Plan Review Details - Permit 18120471
Plan Review Stops For Permit 18120471
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-28 Cont ID  
Sent By jgomez Date 2018-12-28 Time 09:24 Rev Time 0.00
Received By jgomez Date 2018-12-28 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-13 Cont ID  
Sent By rmcdouga Date 2018-12-13 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2018-12-13 Time 18:26 Sent To I
Notes
2018-12-13 18:46:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VULT WINDSPEED FOR CATEGORY II BUILDINGS IN WEST
 PALM BEACH IS 170 MPH. FBC 1604.5 AND 1609.1.1
  
 2) THE DEFAULT EXPOSURE CATEGORY IS C. IF YOU WANT TO
 USE EXPOSURE CATEGORY B, SUBMIT AN ANALYSIS REPORT FROM
 A FLORIDA LICENSED ENGINEER. FBC 1609.4.3
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-28 Cont ID  
Sent By jgomez Date 2018-12-28 Time 09:24 Rev Time 0.00
Received By jgomez Date 2018-12-26 Time 12:36 Sent To I
Notes
2018-12-27 12:36:21RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-13 Cont ID  
Sent By rmcdouga Date 2018-12-13 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2018-12-13 Time 16:22 Sent To  
Notes
2018-12-13 16:22:08RMCDOUGAL