 ACCEPTABLE FOR PERMITTING- PROVIDE ENGINEERED DRAWINGS
 AND A SUBPERMIT APPLICATION- SECTION 107.2.1 WPB.
  
 5) PROVIDE A ROOF PLAN THAT SHOWS THE LOCATIONS OF THE
 FANS AND THE GUARD RAIL, AND THE FULL RUN LENGTH OF THE
 RAIL PER SECTION 304.11 FBC M.
  
 6) REFER TO SECTION 508.1.1 FBC M AND SHOW COMPLIANCE.
 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 7) SUBMIT THE NOA'S FOR THE FANS LISTED ON SHEET #4
  
 8) THE $11,000 JOB VALUE LISTED ON THE APPLICATION
 APPEARS LOW FOR THE ENTIRE SCOPE OF WORK. PLEASE
 PROVIDE COPIES OF CONTRACTS, INVOICES ETC. TO VERIFY
 ACCURATE VALUE- SECTION 109.3. PLEASE NOTE THAT VALUE
 IS BASED ON LABOR, MATERIALS, EQUIPMENT, SITE WORK,
 DESIGN FEES, AND OVERHEAD AND PROFIT.
  
 9) COPIED ENGINEER'S SEALS AND SIGNATURES ARE NOT
 ACCEPTABLE PER SECTION 61G15-23.002 FAC. PLEASE PROVIDE
 ORIGNAL SIGNED AND SEALED PLANS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  